Friedrich WS10B10 Hermetic Components Check, Metering Device, Check Valve, Capillary Tube Systems

Page 22

HERMETIC COMPONENTS CHECK

WARNING

BURN HAZARD

Proper safety procedures must be followed, and proper protective clothing must be worn when working with a torch.

Failure to follow these procedures could

result in moderate or serious injury.

WARNING

CUT/SEVER HAZARD

Be careful with the sharp edges and corners. Wear protective clothing and gloves, etc.

Failure to do so could result in serious injury.

METERING DEVICE

Capillary Tube Systems

All units are equipped with capillary tube metering devices.

Checking for restricted capillary tubes.

1.Connect pressure gauges to unit.

2.Start the unit in the cooling mode. If after a few minutes of operation the pressures are normal, the check valve and the cooling capillary are not restricted.

3.Switch the unit to the heating mode and observe the gauge readings after a few minutes running time. If the system pressure is lower than normal, the heating capillary is restricted.

4.If the operating pressures are lower than normal in both the heating and cooling mode, the cooling capillary is restricted.

CHECK VALVE

A unique two-way check valve is used on the reverse cycle heat pumps. It is pressure operated and used to direct the flow of refrigerant through a single filter drier and to the proper capillary tube during either the heating or cooling cycle.

One-way Check Valve

(Heat Pump Models)

NOTE: The slide (check) inside the valve is made of teflon. Should it become necessary to replace the check valve, place a wet cloth around the valve to prevent overheating during the brazing operation.

CHECK VALVE OPERATION

In the cooling mode of operation, high pressure liquid enters the check valve forcing the slide to close the opposite port (liquid line) to the indoor coil. Refer to refrigerant flow chart. This directs the refrigerant through the filter drier and cooling capillary tube to the indoor coil.

In the heating mode of operation, high pressure refrigerant enters the check valve from the opposite direction, closing the port (liquid line) to the outdoor coil. The flow path of the refrigerant is then through the filter drier and heating capillary to the outdoor coil.

Failure of the slide in the check valve to seat properly in either mode of operation will cause flooding of the cooling coil. This is due to the refrigerant bypassing the heating or cooling capillary tube and entering the liquid line.

COOLING MODE

In the cooling mode of operation, liquid refrigerant from condenser (liquid line) enters the cooling check valve forcing the heating check valve shut. The liquid refrigerant is directed into the liquid dryer after which the refrigerant is metered through cooling capillary tubes to evaporator. (Note: liquid refrigerant will also be directed through the heating capillary tubes in a continuous loop during the cooling mode).

HEATING MODE

In the heating mode of operation, liquid refrigerant from the indoor coil enters the heating check valve forcing the cooling check valve shut. The liquid refrigerant is directed into the liquid dryer after which the refrigerant is metered through the heating capillary tubes to outdoor coils. (Note: liquid refrigerant will also be directed through the cooling capillary tubes in a continuous loop during the heating mode).

21

Image 22
Contents Thru-the-wall Table Of Contents Important Safety Information Your safety and the safety of others are very importantRefrigeration System Hazards Introduction Property Damage HazardsFriedrich wallmaster Model Number Code Sleeve / Chassis Dimensions Performance DataElectric Shock Hazard Electrical DataPlug/Outlet/Circuit Rating Fire HazardTo activate Smart FanWS cool-only models To adjust fan speedElectronic Control Operation To activate Smart FanWY/WE heat-cool modelsChecking Room Temperature To set the timerTo Activate Money Saver WY/WE models To adjust temperature To set mode of operationTo start unit Electronic Control Panel Error Code ModeTesting the Electronic Control Automatic component protectionReboot the Control Panel Error Codes Listing for WS ModelsError Codes Listing for WE/WY Models E7 Motor Operation E9 Heat Pump FailureFAN Motor Components TestingCoil Sensors FAN Motor TestDrain PAN Valve CapacitorsHeating Element Capacitor Check with Capacitor AnalyzerRefrigeration System Sequence of Operation 410A Sealed System Repair Considerations Refrigeration system under high pressureEquipment Must be Capable 410A Sealed Refrigeration System RepairsEquipment Required Risk of Electric ShockBurn Hazard Method Of Charging / RepairsFreeze Hazard Undercharged Refrigerant Systems Overcharged Refrigerant SystemsRestricted Refrigerant System Check Valve Hermetic Components CheckMetering Device Capillary Tube SystemsReversing Valve DESCRIPTION/OPERATION POSITION, 4 Port Reversing ValveTesting the Coil Checking the Reversing ValveTouch Test in Heating/Cooling Cycle Procedure For Changing Reversing ValveExplosion Hazard Compressor Checks Single Phase Resistance Test Ground TestRecommended procedure for compressor replacement Compressor ReplacementHigh Temperatures Rotary Compressor Special Troubleshooting and Service Routine Maintenance Front Cover Sleeve / DrainClearances Room AIR Conditioner Unit Performance Test Data Sheet Date Model SerialGeneral Troubleshooting Tips General Troubleshooting Tips Cooling only Room AIR Conditioners Troubleshooting Tips Possible Cause Possible Solution Problem Possible Cause Possible Action HEAT/COOL only Room AIR Conditioners Troubleshooting Tips Heat Pump Troubleshooting Troubleshooting Chart Heating Heat Pump Troubleshooting Chart CoolingProblem System Cools When Heating is Desired Electrical Troubleshooting Chart Heat PumpYES Normal Function of Valve Malfunction of ValvePage Page Page Installation Accessories Wall Preparation Mounting Hardware ProvidedDescription QTY Installation Requirements MECHANICALCUT/SEVER HazardhazardInstallation Instructions for Baffle Adapter KIT BAK MECHANICALCUT/SEVER HazardWallMaster Thru-the-Wall CUT/SEVERInstallation Instructions Mechanical Hazard MECHANICALCUT/SEVER HazardAssembly & Installation Instructions Installation Instructions Subbase for WS, WE & WY Models Installation Instructions Architectural Grille Model AG MECHANICALCUT/SEVER Hazard WALLMASTER≤ THRU-THE-WALL AIR Conditioners Limited Warranty Technical Support Contact Information Page Page Friedrich AIR Conditioning CO