Restricted Refrigerant System

Troubleshooting a restricted refrigerant system can be GLI¿FXOWThe following procedures are the more common problems and solutions to these problems. There are two types of refrigerant restrictions: Partial restrictions and complete restrictions.

A partial restriction allows some of the refrigerant to circulate through the system.

With a complete restriction there is no circulation of refrigerant in the system.

Restricted refrigerant systems display the same symptoms as a “low-charge condition.”

When the unit is shut off, the gauges may equalize very slowly.

Gauges connected to a completely restricted system will run in a deep vacuum. When the unit is shut off, the

gauges will not equalize at all.

A quick check for either condition begins at the evaporator. With a partial restriction, there may be gurgling sounds

at the metering device entrance to the evaporator. The evaporator in a partial restriction could be partially frosted or have an ice ball close to the entrance of the metering device. Frost may continue on the suction line back to the compressor.

Often a partial restriction of any type can be found by feel, as there is a temperature difference from one side of the restriction to the other.

With a complete restriction, there will be no sound at the metering device entrance. An amperage check of the compressor with a partial restriction may show normal FXUUHQWZKHQFRPSDUHGWRWKHXQLWVSHFL¿FDWLRQ:LWKD complete restriction the current drawn may be considerably less than normal, as the compressor is running in a deep vacuum (no load.) Much of the area of the condenser will be relatively cool since most or all of the liquid refrigerant will be stored there.

The following conditions are based primarily on a system in the cooling mode.

33

Image 34
Contents Room Air Conditioners Table Of Contents Important Safety Information Your safety and the safety of others are very importantRefrigeration System Hazards Introduction Register your air conditioner08 N 1 0 a a Unit IdentificationPerformance Data SQ05N10-A 115 146Electric Shock Hazard Electrical DataFire Hazard Keep the filter clean Make sure the wiring is adequate for your unitTest the power cord Proper installation of chassis seal gasketKuhl Q Control Panel Operation Kühl Control Options Control Panel Operation Instructions Timer Schedule Button ºF ºC SelectWait Icon DIM FunctionAlerts Control Panel LockTo Turn On the Timer or Schedule Selected Timer or Schedule Options 1 or 2 SelectionTimer Start Time Timer SettingsSet theTimer Stop Time Timer on ScenariosTimer OFF Scenarios Timer Schedule Control BlockRemote Control Operation Auto FAN Continuous Cooling Mode Electronic Control Sequence of OperationCompressor Lock Out Time User Interface Tests Components TestingIf the user interface does not turn on Relay Board TestComponents Testing CON’T Testing the Relay BoardFAN Motor Capacitor Check with Capacitor AnalyzerCapacitor Connections BLOWER/FAN Motor TestHeating Element Testing the Heating Element Electric Shock HazardDrain PAN Valve Refrigeration Sequence of Operation 410A Sealed System Repair Considerations Refrigeration system under high pressure410A Sealed Refrigeration System Repairs Refrigerant ChargingRefrigeration Sequence of Operation 410A Sealed Refrigeration System Repairs Burn Hazard Method Of Charging / RepairsFreeze Hazard Undercharged Refrigerant Systems Overcharged Refrigerant SystemsRestricted Refrigerant System Compressor Checks Single Phase Resistance Test Ground TestHigh Temperatures Recommended procedure for compressor replacementExplosion Hazard Available Accessories Rotary Compressor Special Troubleshooting and ServiceStandard Filter Cleaning / Installation Instructions Routine Maintenance Routine Maintenance Frosting This is a warm weather applianceCondensation is normal NoisesPage See codes chart on next Error Codes Problem Control Boards ActionTest Mode Page Page Cooling only Room AIR Conditioners Troubleshooting Tips Cooling only Room AIR Conditioners Troubleshooting Tips Cooling only Room AIR Conditioners Troubleshooting Tips Cooling only Room AIR Conditioners Troubleshooting Tips Heat / Cool only Room AIR Conditioners Troubleshooting Tips Electronic Controls Wiring Diagram THERMISTORS’ Resistance Values Page Page Following is an example using the heat load form Heat Load FormHeating Load Form Friedrich Room Unit Heat Pumps Infiltration Windows & Doors AVGKühl-Q Kühl-Q Units’ 2012 Parts List Kühl Q-Chassis Service Parts List Addendum Schedule Table with Energy Saving ValuesRoom AIR Conditioners Limited Warranty Technical Support Contact Information Friedrich AIR Conditioning CO