Installing the Inverter/Charger

Step 4: Connecting the DC Cables

DC Connection Precautions

ELECTRICAL SHOCK HAZARD

Connect and disconnect DC wiring only after opening the disconnect switches or breakers at all AC and DC sources.

Failure to follow these instructions will result in death or serious injury.

Recommended Cable Sizes and Lengths and Fuse Size

For recommended DC cables and fuse sizes, see Table 2 and Table 3 on page 14.

Preparing the Cables

To prepare the DC cables:

1.Cut the negative and positive cables to the required length. Strip off enough insulation so you can install the terminals you will be using.

Use crimp connectors. The connector should be designed for a

9.5mm stud size to connect to the Freedom SW 230V. If a crimp connector is used, it should be crimped using the tool indicated by the connector manufacturer.

2.Cut the DC ground cable to the required length. Strip off enough insulation so you can install the terminals you will be using.

Use crimp connectors. The connector should be designed for a

6.35mm stud size to connect to the Freedom SW 230V. If a crimp connector is used, it should be crimped using the tool indicated by the connector manufacturer.

3.Attach the connectors to the ends of both cables. Make sure no stray wire strands protrude from the connectors.

28

Freedom SW 230V Installation Guide

Image 42
Contents Freedom SW Sine Wave Inverter/Chargers Page This guide for use by qualified About This Guide PurposeImportant Safety Instructions Electrical Shock and Fire HazardElectrical Shock Hazard Fire and Burn Hazard Explosion HazardPrecautions When Working With Batteries Exposure to Chemicals and Gases Hazard Risk of Damage to the INVERTER/CHARGERRegulatory Limitations on USEPage Contents Page This guide for use by qualified installers only Page Introduction Materials List Freedom SW 230V Installation Guide Materials ListInstallation Codes Installation InformationBefore You Begin the Installation Electrical Shock and Fire HazardsAbout the Xanbus System Xanbus SystemXanbus-enabled Products and Accessories About the Xanbus SystemSize and Length of DC Cables Planning the InstallationTwo Key Performance Factors Mounting Location of the Freedom SWPlanning Preparations AC, DC, and Network ComponentsPlanning Preparations Planning Preparations AC Disconnect and Over-Current Protection Device AC ComponentsAC Input AC OutputAC Wiring Distribution PanelsModels Freedom SWDC Cabling DC ComponentsBatteries Fire HazardDC Disconnects and Over-Current Devices DC GroundingMarine Applications1 Heavy Item To unpack and inspectInstallation Tools and Materials ToolsMaterials Installing the Inverter/Charger OverviewChoosing a Location for the Inverter/Charger Fire and Explosion HazardHeat Hazard Safe Mounting the Inverter/Charger ConsiderationsTo mount the inverter/charger Approved Mounting Orientation Orientation? Comment Orientation Approved Mounting Orientation? Comment This guide for use by qualified Connecting the AC Input and AC Output Wires General AC Wiring ConsiderationsFIRE, Electrical SHOCK, and Energy Hazards Connecting AC Input Wires Correct Batter Polarity will Cause Damage toInstalling the Inverter/Charger Connecting the AC Output Wires To make the AC output wiring connectionsEquipment Damage Recommended Cable Sizes and Lengths and Fuse Size Connecting the DC CablesDC Connection Precautions Preparing the CablesGuidelines for Routing the DC Cables Connecting the DC Cables to the Inverter/Charger Equipment Damage DUE to Reverse PolarityTo connect the DC cables DC Cable Connections To connect the chassis ground Connecting the Battery Temperature Sensor BTS Mounting OptionsMounting to the Negative Battery Terminal To mount the sensor on the negative battery terminalBTS port Mounting to the Side of the Battery Case To mount the sensor on the battery caseConnecting to the Network To connect the Freedom SW 230V to the Xanbus networkPerforming Checks Prior to Initial Start-Up Testing Your Installation Testing in Invert ModeTesting in Charge Mode and AC Bypass Mode Installation CompleteTo verify that the Freedom SW 230V starts charging Stacking Features Parallel Stacking DC Connections for Stacked Inverters Connect the stacked system as followsNeutral Wiring for Stacked Inverters Configuring System for Stacked Operation To configure the system for stackingDisabling Search Mode on the Master Unit Search Mode Operation in Parallel StackingWiring Schematic Setting Search Mode on the Slave UnitCharger Settings in a Dual Freedom SW Configuration CalculationsTo set the Max Chg Rate % setting in each Freedom SW ExamplesTo set the Max Chg Rate % setting in each Freedom SW To set the Max Chg Rate % setting in each Freedom SW Inverter/Charger Physical Specifications Freedom SW Physical SpecificationsBattery Information Battery Bank SizingBattery AMP-HOURS Used = AC WATT-HOURS÷10 Estimating Battery RequirementsCalculating Battery Size Watts = Volts × AmpsDaily watt-hours needed Battery Banks Battery Bank Sizing WorksheetRestrictions on Motor Size Battery Information Battery Sizing Worksheet Battery Cabling and Hook-up Configurations Battery Series ConnectionBattery Series-Parallel Connections Specifications Environmental SpecificationsInverter Specifications Charger Specifications Transfer and General Specifications Inverter Drip Shield Installation To install the drip shieldShock Hazard Drip Shield Placement Desktop Mount 20 mm No clearance required here Page Page Schneider Electric Solar Inverters USA Inc