Friedrich WS10B10 service manual Problem Possible Cause Possible Action

Page 37

COOLING ONLY ROOM AIR CONDITIONERS: TROUBLESHOOTING TIPS

Problem

Possible Cause

Possible Solution

 

Sublimation:

Ensure that foam gaskets are installed in

 

When unconditioned saturated,

between window panes & in between the

 

outside air mixes with conditioned

unit & the sleeve. Also, ensure that fresh

 

air, condensation forms on the

air/exhaust vents (on applicable models) are in

Water “spitting”

cooler surfaces

the closed position & are in tact

into room

Downward pitch of installation is

Follow installation instructions to ensure that

 

downward pitch of installed unit is no less than

 

too steep towards back of unit

 

1/4” & no more than 3/8”

 

 

 

Restricted coil or dirty filter

Clean & advise customer of periodic cleaning

 

& maintenance needs of entire unit

 

 

Problem

Possible Cause

Possible Solution

 

Insufficient air circulation thru area

Adjust louvers for best possible air circulation

 

to be air conditioned

Excessive

 

Oversized unit

Operate in “MoneySaver” position

moisture

Inadequate vapor barrier in building

Advise customer

 

 

structure, particularly floors

 

 

Problem

Possible Cause

Possible Solution

 

Defective thermistor

Replace thermistor or electronic control board

 

Unit oversized

See sizing chart.

Unit short cycles

Chassis seal gasket not sealing or

Check gasket. Reposition or replace as

absent causing unit to short cycle

needed

 

 

 

 

 

Restricted coil or dirty filter

Clean & advise customer of periodic cleaning

 

& maintenance needs of entire unit

 

 

Problem

Possible Cause

Possible Action

Prolonged off

Defective indoor ambient air thermistor

Replace thermistor or electronic control board

cycles

 

 

 

 

 

Problem

Possible Cause

Possible Solution

 

Evaporator drain pan cracked or

Repair, clean or replace as required

 

obstructed

 

 

 

Water in compressor area

Detach shroud from pan & coil. Clean &

Outside water

remove old sealer. Reseal, reinstall & check

 

leaks

Obstructed condenser coil

Use pressure wash or biodegradable cleaning

 

agent to clean

 

 

 

Fan blade/slinger ring improperly

Adjust fan blade to 1/2” of condenser coil fin

 

positioned

pack

36

Image 37
Contents Thru-the-wall Table Of Contents Your safety and the safety of others are very important Important Safety InformationRefrigeration System Hazards Property Damage Hazards IntroductionFriedrich wallmaster Model Number Code Performance Data Sleeve / Chassis DimensionsPlug/Outlet/Circuit Rating Electrical DataElectric Shock Hazard Fire HazardElectronic Control Operation To adjust fan speedTo activate Smart FanWS cool-only models To activate Smart FanWY/WE heat-cool modelsChecking Room Temperature To set the timerTo Activate Money Saver WY/WE models To adjust temperature To set mode of operationTo start unit Testing the Electronic Control Error Code ModeElectronic Control Panel Automatic component protectionError Codes Listing for WE/WY Models Error Codes Listing for WS ModelsReboot the Control Panel E7 Motor Operation E9 Heat Pump FailureCoil Sensors Components TestingFAN Motor FAN Motor TestHeating Element CapacitorsDrain PAN Valve Capacitor Check with Capacitor AnalyzerRefrigeration System Sequence of Operation Refrigeration system under high pressure 410A Sealed System Repair ConsiderationsEquipment Required 410A Sealed Refrigeration System RepairsEquipment Must be Capable Risk of Electric ShockBurn Hazard Method Of Charging / RepairsFreeze Hazard Overcharged Refrigerant Systems Undercharged Refrigerant SystemsRestricted Refrigerant System Metering Device Hermetic Components CheckCheck Valve Capillary Tube SystemsPOSITION, 4 Port Reversing Valve Reversing Valve DESCRIPTION/OPERATIONChecking the Reversing Valve Testing the CoilTouch Test in Heating/Cooling Cycle Procedure For Changing Reversing ValveExplosion Hazard Compressor Checks Ground Test Single Phase Resistance TestRecommended procedure for compressor replacement Compressor ReplacementHigh Temperatures Rotary Compressor Special Troubleshooting and Service Routine Maintenance Front Cover Sleeve / DrainClearances Date Model Serial Room AIR Conditioner Unit Performance Test Data SheetGeneral Troubleshooting Tips General Troubleshooting Tips Cooling only Room AIR Conditioners Troubleshooting Tips Possible Cause Possible Solution Problem Possible Cause Possible Action HEAT/COOL only Room AIR Conditioners Troubleshooting Tips Heat Pump Troubleshooting Troubleshooting Chart Heating Heat Pump Troubleshooting Chart CoolingProblem System Cools When Heating is Desired Electrical Troubleshooting Chart Heat PumpYES Malfunction of Valve Normal Function of ValvePage Page Page Installation Accessories Wall Preparation Mounting Hardware ProvidedDescription QTY MECHANICALCUT/SEVER Hazardhazard Installation RequirementsMECHANICALCUT/SEVER Hazard Installation Instructions for Baffle Adapter KIT BAKCUT/SEVER WallMaster Thru-the-WallMechanical Hazard MECHANICALCUT/SEVER Hazard Installation InstructionsAssembly & Installation Instructions Installation Instructions Subbase for WS, WE & WY Models Installation Instructions Architectural Grille Model AG MECHANICALCUT/SEVER Hazard WALLMASTER≤ THRU-THE-WALL AIR Conditioners Limited Warranty Technical Support Contact Information Page Page Friedrich AIR Conditioning CO