Siemens SIMATICS PCS7 brochure Operating modes

Page 19

© Siemens AG 2011

Operating modes

The communication mode between the control center and outstation (RTU) depends on the support provided by the tele- control protocol, the configuration of the telecontrol commu- nication, and the type of WAN.

The SINAUT ST 7 telecontrol protocol supports the following operating modes:

Polling

-Control of data exchange by the TIM module of the con- trol center

-The TIM of the control center calls the outstations and node stations one after the other

-Stations with modified data (since the last transmission) send this when called

-Stations without modified data only acknowledge the call

-Transmission of control center data for the stations in between the calls

-Data exchange using internode communication between the stations is possible via the polling TIM of the control center

Polling with time slot procedure

-Operating mode for a radio network with division of the radio frequency between several providers

-Typically 6 s/min (time slot) for each provider for data exchange

-Data exchange during the time slot is carried out as described under "Polling"

-Following the data exchange, the frequency swaps to the next provider

-Data exchange using internode communication between the stations is possible via the polling TIM of the control center

-Control of the polling TIM by DCF77 or GPS radio-con- trolled clock for exact observation of the time slot

Multi-master polling with time slot procedure

-Operating mode for communication between outsta- tions and more than one control center via dedicated line or radio network

-Each control center is assigned one or more time slots per minute for polling

-Separate data buffer for each control center in the sta- tions (including node stations)

-Data exchange using internode communication between the stations is possible via the polling TIM of the active control center

-Redundant internode communication is possible; upon failure of the preferred control center, internode commu- nication is carried out via the TIM of the alternative con- trol center

-Each TIM of the control centers involved must be con- trolled by means of a DCF77 or GPS radio-controlled clock for exact observation of the time slot

Spontaneous mode in dial-up networks

-Data from outstations and node stations can be assigned priorities for transmission in the dial-up network: normal, high, alarm

-Immediate establishment of a dial-up connection for data with alarm priority or high priority; priority trans- mission of alarm frames

-Intermediate storage of data with normal priority; trans- mission during the next dial-up connection with the part- ner in the original chronological order (FIFO principle)

-Transmitted data from the control center always has high priority

-Data exchange possible between the stations with direct internode communication

Spontaneous mode in the TCP/IP-based WAN

-Establishment of a permanent S7 connection between two TIMs or between TIM and control center

-Exchange of SINAUT ST7-specific data packets via this

S7 connection using S7 communication functions with application of the TCP/IP transport protocol

-If the data transmission costs are related to the data quantity, processing is carried out with priority as with spontaneous mode for dial-up networks: immediate transmission of data with high priority and alarm priority (latter with priority); collection of data with normal prior- ity and transmission in larger blocks

-If the data quantity is not cost-relevant, all data is trans- mitted immediately to the respective partner, i.e. with- out intermediate storage. Message frames with alarm priority then have priority.

SINAUT ST7 telecontrol protocol 19

Image 19
Contents Simatic PCS Totally Integrated Automation Totally Integrated AutomationContents Simatic PCS 7 TeleControl Simatic PCS 7 TeleControlProcess control system with integral telecontrol center Automation of widely spread process plantsOil and gas industries Typical application areasWater industry Communication with the outstations remote terminal units Simatic PCS 7 TeleControl system architectureSystem overview Integration in process control EngineeringSimatic S7-300/S7-300F controllers Outstations remote terminal unitsSimatic S7-400/S7-400F controllers Spectrum of outstations and integration versions Combinations of basic topologies and media versions TopologiesBasic topologies Media versionsDual-channel operation Simatic PCS 7 TeleControl system componentsPCS 7 TeleControl Operator System Single-user and multi-user systemsLong-term archiving and logging Data Base Automation DBA PCS 7 TeleControl engineering stationSimatic PCS 7 TeleControl blocks RTU Large Simatic S7-400/S7-400F controller Remote terminal unitsPossible tele Information points RTU Medium Simatic S7-300/S7-300F controllerGeneral/elementary telecontrol functions Telecontrol protocolsSinaut ST7 telecontrol protocol Sinaut ST7 telecontrol protocolRange without repeaters example Classic WAN mediaRedundant transmission path TCP/IP-based WAN mediaTechnological configuration with Simatic water library Special characteristics Sinaut ST7 communicationOperating modes 20 DNP3 telecontrol protocol DNP3 telecontrol protocolScalance DNP3 telecontrol protocol22 DNP3 telecontrol protocol Special characteristics of DNP3 communicationIEC 870-5-101/IEC 870-5-104 telecontrol protocol IEC 870-5-101/IEC 870-5-104 telecontrol protocolTCP/IP-based WAN media IEC 870-5-104 telecontrol protocol Classic WAN media IEC 870-5-101 telecontrol protocolRTU ET 200S Modbus telecontrol protocol Modbus telecontrol protocolIncreasing the plant availability RedundancyRedundancy Third-party stations MigrationMigration of existing telecontrol systems Units with Modbus communicationSinaut LSX systems Integration of third-party stations with OPCLinking of Siprotec or third-party protection equipment Application examples Application examplesUniform automation of all stations in the gas network High system availability resulting from redundancyCost-effective RTUs exactly matched to the respective unit Reporting and archiving in compliance withAdditional information