Tripp Lite APSX, APINT Series owner manual Select Battery Charger-Limiting Points-OPTIONAL

Page 6
MAX OFF (GREATER (LESSER
LOAD LOAD
ON) ON)
B4 B3 B2 B1
B4 B3 B2 B1

Configuration (continued)

Select Battery Charger-Limiting

B4

 

B3

 

B2

 

B1

Points—OPTIONAL

 

 

 

 

 

 

 

Most Limiting (#B1 & #B2 Up, factory setting): Charger-limiting takes effect the moment any 230V AC load is applied;

charger output falls gradually from full output at no 230V load passing through to no output at full load.

Less Limiting (#B1 Down & #B2 Up): Charger-limiting begins when the Inverter/Charger’s load reaches 33% of the Inverter/Charger’s load rating. Charger output falls gradually from full output at

33% of the Inverter/Charger’s load rating to about 33% of full output at full load.

Least Limiting (#B1 Up & #B2 Down):

Charger-limiting begins at when the Inverter/Charger’s load reaches 66% of the Inverter/Charger’s load rating. Charger output falls gradually from full output at

66% of the Inverter/Charger’s load rating to about 66% of full output at full load.

No Limiting (#B1 & #B2 Down): No

 

 

 

 

 

 

 

 

 

 

 

 

 

 

B4

 

B3

 

B2

 

B1

 

charger-limiting occurs at any load size.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

B3 Select Equalize Battery Charge—OPTIONAL

This DIP Switch is momentarily

 

 

 

 

 

 

 

 

 

 

 

 

B4

 

B3

 

B2

 

B1

"Reset"

engaged to begin the process of equal-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

izing the charge state of your battery’s

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

cells by time-limited overcharge of all

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

"Equalize"

cells. This can extend the useful life of

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

certain types of batteries; consult with your battery’s manufac- turer to determine if your batteries could benefit from this process. The charge equalization process is automatic; once started, it can only be stopped by removing the input power.

Setting Procedure

Move to “Equalize” (DOWN) position for three seconds.

Move to “Reset” (UP) position and leave it there. This is the factory default setting.

CAUTION: Do not leave DIP switch #3 in the down position after beginning process. Battery charge equalization should only be performed in strict accordance with the battery manufacturer’s instructions and specifications.

Battery Charge

Switch Position

Reset

Up (factory setting)

Equalize

Down—momentarily

B4 Set Battery Charging Amps—OPTIONAL

Check specifications for your unit’s high-

and low-charging amp options. By setting B4 B3 B2 B1 on high charging, your batteries will

charge at maximum speed. When setting on low charging, you lengthen the life of

your batteries (especially smaller ones).

Battery Charger

Switch Position

Low Charge Amps

Up (factory setting)

High Charge Amps

Down

CAUTION: When switching to the High Charge Amp setting, the user must ensure that the amp hour capacity of their battery system exceeds the amperage of the High Charge Amp setting or the batteries may be damaged or degraded.

Set Battery Charge Conserver (Load Sense) Control—OPTIONAL (Not on 750 or 1250 models)

In order to save battery power, the unit's inverter automatically shuts off in the absence of any power demand from connected equipment or appliances (the electrical load). When the Inverter/Charger detects a load, it automatical-

ly turns its inverter function on. Users may choose the minimum load the Inverter/Charger will detect by adjusting the Battery Charge Conserver Control (see diagram). Using a small tool, turn the control clockwise to lower the

minimum load that will be detected, causing the inverter to turn on for smaller loads. When the control is turned

fully clockwise, the inverter will operate even when there is no load. Turn the control counterclockwise to increase the minimum load that will be detected, causing the inverter to stay off until the new minimum load is reached.

NOTE: The factory setting for the control is fully clockwise. However, based on the threshold load to which you’d like the inverter to respond, you should adjust the control counterclockwise to reduce its sensitivity until the inverter is active only when connected equipment or appliances are actually in use.

Connect Remote Control—Optional

All models feature an 8-conductor telephone style receptacle on the front panel for use with an optional remote control module (Tripp Lite model APSRM4, sold separately). The remote module allows the Inverter/Charger to be mounted in a compartment or cabinet out of sight, while operated conveniently from a remote location. See instructions packed with the remote control module.

6A

Image 6
Contents Contents Apsx & Apsint Series DC-to-AC Inverter/ChargersImportant Safety Instructions Limited WarrantyFeature Identification Operation Switch ModesIndicator Lights Flashing red Inverter ShutdownGroup a DIP Switches ConfigurationSet Configuration DIP Switches Group B DIP SwitchesSelect Battery Charger-Limiting Points-OPTIONAL Match Battery Amp-Hour Capacity to Your Application Battery SelectionSelect Battery Type ExampleMounting Vehicular and Non-Vehicular Horizontal MountBattery Connection Non-Vehicular or VehicularAC Input/Output Connection Service MaintenanceTroubleshooting Mejor para su equipo ContenidoConfiable energía de respaldo de emergencia Mejor para sus bateríasInstrucciones de seguridad importantes Garantía limitadaIdentificación de funciones Operación Modos de conmutaciónLuces indicadoras Conmutadores DIP Grupo a ConfiguraciónFijar conmutadores DIP de configuración Conmutadores DIP Grupo BConfiguración continuación Opciones de carga alta y baja de su unidadUsted prolonga la vida de sus baterías Selección de batería Seleccionar tipo de bateríaEjemplo Montaje Montaje horizontal vehicular y no vehicularConexión de batería No vehicular o VehicularConexión de entrada/salida de corriente alterna Solución de problemas ServicioMantenimiento Meilleur pour votre équipement Table des matièresAlimentation fiable en énergie de secours Meilleur pour vos batteriesGarantie limitée Mise en garde concernant lemplacementImportantes consignes de sécurité Mises en garde Connexion déquipementIdentification de caractéristiques Fonctionnement Commutation des modesVoyants lumineux Réglage de la configuration des commutateurs DIP Groupe a de commutateurs DIPGroupe B de commutateurs DIP Configuration suite Choix de batterie Choisir le type de batterieExemple Montage Montage horizontal véhiculaire et non-véhiculaireBranchement des batteries Véhiculaire ou non- véhiculaireBranchement Entrée/Sortie CA Réparation EntretienDépannage Ñîäåðæàíèå Âàæíûå óêàçàíèÿ ïî òåõíèêå áåçîïàñíîñòè Îãðàíè÷åííàÿ ãàðàíòèÿÎïðåäåëåíèå ýëåìåíòîâ ÀÂÒÎÌÀÒÈ×ÅÑÊÈÉÔóíêöèîíèðîâàíèå Ïåðåêëþ÷åíèå ðåæèìîâÊîíôèãóðàöèÿ Óñòàíîâêà êîíôèãóðàöèîííûõ DIP-ïåðåêëþ÷àòåëåéÊîíôèãóðàöèÿ ïðîäîëæåíèå 540 âàòò 12  = Âûáîð áàòàðåèÈíñòðóìåíòû 45 àìïåð ïîñòîÿííîãî òîêà õ 5 ÷àñîâ ðàáîòûÌîíòàæ Ïîäêëþ÷åíèå áàòàðåè Ìîáèëüíîå èëè ñòàöèîíàðíîåÏîäêëþ÷åíèå âõîäà/âûõîäà ïåðåìåííîãî òîêà Îáñëóæèâàíèå Òåõíè÷åñêîå îáñëóæèâàíèåÓñòðàíåíèå íåèñïðàâíîñòåé