Lincoln Electric IM730 manual Connection of Ranger 305D to Premises Wiring

Page 14

A-6

INSTALLATION

A-6

 

 

 

CONNECTION OF RANGER 305D TO PREMISES WIRING

240Volt

60 Hz.

3-Wire

Service

240 VOLT

POWER

120 VOLT

COMPANY

120 VOLT

METER

GROUNDED CONDUCTOR

NEUTRAL

BUS

DOUBLE POLE DOUBLE THROW

SWITCH RATING TO BE THE SAME

AS OR GREATER THAN PREMISES

SERVICE OVERCURRENT

PROTECTION.

 

 

50AMP

 

 

240 VOLT

 

 

DOUBLE

50 AMP, 120/240

 

POLE

 

CIRCUIT

VOLT PLUG

240 VOLT

BREAKER

NEMA TYPE 14-50

 

 

GND

N

N

LOAD

PREMISES

DISCONNECT AND

SERVICE

GROUNDOVERCURRENT PROTECTION

50 AMP, 120/240 VOLT

RECEPTACLENOTE: No. 6 COPPER CONDUCTOR CABLE SEE NATIONAL ELECTRICAL CODE FOR ALTERNATE WIRE

SIZE RECOMMENDATIONS.

WARNING

Only a licensed, certified, trained electrician should install the machine to a premises or residential electrical system. Be certain that:

The installation complies with the National Electrical Code and all other applicable electrical codes.

The premises is isolated and no feedback into the utility system can occur. Certain state and local laws require the premises to be isolated before the generator is linked to the premises. Check your state and local requirements.

A double pole, double throw transfer switch in conjunction with the properly rated double throw circuit breaker is connected between the generator power and the utility meter.

RANGER 305D

Image 14
Contents Ranger 305 D Safety Electric Shock can kill Welding Sparks can cause fire or explosion IiiPrécautions DE Sûreté Sûreté Pour Soudage a L’ArcThank You Table of Contents Section F Section DSection E P417Lubrication Emissions Fuel System Governor Height Width Depth WeightAIR Cleaner Engine Idler Muffler Engine Protection Ranger 305DSafety Precautions Location and VentilationVehicle Mounting PRE-OPERATION Engine ServiceBattery Connection OILElectrical Connections Cable Installation Auxiliary Power ReceptaclesStandby Power Connections Total Combined Length of Electrode and Work CablesConnection of Ranger 305D to Premises Wiring Connection of LN-7 or LN-8 to the Ranger 305D Connection of Lincoln Electric Wire FeedersConnection of an LN-23P Wire Feeder to the Ranger 305D Connection of LN-15 to the Ranger 305DTerminals on Connection of Prince XL Spool GUN to the Ranger 305DGeneral Description Safety PrecautionsFor Auxiliary Power Engine OperationWeld Mode Selector Switch Digital Output MetersWire Feeder Voltmeter Switch Figure B.2Typical Ranger 305D Fuel Consumption Starting the EngineStopping the Engine Table B.1Duty Cycle Welder OperationTypical Current Ranges 1 for Tungsten ELECTRODES2 TIG WeldingTable B.3 Wire WELDING-CVARC Gouging Auxiliary Power Ranger 305D Extension Cord Length RecommendationsField Installed Options / Accessories TIG OptionsEngine Maintenance Components Kubota D722 Diesel Engine Kubota D722 Diesel EngineEngine Oil Change AIR CleanerEngine Oil Refill capacities Without oil filter replacement Oil Filter ChangeService Instructions & Installation Tips Bleeding the Fuel System Cooling SystemTightening the FAN Belt Servicing Optional Spark Arrestor Engine AdjustmentBattery Maintenance Welder / Generator Maintenance Troubleshooting HOW to USE Troubleshooting GuideContact your local Lincoln Authorized Field Service FacilityYour local Lincoln Welding without a control cable Functioning properly / linkage Faulty control cable. Repair or Process being used. For exam Diagrams Diagrams Diagrams Diagrams Diagrams Engine Welders /LN-8 Connection Diagram S24787-6Diagrams Diagrams Diagrams Diagrams Diagrams Ranger 305D- Kubota Wiring Diagram Dimension Print Ranger 305D Ranger 305D Ranger 305D Precaucion Warnung