Secondary LOG2 Screen
The Secondary Log2 screen shows the basic recharging state of the MX60 (EQ, FLOAT) time in min- utes, and the daily maximum (HighWatts) wattage seen by the MX60 during the day.
When initiated, EQ information will be
displayed here.
The lower and upper
battery temperatureBACK compensation voltage
0000 float Tmin
0705 HighWatts
Lo 13.2 Hi 14.8
DCkWh
The present day’s time— in
This value is the peak daily Watts seen by the MX60.
is visible and active only when the mode is set to LMIT
(5.11 Rev.).
Press soft key #3 to display the accumulated total kWh reading in AC or DC the Data
Logging screen.
•DCkWh (default) shows DC kiloWatthours and should be used in a non grid tied system.
•ACkWh is used with a grid tied system. The heading in the logging screen will change to “TotalKWh AC”. TotalKWh AC is based on a 90% inverter efficiency (1kWH DC = 0.9kWH AC).
Note: Float time does not accumulate (1) when the MX60 is sleeping or (2) when an external power source keeps the battery above fl oat voltage.