Lincoln Electric IM602-A manual Reconnect Procedure, Input Power Supply Connections

Page 13

A-4

INSTALLATION

A-4

INPUT POWER SUPPLY CONNECTIONS

A qualified electrician should connect the input power supply leads.

1.Follow all national and local electrical codes.

2.Use a three-phase line.

3.Remove the input access door at upper rear of the machine.

4.Follow input supply connection diagram located on the inside the door. For multiple voltage machines, follow the diagram for the voltage that is within 10% of your actual input line voltage.

5.Connect the three-phase AC power supply leads L1, L2, and L3 to the input contactor terminals in the input box assembly. See Figure A.1.

RECONNECT PROCEDURE

WARNING

Electric Shock Can Kill

Disconnect input power before perform- ing this procedure.

------------------------------------------------------------------------

Multiple voltage machines are shipped connected to the highest input voltage listed on the machine’s rating plate. Before installing the machine, check that the reconnect panel in the input box assembly is connect- ed for the proper voltage.

CAUTION

Failure to follow these instructions can cause immedi- ate failure of components within the machine. When powering welder from a generator be sure to turn off welder first, before generator is shut down in order to prevent damage to welder.

------------------------------------------------------------------------

To reconnect a multiple voltage machine to a different voltage, remove input power and refer to the input connection diagram located on the inside of case back input access door. Follow the diagram for the voltage that is within 10% of your actual input line voltage.

1.Figure A.2 shows a sample of the reconnect instructions for a dual voltage machine.

Do not operate with covers

Do not touch electrically live parts

removed

Only qualified persons should install,

Disconnect input power before

servicing

use or service this equipment

DUAL VOLTAGE MACHINE

INPUT SUPPLY CONNECTION DIAGRAM

IMPORTANT: CHANGE LINK POSITIONS AND CONTROL TRANSFORMER CONNECTIONS. NOTE: MACHINES ARE SHIPPED FROM FACTORY CONNECTED FOR OVER 300 VOLTS

L3

W CR1

INPUT

V

LINES L2

CONTACTOR

L1

U

GND

H1

 

H3

 

CONTROL

 

TRANSF.

LINKS

CONNECTION FOR HIGHEST RATING PLATE VOLTAGE

 

1

. TURN OFF THE INPUT POWER USING THE DISCONNECT SWITCH AT THE FUSE BOX.

 

2

. DISCONNECT AND INSULATE THE H2 LEAD TERMINAL WITH TAPE TO PROVIDE AT

 

 

LEAST 600 VOLT INSULATION.

 

 

3. CONNECT L1, L2 & L3 INPUT SUPPLY LINES AND H1 & H3 CONTROL TRANSFORMER

 

 

LEADS TO THE INPUT SIDE OF CR1 CONTACTOR AS SHOWN.

 

4

. CONNECT TERMINAL MARKED

TO GROUND PER LOCAL AND NATIONAL ELECTRIC

 

 

CODES.

 

H2

5. MOUNT THE LINKS IN THE POSITIONS SHOWN; DOUBLE OR TRIPLE STACK THE LINKS

 

IN THREE POSITIONS. LOOP THE FLEX LEAD IN THE POSITION SHOWN; POSITIONING

 

 

 

 

THE LUGS TO MAINTAIN MAXIMUM CLEARANCE TO THE LINKS. INSTALL AND TIGHTEN

 

 

ALL OF THE HEX NUTS.

 

 

 

 

 

CONNECTION FOR LOWEST RATING PLATE VOLTAGE

 

 

 

 

 

1. TURN OFF THE INPUT POWER USING THE DISCONNECT SWITCH AT THE FUSE BOX.

 

 

L3

 

W CR1

2. DISCONNECT AND INSULATE THE H3 LEAD TERMINAL WITH TAPE TO PROVIDE AT

INPUT

 

LEAST 600 VOLT INSULATION.

 

L2

 

V

3. CONNECT L1, L2 & L3 INPUT SUPPLY LINES AND H1 & H2 CONTROL TRANSFORMER

LINES

 

 

CONTACTOR

LEADS TO THE INPUT SIDE OF CR1 CONTACTOR AS SHOWN.

 

 

L1

 

U

4. CONNECT TERMINAL MARKED

TO GROUND PER LOCAL AND NATIONAL ELECTRIC

 

GND

 

H1

CODES.

 

 

H2

5. MOUNT THE LINKS IN THE POSITIONS SHOWN. CONNECT THE FLEX LEAD AS SHOWN;

 

 

 

H3

 

 

 

 

CONTROL

POSITIONING THE LUGS TO MAINTAIN MAXIMUM CLEARANCE TO THE LINKS.

 

 

 

 

INSTALL AND TIGHTEN ALL OF THE HEX NUTS.

 

 

 

 

TRANSF.

LINKS

 

 

 

 

D-UF

 

 

 

 

 

THE LINCOLN ELECTRIC CO., CLEVELAND OHIO U.S.A.

 

M18225

FIGURE A.2 Dual Voltage Machine Reconnection Procedure

DC-655

Image 13
Contents DC-655 California Proposition 65 Warnings SafetyE C T R I C S H O C K c a n kill Iii Welding and Cutting Sparks can Cause fire or explosionSûreté Pour Soudage a L’Arc Précautions DE SûretéVSAFETY ViSAFETY Thank You Table of Contents Technical Specifications DC-655 InstallationHeight Width Depth Weight Input Hertz Input Ampere Type 80CGmaw Fcaw Input Power Three PhaseSmaw SAW NRTL/C NrtlSelect Suitable Location Safety PrecautionsElectrical Input Connections Input Power Supply Connections Reconnect ProcedureElectrode and Work Cables Output ConnectionsTable A.1 LOW Inductance TerminalAuxiliary Power Control Connections Terminal Strip 2 T.S.2 Terminal Strip 1 T.S.1Terminal Strips General Description OperationGeneral Warnings Recommended Processes and EquipmentWelding Capability Design Features and AdvantagesPower ON/OFF Switch This tog Controls and SettingsLOCAL/REMOTE Control Switch When this Output Terminals ON/REMOTE When thisFigure B.2 Lower Case Front Controls & Connections Machine Protection Welding Performance CC Mode HOT Start CV Mode CURRENT-LIMITINGCC Mode ARC Gouging CC Mode ARC ForceSEMI-AUTOMATIC Wire Feeders AccessoriesAutomatic Wire Feeders Field Installed OptionsAccessories General Maintenance MaintenanceSafety Precautions HOW to USE Troubleshooting Guide TroubleshootingProblems Troubleshooting Trol circuit. #75, #76, #77 Problems Troubleshooting Troubleshooting Troubleshooting PC Board Troubleshooting Guide Control P.C. Board PC Board Troubleshooting Guide Firing P.C. Board10TROUBLESHOOTINGE-10 Negative Positive DiagramsGND Negative Positive Receptacle Convenience, this extended #21 lead should be taped to 655 Wiring Diagram for Codes 10501,10503, 10504 Diagrams Diagrams Diagrams Diagrams Aviso DE Keep your head out of fumes Turn power off before servicing