Friedrich WS10B10 service manual Cooling only Room AIR Conditioners Troubleshooting Tips

Page 35

COOLING ONLY ROOM AIR CONDITIONERS: TROUBLESHOOTING TIPS

Problem

Possible Cause

Possible Solution

 

Low voltage

Check voltage at compressor. 115V & 230V

 

units will operate at 10% voltage variance

 

 

 

Temperature not set cold enough or

Set temperature to lower than ambient

 

room air thermistor inoperative

temperature. Test thermistor and replace

 

 

if inoperative.

 

Compressor hums but cuts off on

Hard start compressor. Direct test compressor.

Compressor

overload

If compressor starts, add starting components

does not run

Open or shorted compressor

Check for continuity & resistance

 

windings

 

 

 

Open overload

Test overload protector & replace if inoperative

 

Open capacitor

Test capacitor & replace if inoperative

 

Inoperative system button

Test for continuity in all positions. Replace if

 

inoperative

 

 

 

Broken, loose or incorrect wiring

Refer to appropriate wiring diagrams to check

 

wiring. Correct as needed.

 

 

Problem

Possible Cause

Possible Solution

 

Inoperative system button

Test button & replace user interface if inoperative

 

Broken, loose or incorrect wiring

Refer to applicable wiring diagram. Repair.

Fan motor

Open capacitor

Test capacitor & replace if inoperative

does not run

Fan speed button defective.

Replace user interface if inoperative

 

Inoperative fan motor

Test fan motor & replace if inoperative (be sure

 

internal overload has had time to reset)

 

 

Problem

Possible Cause

Possible Solution

 

Undersized unit

Refer to industry standard sizing chart

 

Indoor ambient thermistor open

See alarms. Replace thermistor if necessary.

 

or shorted.

 

 

Does not cool or

Dirty filter

Clean as recommended in Owner’s Manual

only cools slightly

Dirty or restricted condenser or

Use pressure wash or biodegradable cleaning

 

evaporator coil

agent to clean

 

Poor air circulation

Adjust discharge louvers. Use high fan speed

 

Low capacity - undercharge

Check for leak & make repair

 

Compressor not pumping properly

Check amperage draw against nameplate. If

 

not conclusive, make pressure test

 

 

34

Image 35
Contents Thru-the-wall Table Of Contents Your safety and the safety of others are very important Important Safety InformationRefrigeration System Hazards Property Damage Hazards IntroductionFriedrich wallmaster Model Number Code Performance Data Sleeve / Chassis DimensionsFire Hazard Electrical DataPlug/Outlet/Circuit Rating Electric Shock HazardTo activate Smart FanWY/WE heat-cool models To adjust fan speedElectronic Control Operation To activate Smart FanWS cool-only modelsTo Activate Money Saver WY/WE models To set the timerChecking Room Temperature To start unit To set mode of operationTo adjust temperature Automatic component protection Error Code ModeTesting the Electronic Control Electronic Control PanelE7 Motor Operation E9 Heat Pump Failure Error Codes Listing for WS ModelsError Codes Listing for WE/WY Models Reboot the Control PanelFAN Motor Test Components TestingCoil Sensors FAN MotorCapacitor Check with Capacitor Analyzer CapacitorsHeating Element Drain PAN ValveRefrigeration System Sequence of Operation Refrigeration system under high pressure 410A Sealed System Repair ConsiderationsRisk of Electric Shock 410A Sealed Refrigeration System RepairsEquipment Required Equipment Must be CapableFreeze Hazard Method Of Charging / RepairsBurn Hazard Overcharged Refrigerant Systems Undercharged Refrigerant SystemsRestricted Refrigerant System Capillary Tube Systems Hermetic Components CheckMetering Device Check ValvePOSITION, 4 Port Reversing Valve Reversing Valve DESCRIPTION/OPERATIONChecking the Reversing Valve Testing the CoilExplosion Hazard Procedure For Changing Reversing ValveTouch Test in Heating/Cooling Cycle Compressor Checks Ground Test Single Phase Resistance TestHigh Temperatures Compressor ReplacementRecommended procedure for compressor replacement Rotary Compressor Special Troubleshooting and Service Routine Maintenance Clearances Sleeve / DrainFront Cover Date Model Serial Room AIR Conditioner Unit Performance Test Data SheetGeneral Troubleshooting Tips General Troubleshooting Tips Cooling only Room AIR Conditioners Troubleshooting Tips Possible Cause Possible Solution Problem Possible Cause Possible Action HEAT/COOL only Room AIR Conditioners Troubleshooting Tips Heat Pump Troubleshooting Problem Troubleshooting Chart CoolingTroubleshooting Chart Heating Heat Pump YES Electrical Troubleshooting Chart Heat PumpSystem Cools When Heating is Desired Malfunction of Valve Normal Function of ValvePage Page Page Installation Accessories Description QTY Mounting Hardware ProvidedWall Preparation MECHANICALCUT/SEVER Hazardhazard Installation RequirementsMECHANICALCUT/SEVER Hazard Installation Instructions for Baffle Adapter KIT BAKCUT/SEVER WallMaster Thru-the-WallMechanical Hazard MECHANICALCUT/SEVER Hazard Installation InstructionsAssembly & Installation Instructions Installation Instructions Subbase for WS, WE & WY Models Installation Instructions Architectural Grille Model AG MECHANICALCUT/SEVER Hazard WALLMASTER≤ THRU-THE-WALL AIR Conditioners Limited Warranty Technical Support Contact Information Page Page Friedrich AIR Conditioning CO