Trane Direct-Fired Indoor and Outdoor Make-Up Air Units, MUA-SVP01A-EN manual Reverse acting

Page 23

Functions

pressure to be+0.03" but does not want it to drop below 0.0" or go above +0.05". The parameters entered on the keypad display will be:

PID Select

Reverse (as input increases output decreases)

High Input Val

.10

Low Input Val

-0.10

User Ctrl SP

0.03

Max User SP

0.05

Min User SP

0.00

The pressure transducer compares the pressure outside the space to the pressure inside the space and transmits a corresponding signal to the AdaptAire controller. The controller compares this signal to the desired user control setpoint (0.03") and uses the PID loop to modulate the output from 0-100% (0- 10Vdc). The output is connected to the VFD that changes speed to maintain the specified building pressure.

If the building pressure is 0.03", the output from the controller will be determined by the PID control sequence, and the override will have no effect on the output.

If the building pressure is more than 0.03", the output from the controller will be determined by the PID control sequence or the override whichever is less.

If the building pressure is less than 0.03", the output from the controller will be determined by the PID control sequence or the override whichever is more.

Figure 3. Reverse acting

Max User SP

User Ctrl SP

.05” 0%

override

scaler

.03” 100%

.03” PID 0-100%

.03” 0%

override

scaler

Input > .03”?

>

0-100%

=

Output

<

 

Input < .03”?

Min User SP

.00” 100%

MUA-SVP01A-ENDirect-Fired Indoor and Outdoor Units

23

Image 23
Contents January Controls Programming GuideOverview Networking Direct-Fired Indoor and Outdoor Units MUA-SVP01A-EN Contents Contents MDT Controls Unit Operating ModesMRT-Pro Controls MRT ControlsUnit Operating Modes MRT-Expert Controls Unit Operating Modes General Burner Control Heating ModeHeating/Ventilating/Cooling Operating Modes Unit Operating Modes Ventilation Mode M P E R a T U R E S E Cooling ModeDamper Control Modes Manual ModeMixed Air Temperature Mode Building Pressure Mode Freezestat Functions100% Outside Air Minimum VentilationDirect Acting User Configured PID Control85ºF Direct acting Reverse ActingReverse acting Multiplexed Inputs Unit ResetsClock Set Fault Code Low Discharge Temperature DiagnosticsCritical Fault Codes Diagnostics Direct-Fired Indoor and Outdoor Units MUA-SVP01A-EN Fault Code Safety Circuit Open SOLUTIONIf fan is running check prior alarm log Fault CODEBurner StatusFault Code Burner Hand Fault Code Flame Failure Diagnostics Non-Critical Fault CodesSolution If fan is not running Fault Code Unit off/Fan onSolution If fan is running Solution If fan/motor is not running Fault CODEUnit on/Fan offSOLUTIONIf fan/motor is running Fault Code Check Airflow Switches SOLUTIONIf clogged filter switch is closing Fault Code Clogged Filter SwitchSOLUTIONIf setpoints are misadjusted Fault CODEEnergy Save ModeSolution If OAT, RoomT or DAT are such that heat is required SOLUTIONIf setpoints are not misadjustedDiagnostics SOLUTIONIf heat is desired Fault CODEInsufficient OASolution If setpoints are misadjusted SOLUTIONIf less outside air is desired Diagnostics Unit Modes Hotkey Menu SelectionMenu Selection Tree for BACview SET Points Hotkey Menu SelectionStatus Menu Hotkey Alarm HotkeyResets Hotkey Alarm History 64 Most RecentSchedules Hotkey User Configurable Output HotkeyHelp Hotkey Clockset HotkeyFuel Select Hotkey Ohms Thermistor Output Curve Thermostat Output CurveAirflow station layout Airflow Station LayoutNetwork Communication Zone 583 Controller SpecificationsRnet MRT-Pro or Room Air sensor Zone 583 Controller SpecificationsNon-recirculating with evap Dfoa and Dfia model diagram Typical Wiring SchematicTypical Wiring Schematic Recirculating Dfoa and Dfia model diagrams Recirculating Dfoa and Dfia model diagram Typical Wiring Schematic Trane