Equalization (continued) | P12 |
7521 AND 7522 BATTERY CHARGERS |
8.To change battery, use the up down arrow buttons to scroll the cursor to the Bat1 window.
9.Press the Select button.
10.Using the left and right arrow buttons, scroll between the three different battery banks connected to the charger.
11.Confirm Equalization parameters for the battery you wish to equalize.
12.Using the up down arrow buttons, scroll the cursor to the StartEQ window.
13.Press the Select button.
14.The charger will now begin to equalize and will display.
15.Monitor batteries and battery temperature throughout the Equalization process.
16.You may pause Equalization at any time by pressing the pause button.
17. If at any point during Equalization a DC load is applied to the battery being equalized, Equalization will stop.
NOTE: If you receive the below warning screen confirm batteries are fully charged and all DC loads connected to the batteries are turned off. Once complete proceed back to step 1 of the Equalization process.
18.You may stop Equalization at any time by pressing the stop button. NOTE: Pressing stop will return you to the Charger Summary screen.
19.Once the max Equalization voltage is reached the battery bank will begin to equalize for the designated Equalization time.
20.After the designated Equalization time is met Equalization will stop and the charger will return to the Charger Summary Screen.
Specifications are subject to change. See bluesea.com/P12 for current information. | 17 |