ADVANCED MENU
Low Cutoff |
|
< .6 Amp |
|
EXIT NEXT | +AMP |
ADVANCED MENU
MPPT Mode Auto Sweep
EXIT NEXT nonGT MODE
The default value is nonGT or
Low Cutoff sets the battery charger’s lowest allow- able current limit the MX60 will charge in MPPT mode before stopping and returning to “Snoozing.” The Low Cutoff is adjustable from .2 amps to 1 amp;
.6 amps is the default Low Cutoff current. Raising this value will assist the MX60 in entering “Sleeping” mode at night. Press the <+Amp> soft key to raise this limit. When fi nished, press the <NEXT> soft key to view the MPPT Mode screen.
This screen allows the user to choose one of these modes:
•Auto Sweep MPPT Mode (the default and preferred mode), which sweeps the PV upon wakeup and then does mini Sweeps from that point on at the selected Sweep Interval. If the sweep interval is set at 0 minutes, the MX60 awakes every 1.5 hours and does a full sweep. Auto Restart applies here as well (see LOG2 Auto Restart, page 52).
•
Press the <MODE> soft key to choose an MPPT mode and the <nonGT> soft key if you have an Out- Back