TROUBLESHOOTING TOUCH TEST CHART: TO SERVICE REVERSING VALVES

NORMAL FUNCTION OF VALVE

VALVE

DISCHARGETUBE

Compressorfrom

TUBESUCTION Compressorto

INSIDEtoTube COIL

OUTSIDEtoTube COIL

PilotLEFT TubeCapillary

PilotRIGHT TubeCapillary

NOTES:

** WARMER THAN VALVE BODY

 

 

 

 

 

 

 

 

OPERATING

 

 

 

 

 

 

 

* TEMPERATURE OF VALVE BODY

CONDITION

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1

2

3

4

5

6

POSSIBLE CAUSES

CORRECTIONS

Normal Cooling

Hot

Cool

Cool

Hot

*TVB

TVB

 

 

as (2)

as (1)

 

 

 

 

 

 

 

 

 

Normal Heating

Hot

Cool

Hot

Cool

*TVB

TVB

 

 

as (1)

as (2)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

MALFUNCTION OF VALVE

 

 

Check Electrical circuit and coil

 

 

 

No voltage to coil.

Repair electrical circuit.

 

 

 

 

 

 

 

 

 

 

Defective coil.

Replace coil.

 

 

 

 

 

 

 

 

Check refrigeration charge

 

 

 

Low charge.

Repair leak, recharge system.

 

 

 

 

 

 

 

 

 

 

Pressure differential too high.

Recheck system.

 

 

 

 

 

 

 

Valve will not

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Deenergize solenoid, raise head pressure,

shift from cool

 

 

 

 

 

 

 

reenergize solenoid to break dirt loose.

Hot

Cool

Cool,

Hot,

*TVB

Hot

Pilot valve okay. Dirt in one bleeder hole.

If unsuccessful, remove valve, wash

to heat.

as (2)

as (1)

out. Check on air before installing. If no

 

 

 

 

 

 

 

 

movement, replace valve, add strainer to

 

 

 

 

 

 

 

 

discharge tube, mount valve horizontally.

 

 

 

 

 

 

 

 

Stop unit. After pressures equalize, restart

 

 

 

 

 

 

 

Piston cup leak

with solenoid energized. If valve shifts,

 

 

 

 

 

 

 

reattempt with compressor running. If still

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

no shift, replace valve.

 

 

 

 

 

 

 

 

 

 

Hot

Cool

Cool,

Hot,

*TVB

*TVB

Clogged pilot tubes.

Raise head pressure, operate solenoid to

 

as (2)

as (1)

free. If still no shift, replace valve.

 

 

 

 

 

 

Valve will not

 

 

 

 

 

 

 

Raise head pressure, operate solenoid

 

 

Cool,

Hot,

 

 

Both ports of pilot open. (Back seat port

to free

shift from cool

Hot

Cool

Hot

Hot

partially clogged port. If still no shift,

as (2)

as (1)

did not close).

to heat.

 

 

 

 

 

 

 

replace

 

 

 

 

 

 

 

valve.

 

 

 

 

 

 

 

 

 

Warm

Cool

Cool,

Hot,

*TVB

Warm

Defective Compressor.

Replace compressor

 

as (2)

as (1)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Not enough pressure differential at start

Check unit for correct operating pressures

 

Hot

Warm

Warm

Hot

*TVB

Hot

of stroke or not enough fl ow to maintain

and charge. Raise head pressure. If no

 

 

 

 

 

 

 

pressure differential.

shift, use valve with smaller port.

 

 

 

 

 

 

 

Body damage.

Replace valve

Starts to shift

 

 

 

 

 

 

 

 

Hot

Warm

Warm

Hot

Hot

Hot

Both ports of pilot open.

Raise head pressure, operate solenoid. If

but does not

no shift, use valve with smaller ports.

 

 

 

 

 

 

 

complete

Hot

Hot

Hot

Hot

*TVB

Hot

Body damage.

Replace valve

reversal.

 

 

 

 

 

 

Valve hung up at mid-stroke. Pumping

Raise head pressure, operate solenoid. If

 

 

 

 

 

 

 

volume of compressor not suffi cient to

no shift, use valve with smaller ports.

 

 

 

 

 

 

 

maintain reversal.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Raise head pressure, operate solenoid.

 

Hot

Hot

Hot

Hot

Hot

Hot

Both ports of pilot open.

If no

 

 

 

 

 

 

 

 

shift, replace valve.

Apparent

Hot

Cool

Hot,

Cool,

*TVB

*TVB

Piston needle on end of slide leaking.

Operate valve several times, then recheck.

as (1)

as (2)

If excessive leak, replace valve.

leap in heat-

 

 

 

 

 

 

 

Hot,

Cool,

 

 

 

Operate valve several times, then recheck.

ing.

Hot

Cool

**WVB

**WVB

Pilot needle and piston needle leaking.

as (1)

as (2)

If excessive leak, replace valve.

 

 

 

 

 

 

 

 

 

 

Hot

Cool

Hot,

Cool,

*TVB

*TVB

Pressure differential too high.

Stop unit. Will reverse during equalization

 

as (1)

as (2)

period. Recheck system

 

 

 

 

 

 

 

 

 

 

 

 

 

Clogged pilot tube.

Raise head pressure, operate solenoid to

 

 

 

 

 

 

 

free dirt. If still no shift, replace valve.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Raise head pressure, operate solenoid.

 

 

 

Hot,

Cool,

 

 

 

Remove valve and wash out. Check on air

 

Hot

Cool

Hot

*TVB

Dirt in bleeder hole.

before reinstalling, if no movement, replace

 

as (1)

as (2)

Will not shift

 

 

 

 

 

valve. Add strainer to discharge tube.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Mount valve horizontally.

from heat to

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Stop unit. After pressures equalize, restart

cool.

 

 

 

 

 

 

 

 

 

Hot,

Cool,

 

 

 

with solenoid deenergized. If valve shifts,

 

Hot

Cool

Hot

*TVB

Piston cup leak.

reattempt with compressor running. If it

 

as (1)

as (2)

 

 

 

 

 

 

still will not reverse while running, replace

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

the valve.

 

Hot

Cool

Hot,

Cool,

Hot

Hot

Defective pilot.

Replace valve.

 

as (1)

as (2)

 

 

 

 

 

 

 

 

Warm

Cool

Warm,

Cool,

Warm

*TVB

Defective compressor.

Replace compressor

 

as (1)

as (2)

 

 

 

 

 

 

 

41

Image 42
Contents Thru-the-wall Table Of Contents Important Safety Information Your safety and the safety of others are very importantRefrigeration System Hazards Introduction Property Damage HazardsFriedrich wallmaster Model Number Code Sleeve / Chassis Dimensions Performance DataElectric Shock Hazard Electrical DataPlug/Outlet/Circuit Rating Fire HazardTo activate Smart FanWS cool-only models To adjust fan speedElectronic Control Operation To activate Smart FanWY/WE heat-cool modelsTo set the timer Checking Room TemperatureTo Activate Money Saver WY/WE models To set mode of operation To adjust temperatureTo start unit Electronic Control Panel Error Code ModeTesting the Electronic Control Automatic component protectionReboot the Control Panel Error Codes Listing for WS ModelsError Codes Listing for WE/WY Models E7 Motor Operation E9 Heat Pump FailureFAN Motor Components TestingCoil Sensors FAN Motor TestDrain PAN Valve CapacitorsHeating Element Capacitor Check with Capacitor AnalyzerRefrigeration System Sequence of Operation 410A Sealed System Repair Considerations Refrigeration system under high pressureEquipment Must be Capable 410A Sealed Refrigeration System RepairsEquipment Required Risk of Electric ShockMethod Of Charging / Repairs Burn HazardFreeze Hazard Undercharged Refrigerant Systems Overcharged Refrigerant SystemsRestricted Refrigerant System Check Valve Hermetic Components CheckMetering Device Capillary Tube SystemsReversing Valve DESCRIPTION/OPERATION POSITION, 4 Port Reversing ValveTesting the Coil Checking the Reversing ValveProcedure For Changing Reversing Valve Touch Test in Heating/Cooling CycleExplosion Hazard Compressor Checks Single Phase Resistance Test Ground TestCompressor Replacement Recommended procedure for compressor replacementHigh Temperatures Rotary Compressor Special Troubleshooting and Service Routine Maintenance Sleeve / Drain Front CoverClearances Room AIR Conditioner Unit Performance Test Data Sheet Date Model SerialGeneral Troubleshooting Tips General Troubleshooting Tips Cooling only Room AIR Conditioners Troubleshooting Tips Possible Cause Possible Solution Problem Possible Cause Possible Action HEAT/COOL only Room AIR Conditioners Troubleshooting Tips Heat Pump Troubleshooting Troubleshooting Chart Cooling Troubleshooting Chart Heating Heat PumpProblem Electrical Troubleshooting Chart Heat Pump System Cools When Heating is DesiredYES Normal Function of Valve Malfunction of ValvePage Page Page Installation Accessories Mounting Hardware Provided Wall PreparationDescription QTY Installation Requirements MECHANICALCUT/SEVER HazardhazardInstallation Instructions for Baffle Adapter KIT BAK MECHANICALCUT/SEVER HazardWallMaster Thru-the-Wall CUT/SEVERInstallation Instructions Mechanical Hazard MECHANICALCUT/SEVER HazardAssembly & Installation Instructions Installation Instructions Subbase for WS, WE & WY Models Installation Instructions Architectural Grille Model AG MECHANICALCUT/SEVER Hazard WALLMASTER≤ THRU-THE-WALL AIR Conditioners Limited Warranty Technical Support Contact Information Page Page Friedrich AIR Conditioning CO