COMPRESSOR CHECKS

WARNING

ELECTRIC SHOCK HAZARD

Turn off electric power before service or installation. Extreme care must be used, if it becomes necessary to work on equipment with power applied.

Failure to do so could result in serious injury or death.

Locked Rotor Voltage (L.R.V.) Test

Locked rotor voltage (L.R.V.) is the actual voltage available at the compressor under a stalled condition.

Single Phase Connections

Disconnect power from unit. Using a voltmeter, attach one lead of the meter to the run “R” terminal on the compressor and the other lead to the common “C” terminal of the com- pressor. Restore power to unit.

Determine L.R.V.

Start the compressor with the volt meter attached; then stop the unit. Attempt to restart the compressor within a couple of seconds and immediately read the voltage on the meter. The compressor under these conditions will not start and will usually kick out on overload within a few seconds since the pressures in the system will not have had time to equalize. Voltage should be at or above minimum voltage of 197 VAC,

DVVSHFL¿HGRQWKHUDWLQJSODWH,IOHVVWKDQPLQLPXPFKHFN

for cause of inadequate power supply; i.e., incorrect wire size, loose electrical connections, etc.

Amperage (L.R.A.) Test

The running amperage of the compressor is the most impor- tant of these readings. A running amperage higher than that indicated in the performance data indicates that a problem exists mechanically or electrically.

Single Phase Running and L.R.A. Test

NOTE:&RQVXOWWKHVSHFL¿FDWLRQDQGSHUIRUPDQFHVHFWLRQ for running amperage. The L.R.A. can also be found on the rating plate.

Select the proper amperage scale and clamp the meter probe around the wire to the “C” terminal of the compres- sor. Turn on the unit and read the running amperage on the meter,IWKHFRPSUHVVRUGRHVQRWVWDUWWKHUHDGLQJ will indicate the locked rotor amperage (L.R.A.).

External Overload

The compressor is equipped with an external overload which senses both motor amperage and winding tem- perature. High motor temperature or amperage heats the overload causing it to open, breaking the common circuit within the compressor.

Heat generated within the compressor shell, usually due to recycling of the motorLVVORZWRGLVVLSDWH,WPD\WDNH anywhere from a few minutes to several hours for the overload to reset.

Checking the External Overload

WARNING

ELECTRIC SHOCK HAZARD

Turn off electric power before service or installation. Extreme care must be used, if it becomes necessary to work on equipment with power applied.

Failure to do so could result in serious injury or death.

WARNING

BURN HAZARD

Certain unit components operate at temperatures hot enough to cause burns.

Proper safety procedures must be followed, and proper protective clothing must be worn.

Failure to follow this warning could result in moderate to serious injury.

With power off, remove the leads from compressor termi- QDOV,IWKHFRPSUHVVRULVKRWDOORZWKHRYHUORDGWRFRRO before starting check. Using an ohmmeter, test continu- LW\DFURVVWKHWHUPLQDOVRIWKHH[WHUQDORYHUORDG,I\RX do not have continuity; this indicates that the overload is open and must be replaced.

34

Image 35
Contents Room Air Conditioners Table Of Contents Your safety and the safety of others are very important Important Safety InformationRefrigeration System Hazards Register your air conditioner IntroductionUnit Identification 08 N 1 0 a aSQ05N10-A 115 146 Performance DataFire Hazard Electrical DataElectric Shock Hazard Proper installation of chassis seal gasket Make sure the wiring is adequate for your unitTest the power cord Keep the filter cleanKuhl Q Control Panel Operation Kühl Control Options Control Panel Operation Instructions ºF ºC Select Timer Schedule ButtonControl Panel Lock DIM FunctionAlerts Wait IconTimer or Schedule Options 1 or 2 Selection To Turn On the Timer or Schedule SelectedTimer Settings Timer Start TimeTimer on Scenarios Set theTimer Stop TimeTimer Schedule Control Block Timer OFF ScenariosRemote Control Operation Auto FAN Continuous Electronic Control Sequence of Operation Cooling ModeCompressor Lock Out Time Relay Board Test Components TestingIf the user interface does not turn on User Interface TestsTesting the Relay Board Components Testing CON’TBLOWER/FAN Motor Test Capacitor Check with Capacitor AnalyzerCapacitor Connections FAN MotorDrain PAN Valve Testing the Heating Element Electric Shock HazardHeating Element Refrigeration Sequence of Operation Refrigeration system under high pressure 410A Sealed System Repair ConsiderationsRefrigerant Charging 410A Sealed Refrigeration System RepairsRefrigeration Sequence of Operation 410A Sealed Refrigeration System Repairs Freeze Hazard Method Of Charging / RepairsBurn Hazard Overcharged Refrigerant Systems Undercharged Refrigerant SystemsRestricted Refrigerant System Compressor Checks Ground Test Single Phase Resistance TestExplosion Hazard Recommended procedure for compressor replacementHigh Temperatures Rotary Compressor Special Troubleshooting and Service Available AccessoriesStandard Filter Cleaning / Installation Instructions Routine Maintenance Routine Maintenance Noises This is a warm weather applianceCondensation is normal FrostingPage See codes chart on next Problem Control Boards Action Error CodesTest Mode Page Page Cooling only Room AIR Conditioners Troubleshooting Tips Cooling only Room AIR Conditioners Troubleshooting Tips Cooling only Room AIR Conditioners Troubleshooting Tips Cooling only Room AIR Conditioners Troubleshooting Tips Heat / Cool only Room AIR Conditioners Troubleshooting Tips Electronic Controls Wiring Diagram THERMISTORS’ Resistance Values Page Page Heat Load Form Following is an example using the heat load formInfiltration Windows & Doors AVG Heating Load Form Friedrich Room Unit Heat PumpsKühl-Q Kühl-Q Units’ 2012 Parts List Kühl Q-Chassis Service Parts List Schedule Table with Energy Saving Values AddendumRoom AIR Conditioners Limited Warranty Technical Support Contact Information Friedrich AIR Conditioning CO