INVERTER DEFAULT VALUES (subject to change with upgrades)
24 VDC System | DEFAULT | MINIMUM | MAXIMUM |
Float Voltage | 27.4 Vdc | 24 Vdc | 30 Vdc |
Absorb Voltage | 29.4 Vdc | 26 Vdc | 32 Vdc |
EQ Voltage | 28.8 V | 28 Vdc | 34 Vdc |
ReFloat | 25 Vdc | 22 Vdc | 26 Vdc |
LBCO | 21 Vdc | 18 Vdc | 24 Vdc |
Absorb Time | 2.0 hours | 0.0 hours | 24.0 hours |
EQ Time | 1.0 hours | 0.0 hours | 24.0 hours |
Float Time | 1.0 hours | 0.0 hours | 24.0 hours |
Charger Draw | 5 Aac | 0 Aac | 7 Aac |
AC1/Grid Transfer Delay | 6 AC cycles | 0 AC cycles | 240 AC cycles |
AC2/Gen Transfer Delay | 60 AC cycles | 0 AC cycles | 240 AC cycles |
|
|
|
|
Grid Lower Limit | 108 Vac | 40 Vac | 115 Vac |
Grid Upper Limit | 140 Vac | 130 Vac | 150 Vac |
Grid Connect Delay | 0.5 min | 0.2 min | 15.0 min |
Gen Lower Limit | 108 Vac | 40 Vac | 115 Vac |
Gen Upper Limit | 140 Vac | 130 Vac | 150 Vac |
|
|
|
|
AC DROP or USE | USE | N/A | N/A |
Charger OFF/AUTO/ON | AUTO | N/A | N/A |
|
|
|
|
Search Threshold | 6 watts | 0 watts | 50 watts |
Search Pulses | 8 | 2 | 20 |
Search Pulse Spacing | 60 AC cycles | 4 AC cycles | 120 AC cycles |
Stacking Phase | 1 or 2 phase | N/A | N/A |
InPut Select | Gen | N/A | N/A |
Grid Input Settings | 28 Aac | 5 Aac | 30 Aac |
Gen Input Settings | 28 Aac | 2 Aac | 30 Aac |
Set Output Voltage | 120 Vac | 115 Vac | 125 Vac |
36