AUXILIARY POWER OPERATION

Start the engine and set the IDLER control switch to the desired operating mode. Full power is available regardless of the welding control settings, if no welding current is being drawn.

The auxiliary power of the Commander consists of two 20Δ Amp-120VAC (5-20ΔR) duplex receptacles and one

50Amp-120/240 VAC (14-50R) receptacle. The 120/240VAC receptacle can be split for single phase

120VAC operation.

Δ15 Amps for codes below 10500 only.

The auxiliary power capacity is 10,000 watts of 60 Hz, single phase power. The auxiliary power capacity rating in watts is equivalent to volt-amperes at unity power factor. The maximum permissible current of the 240 VAC output is 44 A. The 240 VAC output can be split to provide two separate 120 VAC outputs with a maximum permissible current of 44 A per output to two separate 120 VAC branch circuits. Output voltage is within ± 10% at all loads up to rated capacity.

NOTE: The 120/240V receptacle has two 120V out- puts of different phases and cannot be paralleled.

The auxiliary power receptacles should only be used with three wire grounded type plugs or approved dou- ble insulated tools with two wire plugs.

The current rating of any plug used with the system must be at least equal to the current capacity of the associated receptacle.

SIMULTANEOUS WELDING AND AUXIL- IARY POWER LOADS

It must be noted that the above auxiliary power ratings are with no welding load. Simultaneous welding and power loads are specified in table B.4. The permissible currents shown assume that current is being drawn from either the 120 VAC or 240 VAC supply (not both at the same time).

TABLE B.4 Commander 300 Simultaneous Welding and Power

Loads

Welding

Output Range

Setting

Welding Output

Permissible

Power - Watts

(Unity Power

Permissible Auxiliary Current in Amperes

30-375

300

230

150

90

60

300A/32V

300A/32V

230A/30V

150A/29V

90A/27V

60A/25V

Factor)

400

400

3100

5650

7600

8500

@120 V ±10% *

3.3

3.3

26*

47**

63**

70**

@ 240 V ±10%

1.6

1.6

13

23.5

31.5

35

*Each duplex receptacle is limited to 20Δ amps.

**Not to exceed 44 A per 120 VAC branch circuit when splitting the 240 VAC output.

COMMANDER 300

Image 27
Contents Commander Safety Electric Shock can kill Cylinder may explode if damaged Précautions DE Sûreté Thank You Table of Contents Vii Installation Safety Precautions Lifting PRE-OPERATION Engine Service High Frequency Generators for TIG Applications Welding Output Cables Power Commander Connection of Lincoln Electric Wire FeedersConnection of the LN-25 to the Commander Connection of LN-7 or LN-8 to the CommanderConnection of AN LN-23P Wire Feeder to the Commander General Description Safety InstructionsDesign Features and Advantages Operating InstructionsWelding Capability For Auxiliary PowerOther Features K1585-1 Commander 300 Standard ModelFuel Level Gauge and Light Controls and SettingsRUN- Stop Switch Start PushbuttonHour Meter Idler SwitchOIL Pressure Gauge K1585-2 Std., K1585-1 Opt. and Light Idler Operational exceptionsAuxiliary Power Controls Engine Operation Starting the EngineStopping the Engine Stick Welding Welder OperationBREAK-IN Period Typical Fuel ConsumptionCommander 300 Settings When Using the K799 HI-FREQ Unit Commander 300 Settings When Using the K930-1 TIG ModuleTable B.3 Typical Current Ranges 1 for Tungsten ELECTRODES2 Wire Feed Constant Voltage Weld ING Simultaneous Welding and AUXIL- Iary Power Loads Auxiliary Power OperationRecommended Optional EQUIP- Ment Optional Field Installed AccessoriesSafety Precautions Routine and Periodic MaintenanceEngine Maintenance Cooling System Cooling Blower Belt Fuel FiltersWelder / Generator Maintenance Nameplates / Warning Decals MaintenanceMake Part Number HOW to USE Troubleshooting Guide TroubleshootingSymptoms Possible AreasCourse of Action Function Problems Output Problems Wiring DiagramWiring DiagramCommander 300-STANDARD Model Wiring Diagram Code 10469 only Connection Diagram Connection Connection S23988 S23989 Installation Instructions Connection S23992 S24787-3 S23994 Commander 300 / K930 TIG Module / Connection Diagram $!#% 300 Dimension PrintCommander Commander $700.00 Basic CoursePrecaucion Aviso DE