Friedrich WS10B10 service manual Single Phase Resistance Test, Ground Test

Page 27

Single Phase Resistance Test

WARNING

ELECTRIC SHOCK HAZARD

Turn off electric power before service or installation. Extreme care must be used, if it becomes necessary to work on equipment with power applied.

Failure to do so could result in serious injury or death.

Remove the leads from the compressor terminals and set the ohmmeter on the lowest scale (R x 1).

Touch the leads of the ohmmeter from terminals common to start (“C” to “S”). Next, touch the leads of the ohmmeter from terminals common to run (“C” to “R”).

Add values “C” to “S” and “C” to “R” together and check resistance from start to run terminals (“S” to “R”). Resistance “S” to “R” should equal the total of “C” to “S” and “C” to “R.”

In a single phase PSC compressor motor, the highest value will be from the start to the run connections (“S” to “R”). The next highest resistance is from the start to the common connections (“S” to “C”). The lowest resistance is from the run to common. (“C” to “R”) Before replacing a compressor, check to be sure it is defective.

GROUND TEST

Use an ohmmeter set on its highest scale. Touch one lead to the compressor body (clean point of contact as a good connection is a must) and the other probe in turn to each compressor terminal. If a reading is obtained the compressor is grounded and must be replaced.

Check the complete electrical system to the compressor and compressor internal electrical system, check to be certain that compressor is not out on internal overload.

Complete evaluation of the system must be made whenever you suspect the compressor is defective. If the compressor has been operating for sometime, a careful examination must be made to determine why the compressor failed.

Many compressor failures are caused by the following conditions:

1.Improper air flow over the evaporator.

2.Overcharged refrigerant system causing liquid to be returned to the compressor.

3.Restricted refrigerant system.

4.Lack of lubrication.

5.Liquid refrigerant returning to compressor causing oil to be washed out of bearings.

6.Noncondensables such as air and moisture in the system. Moisture is extremely destructive to a refrigerant system.

7.Defective capacitor.

26

Image 27
Contents Thru-the-wall Table Of Contents Your safety and the safety of others are very important Important Safety InformationRefrigeration System Hazards Property Damage Hazards IntroductionFriedrich wallmaster Model Number Code Performance Data Sleeve / Chassis DimensionsFire Hazard Electrical DataPlug/Outlet/Circuit Rating Electric Shock HazardTo activate Smart FanWY/WE heat-cool models To adjust fan speedElectronic Control Operation To activate Smart FanWS cool-only modelsTo set the timer Checking Room TemperatureTo Activate Money Saver WY/WE models To set mode of operation To adjust temperatureTo start unit Automatic component protection Error Code ModeTesting the Electronic Control Electronic Control PanelE7 Motor Operation E9 Heat Pump Failure Error Codes Listing for WS ModelsError Codes Listing for WE/WY Models Reboot the Control PanelFAN Motor Test Components TestingCoil Sensors FAN MotorCapacitor Check with Capacitor Analyzer CapacitorsHeating Element Drain PAN ValveRefrigeration System Sequence of Operation Refrigeration system under high pressure 410A Sealed System Repair ConsiderationsRisk of Electric Shock 410A Sealed Refrigeration System RepairsEquipment Required Equipment Must be CapableMethod Of Charging / Repairs Burn HazardFreeze Hazard Overcharged Refrigerant Systems Undercharged Refrigerant SystemsRestricted Refrigerant System Capillary Tube Systems Hermetic Components CheckMetering Device Check ValvePOSITION, 4 Port Reversing Valve Reversing Valve DESCRIPTION/OPERATIONChecking the Reversing Valve Testing the CoilProcedure For Changing Reversing Valve Touch Test in Heating/Cooling CycleExplosion Hazard Compressor Checks Ground Test Single Phase Resistance TestCompressor Replacement Recommended procedure for compressor replacementHigh Temperatures Rotary Compressor Special Troubleshooting and Service Routine Maintenance Sleeve / Drain Front CoverClearances Date Model Serial Room AIR Conditioner Unit Performance Test Data SheetGeneral Troubleshooting Tips General Troubleshooting Tips Cooling only Room AIR Conditioners Troubleshooting Tips Possible Cause Possible Solution Problem Possible Cause Possible Action HEAT/COOL only Room AIR Conditioners Troubleshooting Tips Heat Pump Troubleshooting Troubleshooting Chart Cooling Troubleshooting Chart Heating Heat PumpProblem Electrical Troubleshooting Chart Heat Pump System Cools When Heating is DesiredYES Malfunction of Valve Normal Function of ValvePage Page Page Installation Accessories Mounting Hardware Provided Wall PreparationDescription QTY MECHANICALCUT/SEVER Hazardhazard Installation RequirementsMECHANICALCUT/SEVER Hazard Installation Instructions for Baffle Adapter KIT BAKCUT/SEVER WallMaster Thru-the-WallMechanical Hazard MECHANICALCUT/SEVER Hazard Installation InstructionsAssembly & Installation Instructions Installation Instructions Subbase for WS, WE & WY Models Installation Instructions Architectural Grille Model AG MECHANICALCUT/SEVER Hazard WALLMASTER≤ THRU-THE-WALL AIR Conditioners Limited Warranty Technical Support Contact Information Page Page Friedrich AIR Conditioning CO