COMPRESSOR REPLACEMENT

Recommended procedure for compressor replacement

WARNING

RISK OF ELECTRIC SHOCK

Unplug and/or disconnect all electrical power to the unit before performing inspections, maintenances or service.

Failure to do so could result in electric shock,

VHULRXVLQMXU\RUGHDWK

1.Be certain to perform all necessary electrical and refrigeration tests to be sure the compressor is actually defective before replacing.

WARNING

HIGH PRESSURE HAZARD

Sealed Refrigeration System contains refrigerant and oil under high pressure.

Proper safety procedures must be followed, and proper protective clothing must be worn when working with refrigerants.

Failure to follow these procedures could

UHVXOWLQVHULRXVLQMXU\RUGHDWK

2.Recover all refrigerant from the system though the process tubes. PROPER HANDLING OF

RECOVERED REFRIGERANT ACCORDING TO EPA REGULATIONS IS REQUIRED. Do not use gauge manifold for this purpose if there has been a burnout. You will contaminate your manifold and hoses. Use a Schrader valve adapter and copper tubing for burnout failures.

WARNING

HIGH TEMPERATURES

([WUHPHFDUHSURSHUMXGJPHQWDQGDOOVDIHW\ procedures must be followed when testing, troubleshooting, handling or working around unit while in operation with high temperature components. Wear protective safety aids such as: gloves, clothing etc.

Failure to do so could result in serious burn

LQMXU\

NOTICE

FIRE HAZARD

The use of a torch requires extreme care and proper

MXGJPHQW )ROORZ DOO VDIHW\ UHFRPPHQGHG SUHFDXWLRQV DQG SURWHFW VXUURXQGLQJ DUHDV ZLWK ¿UH SURRI PDWHULDOV +DYHD¿UHH[WLQJXLVKHUUHDGLO\DYDLODEOH)DLOXUHWRIROORZ this notice could result in moderate to serious property damage.

3.After all refrigerant has been recovered, disconnect suction and discharge lines from the compressor and remove compressor. Be certain to have both suction and discharge process tubes open to atmosphere.

4.Carefully pour a small amount of oil from the suction stub of the defective compressor into a clean container.

5.Using an acid test kit (one shot or conventional kit), test the oil for acid content according to the instructions with the kit.

6.If any evidence of a burnout is found, no matter how slight, the system will need to be cleaned up following proper procedures.

7.Install the replacement compressor.

WARNING

EXPLOSION HAZARD

The use of nitrogen requires a pressure regulator. Follow all safety procedures and wear protective safety clothing etc.

Failure to follow proper safety procedures

UHVXOWLQVHULRXVLQMXU\RUGHDWK

8.Pressurize with a combination of R410-A and nitrogen and leak test all connections with an electronic or Halide leak detector. Recover refrigerant and repair any leaks found.

Repeat Step 8 to insure no more leaks are present.

(YDFXDWHWKHV\VWHPZLWKDJRRGYDFXXPSXPSFDSDEOH

RID¿QDOYDFXXPRIPLFURQVRUOHVV7KHV\VWHP

should be evacuated through both liquid line and suction line gauge ports. While the unit is being evacuated, seal all openings on the defective compressor. Compressor manufacturers will void warranties on units received not properly sealed. Do not distort the manufacturers tube connections.

CAUTION

FREEZE HAZARD

Proper safety procedures must be followed, and proper protective clothing must be worn when working with liquid refrigerant.

Failure to follow these procedures could

UHVXOWLQPLQRUWRPRGHUDWHLQMXU\

10.Recharge the system with the correct amount of refrigerant. The proper refrigerant charge will be found on the unit rating plate. The use of an accurate measuring device, such as a charging cylinder, electronic scales or similar device is necessary.

36

Image 37
Contents Room Air Conditioners Table Of Contents Your safety and the safety of others are very important Important Safety InformationRefrigeration System Hazards Register your air conditioner IntroductionUnit Identification 08 N 1 0 a aSQ05N10-A 115 146 Performance DataElectric Shock Hazard Electrical DataFire Hazard Test the power cord Make sure the wiring is adequate for your unitKeep the filter clean Proper installation of chassis seal gasketKuhl Q Control Panel Operation Kühl Control Options Control Panel Operation Instructions ºF ºC Select Timer Schedule ButtonAlerts DIM FunctionWait Icon Control Panel LockTimer or Schedule Options 1 or 2 Selection To Turn On the Timer or Schedule SelectedTimer Settings Timer Start TimeTimer on Scenarios Set theTimer Stop TimeTimer Schedule Control Block Timer OFF ScenariosRemote Control Operation Auto FAN Continuous Electronic Control Sequence of Operation Cooling ModeCompressor Lock Out Time If the user interface does not turn on Components TestingUser Interface Tests Relay Board TestTesting the Relay Board Components Testing CON’TCapacitor Connections Capacitor Check with Capacitor AnalyzerFAN Motor BLOWER/FAN Motor TestHeating Element Testing the Heating Element Electric Shock HazardDrain PAN Valve Refrigeration Sequence of Operation Refrigeration system under high pressure 410A Sealed System Repair ConsiderationsRefrigerant Charging 410A Sealed Refrigeration System RepairsRefrigeration Sequence of Operation 410A Sealed Refrigeration System Repairs Burn Hazard Method Of Charging / RepairsFreeze Hazard Overcharged Refrigerant Systems Undercharged Refrigerant SystemsRestricted Refrigerant System Compressor Checks Ground Test Single Phase Resistance TestHigh Temperatures Recommended procedure for compressor replacementExplosion Hazard Rotary Compressor Special Troubleshooting and Service Available AccessoriesStandard Filter Cleaning / Installation Instructions Routine Maintenance Routine Maintenance Condensation is normal This is a warm weather applianceFrosting NoisesPage See codes chart on next Problem Control Boards Action Error CodesTest Mode Page Page Cooling only Room AIR Conditioners Troubleshooting Tips Cooling only Room AIR Conditioners Troubleshooting Tips Cooling only Room AIR Conditioners Troubleshooting Tips Cooling only Room AIR Conditioners Troubleshooting Tips Heat / Cool only Room AIR Conditioners Troubleshooting Tips Electronic Controls Wiring Diagram THERMISTORS’ Resistance Values Page Page Heat Load Form Following is an example using the heat load formInfiltration Windows & Doors AVG Heating Load Form Friedrich Room Unit Heat PumpsKühl-Q Kühl-Q Units’ 2012 Parts List Kühl Q-Chassis Service Parts List Schedule Table with Energy Saving Values AddendumRoom AIR Conditioners Limited Warranty Technical Support Contact Information Friedrich AIR Conditioning CO