Friedrich SQ10N10, SQ08N10, SQ05N10, SQ06N10, EQ08N11 Error Codes, Problem Control Boards Action

Page 45

ERROR CODES

Error

Problem

Control Board's Action

Code

 

 

1

Front Panel Button Stuck For More

Continue to monitor for "OPEN" (Unstuck) switch. Do not process switch

Than 20 Seconds

input.

 

2Input Voltage Out of Specification (103 Open all relays until voltage is back within specs. Resume operation - 127 / 187 - 253)

3Indoor Temperature Sensor is Open or Set temp to 75°F in COOLING or 68°F in HEATING. Unit continues to

Shortedoperate

4

Indoor Coil Temperature Sensor is

Control Board sets temp to a default of 40°F. Override sensor. Unit

Open or Shorted

continues to operate.

 

5

Outdoor Coil Temperature Sensor is

Sets temp to 20°F. Override sensor. Continue operation. Use Elec Heat if

available for HEATING. If not available use HEAT PUMP if outdoor temp

Open or Shorted

 

allows.

 

 

 

 

Shut down for 5 min. Resume operation for 3 min. Continues to monitor. If

6Outdoor Coil > (grater than) 175 F test fails 3 times, the unit operation is locked out. Unplug and replug to reset.

7Indoor Coil < (less than) 30 F for 2 Turn compressor off. Run High Fan speed. When coil temp reachs 45°F

consecutive minutesresume operation after lockout time.

8Unit Cycles > (grater than) 9 Times per Continue operation. Continue to monitor. Take no action. Log Only. hour

9

Unit Cycles < (less than) 3 Times per

Continue operation. Continue to monitor. Take no action. Log Only.

Hour

 

 

 

 

Only used if Electric Heat is available. Run High Speed and Electric heat

10

Room Freeze Protection

until room temp reaches 46°F. Display "FRZ" during operation. Logged

 

 

Only

11

WallStat Problem or Connection Issue

Unit operates based on standard t-stat connection. If miswired, unit will not

not operate. (See pages 32 and 68)

12

Not Applicable

Not Applicable

 

 

 

13

Not Applicable

Not Applicable

 

 

 

14

Discharge Air Temperature Sensor is

Override Sensor. Set temp to 75°F. Continue to monitor. Set error code 14

Open or Shorted

ON.

 

15

Not Applicable

Not Applicable

16Temperature Beyond Operating Limits Ambient temp < (less than) 0°F and ambient temp > (greater than) 130°F. Set error code 16 ON. When cleared return unit to normal.

17

Equipment Doesn't Meet Minimum

Must have compressor enabled and at least 2 fan speeds

Configuration

 

 

18

Not Applicable

Not Applicable

 

 

 

19

Not Applicable

Not Applicable

20

Not Applicable

Not Applicable

 

 

 

21

Not Applicable

Not Applicable

22

Outdoor Coil Temperature < 30 F for 2

Unit will use electric heat to satisfy heating demands until temp is greater

consecutive Minutes

than 45°F. Unit must be a Heat Pump with electric heat.

 

23

Not Applicable

Not Applicable

24

Not Applicable

Not Applicable

 

 

Key Sequence

 

 

Action

 

To Access Error Codes

Press the fan speed and key for 3 seconds

 

Reset Error Codes & Error History

Press + timer/schedule for 3 seconds

 

When you have entered the Error Codes section, an “E” will appear. Use the up

and down keys to scroll through error codes.

Only active error codes will display.

 

 

 

44

Image 45
Contents Room Air Conditioners Table Of Contents Your safety and the safety of others are very important Important Safety InformationRefrigeration System Hazards Register your air conditioner IntroductionUnit Identification 08 N 1 0 a aSQ05N10-A 115 146 Performance DataElectrical Data Electric Shock HazardFire Hazard Test the power cord Make sure the wiring is adequate for your unitKeep the filter clean Proper installation of chassis seal gasketKuhl Q Control Panel Operation Kühl Control Options Control Panel Operation Instructions ºF ºC Select Timer Schedule ButtonAlerts DIM FunctionWait Icon Control Panel LockTimer or Schedule Options 1 or 2 Selection To Turn On the Timer or Schedule SelectedTimer Settings Timer Start TimeTimer on Scenarios Set theTimer Stop TimeTimer Schedule Control Block Timer OFF ScenariosRemote Control Operation Auto FAN Continuous Electronic Control Sequence of Operation Cooling ModeCompressor Lock Out Time If the user interface does not turn on Components TestingUser Interface Tests Relay Board TestTesting the Relay Board Components Testing CON’TCapacitor Connections Capacitor Check with Capacitor AnalyzerFAN Motor BLOWER/FAN Motor TestTesting the Heating Element Electric Shock Hazard Heating ElementDrain PAN Valve Refrigeration Sequence of Operation Refrigeration system under high pressure 410A Sealed System Repair ConsiderationsRefrigerant Charging 410A Sealed Refrigeration System RepairsRefrigeration Sequence of Operation 410A Sealed Refrigeration System Repairs Method Of Charging / Repairs Burn HazardFreeze Hazard Overcharged Refrigerant Systems Undercharged Refrigerant SystemsRestricted Refrigerant System Compressor Checks Ground Test Single Phase Resistance TestRecommended procedure for compressor replacement High TemperaturesExplosion Hazard Rotary Compressor Special Troubleshooting and Service Available AccessoriesStandard Filter Cleaning / Installation Instructions Routine Maintenance Routine Maintenance Condensation is normal This is a warm weather applianceFrosting NoisesPage See codes chart on next Problem Control Boards Action Error CodesTest Mode Page Page Cooling only Room AIR Conditioners Troubleshooting Tips Cooling only Room AIR Conditioners Troubleshooting Tips Cooling only Room AIR Conditioners Troubleshooting Tips Cooling only Room AIR Conditioners Troubleshooting Tips Heat / Cool only Room AIR Conditioners Troubleshooting Tips Electronic Controls Wiring Diagram THERMISTORS’ Resistance Values Page Page Heat Load Form Following is an example using the heat load formInfiltration Windows & Doors AVG Heating Load Form Friedrich Room Unit Heat PumpsKühl-Q Kühl-Q Units’ 2012 Parts List Kühl Q-Chassis Service Parts List Schedule Table with Energy Saving Values AddendumRoom AIR Conditioners Limited Warranty Technical Support Contact Information Friedrich AIR Conditioning CO