COOLING ONLY ROOM AIR CONDITIONERS: TROUBLESHOOTING TIPS

Problem

Possible Cause

Possible Solution

 

Overload inoperative. Opens too

Check operation of unit. Replace overload if

 

soon

system operation is satisfactory

 

Compressor restarted before

Control board’s default of 3 minutes

 

system pressures equalized

delay inoperative. Replace board.

 

 

 

Compressor runs

 

Check voltage with unit operating. Check for

Low or fluctuating voltage

other appliances on circuit. Air conditioner

for short periods

should be in a dedicated circuit with proper

 

only. Cycles on

 

voltage & fused separately

overload

 

 

Incorrect wiring

Refer to appropriate wiring diagram

 

 

Shorted or incorrect capacitor

Test capacitor and replace as needed.

 

 

 

 

Restricted or low air flow through

Check for proper fan speed or blocked

 

condenser coil or evaporator coil

coils. Correct as needed.

 

Compressor running abnormally

Check for kinked discharge line or restricted

 

condenser. Refrigerant overcharge.

 

hot

 

Check amperage, connections.

 

 

 

 

 

Problem

Possible Cause

Possible Solution

 

No power

Check power supply, LCD I plug, wire

Unit does not

connection.

 

turn on

Incorrect wiring

Refer to appropriate wiring diagram

 

 

Defective thermistor

Replace thermistor or electronic control board

 

 

 

Problem

Possible Cause

Possible Solution

 

Poorly installed

Refer to Installation Manual for proper

 

installation

 

 

 

Fan blade striking chassis

Reposition - adjust motor mount

Noisy operation

 

Check that compressor grommets have not

Compressor vibrating

deteriorated. Check that compressor mounting

 

 

 

parts are not missing

 

Improperly mounted or loose

Check assembly & parts for looseness,

 

cabinet parts

rubbing & rattling

 

 

 

Problem

Possible Cause

Possible Solution

 

Evaporator drain pan overflowing

Clean obstructed drain trough

 

Condensation forming underneath

Evaporator drain pan broken or cracked.

 

Reseal or replace. No chassis gasket installed.

 

base pan

 

Install chassis gasket

 

 

 

Poor installation resulting in rain

Check installation instructions. Reseal as

Water leaks into

entering the room

required

 

Dirty evaporator coil. Use pressure wash

the room

Condensation on discharge grille

or biodegradable cleaning agent to clean.

 

 

louvers

Environmental phenomena: point supply

 

 

louvers upward. Put fan on high.

 

Chassis gasket not installed

Install gasket, per Installation manual

 

Downward slope of unit is too

Refer to installation manual for proper

 

steep inward

installation

35

Image 36
Contents Thru-the-wall Table Of Contents Important Safety Information Your safety and the safety of others are very importantRefrigeration System Hazards Introduction Property Damage HazardsFriedrich wallmaster Model Number Code Sleeve / Chassis Dimensions Performance DataElectrical Data Plug/Outlet/Circuit RatingElectric Shock Hazard Fire HazardTo adjust fan speed Electronic Control OperationTo activate Smart FanWS cool-only models To activate Smart FanWY/WE heat-cool modelsTo set the timer Checking Room TemperatureTo Activate Money Saver WY/WE models To set mode of operation To adjust temperatureTo start unit Error Code Mode Testing the Electronic ControlElectronic Control Panel Automatic component protectionError Codes Listing for WS Models Error Codes Listing for WE/WY ModelsReboot the Control Panel E7 Motor Operation E9 Heat Pump FailureComponents Testing Coil SensorsFAN Motor FAN Motor TestCapacitors Heating ElementDrain PAN Valve Capacitor Check with Capacitor AnalyzerRefrigeration System Sequence of Operation 410A Sealed System Repair Considerations Refrigeration system under high pressure410A Sealed Refrigeration System Repairs Equipment RequiredEquipment Must be Capable Risk of Electric ShockMethod Of Charging / Repairs Burn HazardFreeze Hazard Undercharged Refrigerant Systems Overcharged Refrigerant SystemsRestricted Refrigerant System Hermetic Components Check Metering DeviceCheck Valve Capillary Tube SystemsReversing Valve DESCRIPTION/OPERATION POSITION, 4 Port Reversing ValveTesting the Coil Checking the Reversing ValveProcedure For Changing Reversing Valve Touch Test in Heating/Cooling CycleExplosion Hazard Compressor Checks Single Phase Resistance Test Ground TestCompressor Replacement Recommended procedure for compressor replacementHigh Temperatures Rotary Compressor Special Troubleshooting and Service Routine Maintenance Sleeve / Drain Front CoverClearances Room AIR Conditioner Unit Performance Test Data Sheet Date Model SerialGeneral Troubleshooting Tips General Troubleshooting Tips Cooling only Room AIR Conditioners Troubleshooting Tips Possible Cause Possible Solution Problem Possible Cause Possible Action HEAT/COOL only Room AIR Conditioners Troubleshooting Tips Heat Pump Troubleshooting Troubleshooting Chart Cooling Troubleshooting Chart Heating Heat PumpProblem Electrical Troubleshooting Chart Heat Pump System Cools When Heating is DesiredYES Normal Function of Valve Malfunction of ValvePage Page Page Installation Accessories Mounting Hardware Provided Wall PreparationDescription QTY Installation Requirements MECHANICALCUT/SEVER HazardhazardInstallation Instructions for Baffle Adapter KIT BAK MECHANICALCUT/SEVER HazardWallMaster Thru-the-Wall CUT/SEVERInstallation Instructions Mechanical Hazard MECHANICALCUT/SEVER HazardAssembly & Installation Instructions Installation Instructions Subbase for WS, WE & WY Models Installation Instructions Architectural Grille Model AG MECHANICALCUT/SEVER Hazard WALLMASTER≤ THRU-THE-WALL AIR Conditioners Limited Warranty Technical Support Contact Information Page Page Friedrich AIR Conditioning CO