INSTALLATION REQUIREMENTS:

STEP 1 The “WSD” SLEEVE should be positioned so that the DRAIN EXTENSION extends a minimum of 9/16” beyond the OUTSIDE WALL (See Figure 1).

STEP 2 The “WSD” SLEEVE must extend a minimum of 7/8” beyond the INSIDE WALL.

STEP 3 The “WSD” SLEEVE must be installed level side to side.

STEP 4 The “WSD” SLEEVE must also be installed with a downward tilt toward the outside of the building. If a level is placed so that it rests on the FRONT and BACK UNIT REST as shown in Figure 2, a properly installed unit provides a 1/2 bubble slope to the outside of the building.

CAUTION: SLEEVE projections and leveling precautions must be observed to prevent the entry of water into the room.

FIGURE 2

RAISED LEDGE

BACK UNIT REST

LEVEL

FRONT UNIT REST

WARNING

MECHANICALCUT/SEVER HAZARDHAZARD

CUT/SEVER

Sharp edges and corners. Be careful with

Be careful with the sharp edges and corners. the sharp edges and corner. Wear protective Wear protective clothing and gloves, etc. clothing and gloves, etc.

Failure to do so could result in serious injury.

Failure to do so could result in serious injury.

SLEEVE INSTALLATION:

STEP 1 After unpacking the “WSD” SLEEVE from the carton, remove the corrugated FRONT PANEL.

For immediate installation of sleeve and chassis (skip if installing chassis into sleeve at a later date):

STEP 2

STEP 3 STEP 4

Remove the rear WEATHER PANEL. Reverse grille and place lower edge into sleeve tab (Friedrich logo facing out). Align slots with screw holes. Secure grille with screws.

Place “WSD” SLEEVE in the wall opening following the instructions given in the INSTALLATION REQUIRE- MENTS section. Attach the SLEEVE to the INSIDE WALL by driving two #12A x 2” screws in each side of the SLEEVE (see Figure 1.). Shim at the top of the SLEEVE, midway between the sides. Drive one #12A x 2” screw in the top of the sleeve, close to the shim. Install screws from inside the SLEEVE. If the wall opening is not framed with wood, use expansion anchor bolts or molly (toggle) bolts (not provided).

Once the SLEEVE has been installed, check the LEVEL again to be sure the 1/2 bubble downward tilt is main- tained. Apply shims, if required, to maintain the proper slope.

Caulk the perimeter of the entire opening on the inside and the outside between the SLEEVE and the WALL.

The corrugated front panel removed in Step 1 above must be remounted back in place if masonry work is to be done and/or if the “WSD” CHASSIS is to be installed at a later date.

47

Image 48
Contents Thru-the-wall Table Of Contents Important Safety Information Your safety and the safety of others are very importantRefrigeration System Hazards Introduction Property Damage HazardsFriedrich wallmaster Model Number Code Sleeve / Chassis Dimensions Performance DataElectrical Data Plug/Outlet/Circuit RatingElectric Shock Hazard Fire HazardTo adjust fan speed Electronic Control OperationTo activate Smart FanWS cool-only models To activate Smart FanWY/WE heat-cool modelsTo set the timer Checking Room TemperatureTo Activate Money Saver WY/WE models To set mode of operation To adjust temperatureTo start unit Error Code Mode Testing the Electronic ControlElectronic Control Panel Automatic component protectionError Codes Listing for WS Models Error Codes Listing for WE/WY ModelsReboot the Control Panel E7 Motor Operation E9 Heat Pump FailureComponents Testing Coil SensorsFAN Motor FAN Motor TestCapacitors Heating ElementDrain PAN Valve Capacitor Check with Capacitor AnalyzerRefrigeration System Sequence of Operation 410A Sealed System Repair Considerations Refrigeration system under high pressure410A Sealed Refrigeration System Repairs Equipment RequiredEquipment Must be Capable Risk of Electric ShockMethod Of Charging / Repairs Burn HazardFreeze Hazard Undercharged Refrigerant Systems Overcharged Refrigerant SystemsRestricted Refrigerant System Hermetic Components Check Metering DeviceCheck Valve Capillary Tube SystemsReversing Valve DESCRIPTION/OPERATION POSITION, 4 Port Reversing ValveTesting the Coil Checking the Reversing ValveProcedure For Changing Reversing Valve Touch Test in Heating/Cooling CycleExplosion Hazard Compressor Checks Single Phase Resistance Test Ground TestCompressor Replacement Recommended procedure for compressor replacementHigh Temperatures Rotary Compressor Special Troubleshooting and Service Routine Maintenance Sleeve / Drain Front CoverClearances Room AIR Conditioner Unit Performance Test Data Sheet Date Model SerialGeneral Troubleshooting Tips General Troubleshooting Tips Cooling only Room AIR Conditioners Troubleshooting Tips Possible Cause Possible Solution Problem Possible Cause Possible Action HEAT/COOL only Room AIR Conditioners Troubleshooting Tips Heat Pump Troubleshooting Troubleshooting Chart Cooling Troubleshooting Chart Heating Heat PumpProblem Electrical Troubleshooting Chart Heat Pump System Cools When Heating is DesiredYES Normal Function of Valve Malfunction of ValvePage Page Page Installation Accessories Mounting Hardware Provided Wall PreparationDescription QTY Installation Requirements MECHANICALCUT/SEVER HazardhazardInstallation Instructions for Baffle Adapter KIT BAK MECHANICALCUT/SEVER HazardWallMaster Thru-the-Wall CUT/SEVERInstallation Instructions Mechanical Hazard MECHANICALCUT/SEVER HazardAssembly & Installation Instructions Installation Instructions Subbase for WS, WE & WY Models Installation Instructions Architectural Grille Model AG MECHANICALCUT/SEVER Hazard WALLMASTER≤ THRU-THE-WALL AIR Conditioners Limited Warranty Technical Support Contact Information Page Page Friedrich AIR Conditioning CO