Friedrich WS10B10 service manual Method Of Charging / Repairs, Burn Hazard, Freeze Hazard

Page 19

Method Of Charging / Repairs

The acceptable method for charging the WallMaster system is the Weighed in Charge Method. The weighed in charge method is applicable to all units. It is the preferred method to use, as it is the most accurate.

The weighed in method should always be used whenever a charge is removed from a unit such as for a leak repair, compressor replacement, or when there is no refrigerant charge left in the unit. To charge by this method, requires the following steps:

1.Install a piercing valve to remove refrigerant from the sealedsystem. (Piercing valve must be removed from the system before recharging.)

2.Recover Refrigerant in accordance with EPA regulations.

WARNING

BURN HAZARD

Proper safety procedures must be followed, and proper protective clothing must be worn when working with a torch.

Failure to follow these procedures could

result in moderate or serious injury.

3. Install a process tube to sealed system.

CAUTION

FREEZE HAZARD

Proper safety procedures must be followed, and proper protective clothing must be worn when working with liquid refrigerant.

Failure to follow these procedures could result in minor to moderate injury.

4.Make necessary repairs to system.

5.Evacuate system to 200 microns or less.

6.Weigh in refrigerant with the property quantity of R-410A refrigerant.

7.Start unit, and verify performance.

WARNING

BURN HAZARD

Proper safety procedures must be followed, and proper protective clothing must be worn when working with a torch.

Failure to follow these procedures could

result in moderate or serious injury.

8. Crimp the process tube and solder the end shut.

18

Image 19
Contents Thru-the-wall Table Of Contents Your safety and the safety of others are very important Important Safety InformationRefrigeration System Hazards Property Damage Hazards IntroductionFriedrich wallmaster Model Number Code Performance Data Sleeve / Chassis DimensionsFire Hazard Electrical DataPlug/Outlet/Circuit Rating Electric Shock HazardTo activate Smart FanWY/WE heat-cool models To adjust fan speedElectronic Control Operation To activate Smart FanWS cool-only modelsChecking Room Temperature To set the timerTo Activate Money Saver WY/WE models To adjust temperature To set mode of operationTo start unit Automatic component protection Error Code ModeTesting the Electronic Control Electronic Control PanelE7 Motor Operation E9 Heat Pump Failure Error Codes Listing for WS ModelsError Codes Listing for WE/WY Models Reboot the Control PanelFAN Motor Test Components TestingCoil Sensors FAN MotorCapacitor Check with Capacitor Analyzer CapacitorsHeating Element Drain PAN ValveRefrigeration System Sequence of Operation Refrigeration system under high pressure 410A Sealed System Repair ConsiderationsRisk of Electric Shock 410A Sealed Refrigeration System RepairsEquipment Required Equipment Must be CapableBurn Hazard Method Of Charging / RepairsFreeze Hazard Overcharged Refrigerant Systems Undercharged Refrigerant SystemsRestricted Refrigerant System Capillary Tube Systems Hermetic Components CheckMetering Device Check ValvePOSITION, 4 Port Reversing Valve Reversing Valve DESCRIPTION/OPERATIONChecking the Reversing Valve Testing the CoilTouch Test in Heating/Cooling Cycle Procedure For Changing Reversing ValveExplosion Hazard Compressor Checks Ground Test Single Phase Resistance TestRecommended procedure for compressor replacement Compressor ReplacementHigh Temperatures Rotary Compressor Special Troubleshooting and Service Routine Maintenance Front Cover Sleeve / DrainClearances Date Model Serial Room AIR Conditioner Unit Performance Test Data SheetGeneral Troubleshooting Tips General Troubleshooting Tips Cooling only Room AIR Conditioners Troubleshooting Tips Possible Cause Possible Solution Problem Possible Cause Possible Action HEAT/COOL only Room AIR Conditioners Troubleshooting Tips Heat Pump Troubleshooting Troubleshooting Chart Heating Heat Pump Troubleshooting Chart CoolingProblem System Cools When Heating is Desired Electrical Troubleshooting Chart Heat PumpYES Malfunction of Valve Normal Function of ValvePage Page Page Installation Accessories Wall Preparation Mounting Hardware ProvidedDescription QTY MECHANICALCUT/SEVER Hazardhazard Installation RequirementsMECHANICALCUT/SEVER Hazard Installation Instructions for Baffle Adapter KIT BAKCUT/SEVER WallMaster Thru-the-WallMechanical Hazard MECHANICALCUT/SEVER Hazard Installation InstructionsAssembly & Installation Instructions Installation Instructions Subbase for WS, WE & WY Models Installation Instructions Architectural Grille Model AG MECHANICALCUT/SEVER Hazard WALLMASTER≤ THRU-THE-WALL AIR Conditioners Limited Warranty Technical Support Contact Information Page Page Friedrich AIR Conditioning CO