R-410A SEALED SYSTEM REPAIR CONSIDERATIONS
WARNING
Refrigeration system under high pressure
'RQRWSXQFWXUHKHDWH[SRVHWRÀDPHRULQFLQHUDWH
OQO\FHUWL¿HGUHIULJHUDWLRQWHFKQLFLDQVVKRXOG service this equipment.
R410A systems operate at higher pressures than R22 equipment. Appropriate safe service and handling practicces must be used.
Only use gauge sets designed for use with R410A. Do not use standard R22 gauge sets.
The following is a list of important considerations when working with
ÀDPPDEOH
6HUYLFLQJHTXLSPHQWDQGFRPSRQHQWVPXVWEHVSHFL¿FDOO\GHVLJQHGIRUXVHZLWK5$DQG
dedicated to prevent contamination.
Manifold sets must be equipped with gauges capable of reading 750 psig (high side) and 200 psig (low side), with a
Gauge hoses must have a minimum
Recovery cylinders must have a minimum service pressure rating of 400 psig, (DOT 4BA400 and DOT BW400 approved cylinders).
POE
To prevent moisture absorption and lubricant contamination, do not leave the refrigeration system open to the atmosphere longer than 1 hour.
Introduce liquid refrigerant charge into the high side of the system.
For low side pressure charging of
8VH)ULHGULFKDSSURYHG5$¿OWHUGU\HUVRQO\
27