Stacking Features
Example 4: System composed of two stacked Freedom SW 3524- 230s. Each Freedom SW
The industry’s commonly accepted practice suggests a typical Flooded battery bank capacity (C) of 600Ah should not be charged beyond 25% of its capacity (150A). Therefore, when configuring the two stacked Freedom SW chargers, each charger may have a maximum charger output current of 75A (that is, 600 × 25% × 1/2) into the common battery bank as described in the Calculations section. Also, the System Total BULK output current is calculated as 150A (that is, 75A + 75A).
To set the Max Chg Rate (%) setting in each Freedom SW 3524-230:
1.Divide the maximum allowable charger output current of 75A by the Freedom SW
So, 75 ÷ 90, gets an approximate value of 0.83 (or 83%) which can be set exactly to 83%.
2.Set the Max Chg Rate (%) setting to 83 which means 83%.
In this example, the actual output current is limited to 83% of 90A which is 74A. Therefore, the actual System Total BULK output current comes out to just under 150A.
50 | Freedom SW 230V Installation Guide |