
Configuring System for Stacked Operation
Verify all DC and AC connections. Check Xanbus network connections and ensure that terminators are installed at devices at each end of the network. The simplest system includes a Xanbus SCP, the two Freedom SW 230V inverter/chargers to be stacked and two Xanbus terminators.
For both units to operate in stacked configurations, a Master and Slave have to be assigned. The default
To configure the system for stacking:
1.Apply DC power to both inverter/chargers.
Power up order has no impact. Because there are now two Master units in the system, the SCP will display an F66 fault, a “system configuration fault”.
2.From the SCP System Status screen, press Enter. The Select Device screen appears.
3.Select the inverter to configure as a Slave unit from the list, then press Enter.
4.Bring up the Advanced Settings screen by pressing Enter, Up, and Down arrow buttons all together.
975-0697-01-01
Stacking Features
5.Select Advanced Settings and press Enter. The Advanced Settings screen appears.
6.Scroll down to select Stacking.
At this point all devices in the system will be automatically placed in standby mode. All three LEDs on the inverter to be configured will start flashing.
|
|
| only. | |
FSW3524 00: Stacking |
| personnel | ||
|
| |||
Dev Name | [00] |
|
| |
Dev Number | [01] |
|
| |
Stack Mode | [Master] | [*Master] [Slave] [L2Master] |
| |
Battery | [Batt1] |
| qualified | |
|
| |||
7. Select Stack Mode and press Enter. | ||||
Figure 19 Stacking Menu Screen |
| |||
8. For Parallel Stacking: Select Slave and press Enter. | by | |||
use | ||||
9. Press the Func button repeatedly until the System Status | ||||
for | ||||
screen appears. |
| |||
NOTES: |
|
| guide | |
|
| This | ||
The only situation in which the Slave may shut down the Master |
inverter is during fault conditions such as high or low battery voltage, overcurrent, or
45