Trane manual Direct-Fired Indoor and Outdoor Units MUA-SVP01A-EN

Page 28

Diagnostics

SOLUTION: If burner was not operating prior to shutdown (check prior alarm log)

1.Is there a prior alarm such as Safety Ckt., Airflow Sw., or Flame Failure?

Yes. See the Diagnostic section for the previous alarm.

No. Continue.

2.Is the room air (Room Temp) displayed on the BACview remote, reading 150°F or more?

Yes. The sensor circuit or the sensor itself is shorted. Unplug the input jack from the AdaptAire controller. Did the display change to -40°F or less?

No. There is a short in the controller input. Replace the controller.

Yes. Disconnect the sensor wiring at the sensor. Connect an ohmmeter to the sensor. If it is shorted replace the sensor. At 70°F the resistance should be 10K?. See thermistor output curve for other temperatures. If it is not shorted, there is a short in the wiring between the sensor and the input plug. Determine cause and rectify. Refer to Appendix II for a typical 10K? thermistor output curve.

No. Continue.

3.Is the discharge air temperature (DA Tempt), displayed on the BACview remote, reading -40°F or less?

Yes. The discharge air temperature sensor circuit or the sensor itself is open. Jumper the input for the sensor. Did the display change to 150°F or more?

No. There is an open in the controller input. Replace the controller.

Yes. Disconnect the discharge air temperature sensor wiring at the sensor. Connect an ohmmeter to the sensor. If it is open replace the sensor. At 70°F the resistance should be 10K?. See thermistor output curve for other temperatures. If it is not open, there is a break in the wiring between the sensor and the input plug. Determine cause and rectify.

No. Continue

4.Reset the alarm. Check and note the DC voltage at controller's analog output for the heating signal. Set the Heating Setpoint for 90°F. Set the HTG MAX DA and HTG MIN DA Setpoints for 130°F. Did the Burner VDC, displayed on the BACview remote, increase?

No. Unless the outside air temperature is extremely warm the Burner VDC should have increased to 7.5VDC or more. Close the manual main gas valve closest to the burner and measure the discharge air temperature. Is it less than 130°F?

Yes. There is a problem with the controller program or controller itself. Contact the factory.

No. The outside air temperature is too hot to determine the actual cause of the problem. Reset the alarm and recheck when the outside air temperature is much cooler.

28

Direct-Fired Indoor and Outdoor Units • MUA-SVP01A-EN

Image 28
Contents Controls Programming Guide JanuaryOverview Networking Direct-Fired Indoor and Outdoor Units MUA-SVP01A-EN Contents Contents Unit Operating Modes MDT ControlsMRT Controls MRT-Pro ControlsUnit Operating Modes MRT-Expert Controls Unit Operating Modes Heating/Ventilating/Cooling Operating Modes Heating ModeGeneral Burner Control Unit Operating Modes Ventilation Mode Cooling Mode M P E R a T U R E S EManual Mode Damper Control ModesMixed Air Temperature Mode Building Pressure Mode Functions 100% Outside AirMinimum Ventilation FreezestatUser Configured PID Control Direct Acting85ºF Reverse Acting Direct actingReverse acting Unit Resets Multiplexed InputsClock Set Critical Fault Codes DiagnosticsFault Code Low Discharge Temperature Diagnostics Direct-Fired Indoor and Outdoor Units MUA-SVP01A-EN Fault Code Safety Circuit Open Fault CODEBurner Status SOLUTIONIf fan is running check prior alarm logFault Code Burner Hand Diagnostics Non-Critical Fault Codes Fault Code Flame FailureSolution If fan is running Fault Code Unit off/Fan onSolution If fan is not running SOLUTIONIf fan/motor is running Fault CODEUnit on/Fan offSolution If fan/motor is not running Fault Code Check Airflow Switches Fault Code Clogged Filter Switch SOLUTIONIf clogged filter switch is closingFault CODEEnergy Save Mode SOLUTIONIf setpoints are misadjustedSOLUTIONIf setpoints are not misadjusted Solution If OAT, RoomT or DAT are such that heat is requiredDiagnostics Solution If setpoints are misadjusted Fault CODEInsufficient OASOLUTIONIf heat is desired SOLUTIONIf less outside air is desired Diagnostics Menu Selection Tree for BACview Menu SelectionUnit Modes Hotkey Menu Selection SET Points HotkeyAlarm Hotkey Resets HotkeyAlarm History 64 Most Recent Status Menu HotkeyUser Configurable Output Hotkey Schedules HotkeyClockset Hotkey Help HotkeyFuel Select Hotkey Thermostat Output Curve Ohms Thermistor Output CurveAirflow Station Layout Airflow station layoutZone 583 Controller Specifications Network CommunicationZone 583 Controller Specifications Rnet MRT-Pro or Room Air sensorTypical Wiring Schematic Non-recirculating with evap Dfoa and Dfia model diagramTypical Wiring Schematic Recirculating Dfoa and Dfia model diagrams Recirculating Dfoa and Dfia model diagram Typical Wiring Schematic Trane