To meet NEC compliance, the largest PV array that can be connected to the MX60 should have a rated
Wire Distance Chart
12 Volt PV Array
16V MPP Typical
Distance in Feet
(Two Wires)
1.5% Voltage Drop
12 Volt Battery System
24 Volt PV Array
32V MPP Typical
Distance in Feet
(Two Wires)
1.5% Voltage Drop
12 or 24 Volt Battery
System
48 Volt PV Array
64V MPP Typical
Distance in Feet
(Two Wires)
1.5% Voltage Drop
12, 24 or 48 Volt Battery
System
Amps | Wire Gauge |
|
|
|
|
| ||
#8 | #6 | #4 | #2 | #1/0 | #2/0 | #4/0 | ||
| ||||||||
8 | 22 | 35 | 57 | 90 | 145 | 180 | 290 | |
10 | 18 | 28 | 45 | 72 | 115 | 145 | 230 | |
15 | 12 | 19 | 30 | 48 | 76 | 96 | 150 | |
20 | 9 | 14 | 22 | 36 | 57 | 72 | 116 | |
30 | 6 | 9 | 15 | 24 | 38 | 48 | 77 | |
40 | 4 | 7 | 11 | 18 | 29 | 36 | 56 | |
50 | 3 | 5 | 9 | 4 | 23 | 29 | 46 | |
Amps | Wire Gauge |
|
|
|
|
| ||
#8 | #6 | #4 | #2 | #1/0 | #2/0 | #4/0 | ||
| ||||||||
8 | 45 | 71 | 114 | 180 | 290 | 360 | 580 | |
10 | 36 | 57 | 91 | 145 | 230 | 290 | 460 | |
15 | 24 | 38 | 60 | 96 | 153 | 192 | 300 | |
20 | 18 | 29 | 45 | 72 | 115 | 145 | 232 | |
30 | 12 | 19 | 30 | 48 | 77 | 97 | 154 | |
40 | 9 | 14 | 23 | 36 | 58 | 72 | 112 | |
50 | 7 | 11 | 18 | 29 | 46 | 58 | 86 | |
Amps | Wire Gauge |
|
|
|
|
| ||
#8 | #6 | #4 | #2 | #1/0 | #2/0 | #4/0 | ||
| ||||||||
8 | 90 | 142 | 228 | 360 | 580 | 720 | 1160 | |
10 | 72 | 114 | 182 | 290 | 460 | 580 | 920 | |
15 | 48 | 76 | 120 | 192 | 306 | 384 | 600 | |
20 | 36 | 58 | 90 | 144 | 230 | 290 | 464 | |
30 | 24 | 38 | 60 | 96 | 154 | 194 | 308 | |
40 | 18 | 28 | 46 | 72 | 116 | 144 | 224 | |
50 | 14 | 22 | 36 | 58 | 92 | 116 | 172 |
80 | OutBack Power Systems Inc. |