Friedrich WS10B10 service manual Restricted Refrigerant System

Page 21

Restricted Refrigerant System

Troubleshooting a restricted refrigerant system can be difficult. The following procedures are the more common problems and solutions to these problems. There are two types of refrigerant restrictions: Partial restrictions and complete restrictions.

A partial restriction allows some of the refrigerant to circulate through the system.

With a complete restriction there is no circulation of refrigerant in the system.

Restricted refrigerant systems display the same symptoms as a “low-charge condition.”

When the unit is shut off, the gauges may equalize very slowly.

Gauges connected to a completely restricted system will run in a deep vacuum. When the unit is shut off, the gauges

will not equalize at all.

A quick check for either condition begins at the evaporator. With a partial restriction, there may be gurgling sounds

at the metering device entrance to the evaporator. The evaporator in a partial restriction could be partially frosted or have an ice ball close to the entrance of the metering device. Frost may continue on the suction line back to the compressor.

Often a partial restriction of any type can be found by feel, as there is a temperature difference from one side of the restriction to the other.

With a complete restriction, there will be no sound at the metering device entrance. An amperage check of the compressor with a partial restriction may show normal current when compared to the unit specifi cation. With a complete restriction the current drawn may be considerably less than normal, as the compressor is running in a deep vacuum (no load.) Much of the area of the condenser will be relatively cool since most or all of the liquid refrigerant will be stored there.

The following conditions are based primarily on a system in the cooling mode.

20

Image 21
Contents Thru-the-wall Table Of Contents Your safety and the safety of others are very important Important Safety InformationRefrigeration System Hazards Property Damage Hazards IntroductionFriedrich wallmaster Model Number Code Performance Data Sleeve / Chassis DimensionsPlug/Outlet/Circuit Rating Electrical DataElectric Shock Hazard Fire HazardElectronic Control Operation To adjust fan speedTo activate Smart FanWS cool-only models To activate Smart FanWY/WE heat-cool modelsTo set the timer Checking Room TemperatureTo Activate Money Saver WY/WE models To set mode of operation To adjust temperatureTo start unit Testing the Electronic Control Error Code ModeElectronic Control Panel Automatic component protectionError Codes Listing for WE/WY Models Error Codes Listing for WS ModelsReboot the Control Panel E7 Motor Operation E9 Heat Pump FailureCoil Sensors Components TestingFAN Motor FAN Motor TestHeating Element CapacitorsDrain PAN Valve Capacitor Check with Capacitor AnalyzerRefrigeration System Sequence of Operation Refrigeration system under high pressure 410A Sealed System Repair ConsiderationsEquipment Required 410A Sealed Refrigeration System RepairsEquipment Must be Capable Risk of Electric ShockMethod Of Charging / Repairs Burn HazardFreeze Hazard Overcharged Refrigerant Systems Undercharged Refrigerant SystemsRestricted Refrigerant System Metering Device Hermetic Components CheckCheck Valve Capillary Tube SystemsPOSITION, 4 Port Reversing Valve Reversing Valve DESCRIPTION/OPERATIONChecking the Reversing Valve Testing the CoilProcedure For Changing Reversing Valve Touch Test in Heating/Cooling CycleExplosion Hazard Compressor Checks Ground Test Single Phase Resistance TestCompressor Replacement Recommended procedure for compressor replacementHigh Temperatures Rotary Compressor Special Troubleshooting and Service Routine Maintenance Sleeve / Drain Front CoverClearances Date Model Serial Room AIR Conditioner Unit Performance Test Data SheetGeneral Troubleshooting Tips General Troubleshooting Tips Cooling only Room AIR Conditioners Troubleshooting Tips Possible Cause Possible Solution Problem Possible Cause Possible Action HEAT/COOL only Room AIR Conditioners Troubleshooting Tips Heat Pump Troubleshooting Troubleshooting Chart Cooling Troubleshooting Chart Heating Heat PumpProblem Electrical Troubleshooting Chart Heat Pump System Cools When Heating is DesiredYES Malfunction of Valve Normal Function of ValvePage Page Page Installation Accessories Mounting Hardware Provided Wall PreparationDescription QTY MECHANICALCUT/SEVER Hazardhazard Installation RequirementsMECHANICALCUT/SEVER Hazard Installation Instructions for Baffle Adapter KIT BAKCUT/SEVER WallMaster Thru-the-WallMechanical Hazard MECHANICALCUT/SEVER Hazard Installation InstructionsAssembly & Installation Instructions Installation Instructions Subbase for WS, WE & WY Models Installation Instructions Architectural Grille Model AG MECHANICALCUT/SEVER Hazard WALLMASTER≤ THRU-THE-WALL AIR Conditioners Limited Warranty Technical Support Contact Information Page Page Friedrich AIR Conditioning CO