Trane MUA-SVP01A-EN manual Reverse Acting, Direct acting

Page 22

Functions

Figure 2. Direct acting

Max User SP

User Ctrl SP

80ºF 100%

override

scaler

75ºF 0%

75ºF PID 0-100%

75ºF 100%

override

scaler

>

0-100%

=

Output

<

 

Min User SP

70ºF 0%

REVERSE ACTING

The controller output AO-1 is modulated by a PID loop from 0% to 100% based on the User Control setpoint and the input signal to IN-9. As the input signal increases the output voltage decreases. Additionally, a secondary control acts to override the PID loop to scale the output as follows.

If the input variable equals the User Control setpoint, the output will be determined by the PID loop. In this situation the override has no effect on the output value.

If the input variable is above the User Control setpoint, the output could decrease from 100% to 0% as the input variable increases from the User Control setpoint to the Max User setpoint. In this situation the output value is the lesser of the PID output or the override output.

If the input variable is below the User Control setpoint, the output could increase from 0% to 100% as the input variable decreases from the User Control setpoint to the Min User setpoint. In this situation the output value is the greater of the PID output or the override output. See the following example.

Assume the user wishes to control the fan speed using a variable frequency drive (VFD). The VFD input is 0-10Vdc. The control variable will be building pressure. As the building pressure increases, the fan speed should decrease. The building pressure transducer has a range of -0.1" to +0.1". The user would like the building

22

Direct-Fired Indoor and Outdoor Units • MUA-SVP01A-EN

Image 22
Contents Controls Programming Guide JanuaryOverview Networking Direct-Fired Indoor and Outdoor Units MUA-SVP01A-EN Contents Contents Unit Operating Modes MDT ControlsMRT Controls MRT-Pro ControlsUnit Operating Modes MRT-Expert Controls Unit Operating Modes Heating/Ventilating/Cooling Operating Modes Heating ModeGeneral Burner Control Unit Operating Modes Ventilation Mode Cooling Mode M P E R a T U R E S EManual Mode Damper Control ModesMixed Air Temperature Mode Building Pressure Mode Minimum Ventilation Functions100% Outside Air FreezestatUser Configured PID Control Direct Acting85ºF Reverse Acting Direct actingReverse acting Unit Resets Multiplexed InputsClock Set Critical Fault Codes DiagnosticsFault Code Low Discharge Temperature Diagnostics Direct-Fired Indoor and Outdoor Units MUA-SVP01A-EN Fault Code Safety Circuit Open Fault CODEBurner Status SOLUTIONIf fan is running check prior alarm logFault Code Burner Hand Diagnostics Non-Critical Fault Codes Fault Code Flame FailureSolution If fan is running Fault Code Unit off/Fan onSolution If fan is not running SOLUTIONIf fan/motor is running Fault CODEUnit on/Fan offSolution If fan/motor is not running Fault Code Check Airflow Switches Fault Code Clogged Filter Switch SOLUTIONIf clogged filter switch is closingFault CODEEnergy Save Mode SOLUTIONIf setpoints are misadjustedSOLUTIONIf setpoints are not misadjusted Solution If OAT, RoomT or DAT are such that heat is requiredDiagnostics Solution If setpoints are misadjusted Fault CODEInsufficient OASOLUTIONIf heat is desired SOLUTIONIf less outside air is desired Diagnostics Menu Selection Tree for BACview Menu SelectionUnit Modes Hotkey Menu Selection SET Points HotkeyAlarm History 64 Most Recent Alarm HotkeyResets Hotkey Status Menu HotkeyUser Configurable Output Hotkey Schedules HotkeyClockset Hotkey Help HotkeyFuel Select Hotkey Thermostat Output Curve Ohms Thermistor Output CurveAirflow Station Layout Airflow station layoutZone 583 Controller Specifications Network CommunicationZone 583 Controller Specifications Rnet MRT-Pro or Room Air sensorTypical Wiring Schematic Non-recirculating with evap Dfoa and Dfia model diagramTypical Wiring Schematic Recirculating Dfoa and Dfia model diagrams Recirculating Dfoa and Dfia model diagram Typical Wiring Schematic Trane