Outback Power Systems OBX-IC2024S-120/60 System Protection, AC and DC Grounding Requirements

Page 9

SYSTEM PROTECTION

Electrical systems are designed to protect you, the wires, the components, and the devices served by the system.

Each Inverter must be part of a permanently grounded electrical system (see below). Grounding protects people and equipment from electrical shock. Grounding must be performed according to required codes and regulations.

Circuit breakers protect wiring by limiting the amount of current entering a system. All wired electrical systems require circuit breakers or fuses for protection. See following pages for sizing.

OutBack Power Systems offers both breakers and fuses for overcurrent protection. If they are provided by other vendors, they must be properly rated.

AC AND DC GROUNDING REQUIREMENTS

Connect only to a grounded, permanent wiring system. Use the box lug on top of the Inverter.

For all installations, the negative battery conductor should be bonded to the grounding system at one (and only one) point in the system.

The Inverter should never be positive-grounded or used in a positive-ground installation. (In other words, never connect battery positive to ground).

For all installations, the AC neutral wire must be connected to the chassis ground at one (and only one) point in the system.

If the installation has no connection between neutral and ground, the Inverter has an internal switch which provides the bond when no other source is present. When a generator is used with the Inverter under these conditions, the generator’s neutral and ground wires must also be bonded together, so that its bond protects the system when the generator is running. The neutral wires on the Inverter’s input and output plugs must be electrically isolated from each other.

If the load panel on the Inverter’s output has neutral and ground bonded together, you should disable the Inverter’s automatic bond switching. (Instructions for this are on page 13.) Under these conditions, the generator’s neutral and ground should NOT be bonded together. The Inverter’s input and output neutral wires can be electrically common.

Failing to establish a neutral-ground bond is a safety hazard. Establishing more than one bond can result in nuisance tripping of GFCIs, and is also a safety hazard.

The equipment ground on each is marked with this symbol:

Box lug for grounding the

Inverter chassis

7

Image 9
Contents OBX-IC2024S-120/60 Warranty Summary OutBack Power SystemsContact Information DisclaimerTable of Contents OutBack Extreme Rugged Water Resistant Inverter/Charger Inverter Maintenance Unit DimensionsParts Included Required ConductorsUse and Storage Initial InspectionSafety and Human Factors Important Battery InstructionsMounting AC and DC Grounding Requirements System ProtectionWire Connections DC WiringConnection Torque SERIES/PARALLEL Example Battery WiringBattery Wiring Examples for a 24-volt system Battery Wiring Examples for a 24-volt system Connector Plate AC WiringPage Locking collar Powering UPMate AT a Glance MATE2 System Controller and DisplayMounting the Mate 13504pINV Hot Key HOT KeysKey AC in Hot KeyPress Three Times SUM Status Setup ADV Soft KeysSummary Screens Fxmate Setup ScreensSrch Input Main Down Grid GEN PortBack Type Delay Roll SETUP/MATE/SUMMARY PG1 Sumry COM Main SETUP/MATE/SUMMARYBack Type Delay Roll Clock CNT Glow PG2Back INC DEC SETUP/MATE/SUM/TYPE SETUP/MATE/SUM/TYPEBack INC DEC SETUP/MATE/SUMMARY Back INC DECSETUP/MATE/SUMMARY/TYPE Communication Setup ScreensBack INC DEC SETUP/MATE/SUMMARY/TYPE PG1 Sumry COM MainBack Repoll PC Debug PG1 Sumry Comm MainFX CC DC Main Status ScreensReading a Status Screen Definition Status Meter ScreensPressing the Batt soft key brings up the first Batt screen Status Battery ScreensModes Meter Batt PG2 PG1 Error Warn PG3 Status Error ScreensStatus Warning Screens Disconnect Screens Status Disconnect ScreensInstallation Drawing Installation Check List OBX-IC2024S-120/60 Inverter/Charger Specifications Model Ampacity DC Breaker DC Fuse Maximum AC Input CurrentVDC System Inverter Default Values subject to change with upgradesTroubleshooting MaintenanceOutBack Extreme Inverter/Chargers Year Limited Warranty2008-01-07 Equipment Owner Address for warranty certificatePage Corporate Headquarters European Sales Office