WIRE AND DISCONNECT SIZING

The MX60 has a 60 amp current output limit (default) and is listed to operate continuously at 60 amps depending on the nominal PV array voltage and the nominal battery voltage. There is no 80% de-rating as required by the NEC for fuses, conductors, and most circuit breakers.

The MX60 is a buck type converter and cannot boost the output current when the PV array peak power point voltage is at or below the battery voltage as may happen on hot days in 24 VDC PV and a 24 VDC battery system or a 48 VDC PV and a 48 VDC battery system.

To meet minimum NEC requirements (NEC 310.15, 690.8, 9), the output conductor should have an ampacity of 75 amps after any temperature and conduit fi ll corrections. This would normally indicate that the output conductors be 4 AWG, but a larger size may be required if there are temperature and/or conduit fi ll corrections required. With an output conductor rated at 75 amps (1.25 X the continuous output current), the OutBack OBDC-60 breaker—rated for continuous 100% duty at 60 amps —can be used to provide the code-required disconnect and output circuit over current protection.

The PV array output connected to the MX60 input may be as high 60 amps, but at this current level, there is very little (if any) current boosting or maximum power-point tracking due to the

60-amp output current limit. Additionally, the input current may exceed 60 amps on bright sunny days and any excess power would be lost. The size and ampacity of the input conductors must be selected to handle 1.56 times the short-circuit current of the PV array. Any disconnect or circuit breaker connected to the input conductors must also be rated at 1.56* times the short-circuit current for the PV array unless the breaker is rated for 100% duty in its enclosure. If that is the case, the circuit breaker may be rated at 1.25 times the PV array short-circuit current. OutBack OBDC-XX breakers are 100% duty rated breakers.

In terms of NEC compliance and the MX60’s 60-amp output rating, the largest PV array it can con- nect to should have a rated short-circuit current of 48 amps. This meets NEC requirements and allows the MX60 to perform maximum power-point tracking functions. The following charts show maximum distance in feet of various gauge two-conductor copper wire from the PV array to the MX60 with a 1.5% maximum voltage drop. Temperature and conduit fi ll corrections may

be required.

*UL requires Isc to be multiplied by 125% for the conductor rating

82

OutBack Power Systems Inc.

Image 82
Contents MX60 PV Mppt Warranty Summary Dear OutBack CustomerEN 61000-6-3 see January 29, 2007 REV 7.0 Software REV 5.10Table of Contents Battery Temperature Compensated Voltage SET Point Scope MX60 PV Mppt Maximum Power Point Tracking Charge ControllerIntroduction OutBack Power Systems Inc Personal Precautions Check the PV array voltage before connecting it to the MX60 Open Circuit VOLTAGE/WIRE and Disconnect SizingWire and Disconnect Sizing To 0 C 49 to 32 FField Wiring Connections and Surge Protection OutBack Power Systems Inc OutBack Power Systems Inc OutBack Power Systems Inc Battery System Voltage KEY to the Example DiagramsPowering UP OFF Screen this screen is initially blank at power up150 PasswordExitenter Enter +Exit Enter OutBack12V Power Systems MX60Battery Voltage Screen Are you sure? 12 24 36 48 NOYes00.0 a Status ScreenPV 005 Bat 12.5 Watts Aux OffPV 087 Bat 12.5 05.0 a 32.9 a Watts 0412 Aux Off KWHrs 00.0 PV 113 Bat 12.5 00.0 a Watts 0000 Aux Off KWHrs SleepingMppt Logging Accessing the Main MenuCharger Aux Light Misc ExitAmps Volts Charger SetupLimit Absorb 60.0 14.4 13.6Manual AUX ModeTerminals. OFF indicates changes to the next mode VDC OffAUX Mode Path OutBack Power Systems Inc Exit Next AUX ModeExit Next on OFF AUX Mode Vent FAN VoltsExit Next Time Volt PV Volts PV Trigger Off140 Back + Exit Next Time Volt Exit Next Time Volt AUX ModePV Trigger Hold Time Sec 01.1 Back +Absorb-Float-EQ Relative Volts 00.0 00.2 AUX Mode Error Alarm Exit NextDiversion Off BackHold Delay 01.0 Time Seconds Example of DiversionDiversion Load and AUX Wiring Set-Up Illustrated Sec TimerLow Batt Disconnect 001RE-CONNECT Volts Exit Next Time Volt Disconnect Volts+ ReCon 14.4 Back + DisVLogging Log2 Remote OffPress the Next soft key to view the Remote screen Backlight Control Always Exit Auto on OFF EQ-BATTERY EqualizeBacklight Charger Aux *Light EQ Misc Optimize Logging Log2Exit Next -HRS +HRS Battery EqualizeExit NEX -EQV +EQV Battery Equalize Back Auto Start Stop000 Auto ModeCount Exit DAY +DAYGT State PWM% ChgT 255 07 50.0 005 Tmp Comp a14.4 f13.6 MISC-MISCELLANEOUSExit Next Wide Rstrt WIDE/LMIT Battery Temperature Compensated Limits 13.2 Lower Limit 14.8 Back + DisV14.8 DisVExit Next Wide Rstrt Force Exit Next Float Bulk Force Float = fl oat cycle Force Bulk = bulk cycleCFB Miscellaneous ScreenPCB AMP +AMPCharger Aux Light Misc *Advanced Logging Log2 Snooze Mode LowcutoffAdvanced Exit Advanced MenuPark Mpp 77 % Voc Exit Next -Voc +Voc Mpp Range Limit %Voc min max Exit Next 1/2 90%Vbatt Calibration 12.8v Sweep Interval MinutesExit Next -MIN MAX+ Advanced Menu Exit Next -V +VLow Cutoff Amp Mppt Mode Auto Sweep Exit Next nonGT ModeThis screen allows the user to choose one of these modes Absorb Time Limits 000m 2hr Exit Next MIN+ MAX+Exit Exit CLR +DAY -DAY Data LoggingDaily KWhours 00.0 Float time mins 0000 TotalKWh 0000 Clear Back Totl DalyClearing Totals and Daily Stats Charger Aux Light Misc Advanced Logging Log2Pressing Back brings back the Logging screen LOG2 Daily peak Battery voltageOperational mode PkBatV Voc HiVoc 012.2 070.2 076.9PkBatV Voc HiVoc 012.2 070.2 Mppt Sunrise Exit Next Auto RestartSecondary LOG2 Screen 0000 float Tmin HighWatts Lo 13.2 Hi DCkWhThis value is the peak daily Watts seen by the MX60 MICRO-HYDRO, Wind TURBINE, and Fuel Cell Applications MICRO-HYDRO and Fuel Cell Systems Performance OptimizationOutBack Power Systems Inc Advanced Menu Micro-Hydro Advanced Menu Park Mpp 77 % VOC Exit Next -Voc +Voc PV 087 Bat 12.0 05.0 a 35.8A Watts This page Intentionally Left Blank Application Notes Calling the Factory for Assistance Warranty Dimensions Weight SpecificationsVoltage step down capability Limit Absorb Float Amps Volts 60.0 14.4 13.660.00 MX60 Efficiency vs. Input Power Graph 24V and 48V Battery System Efficiency CurveUnderstanding the Various Operational Modes OutBack Power Systems Inc OutBack Power Systems Inc OutBack Power Systems Inc MATE-DISPLAYED MX60 Status Mode Screens MATE-DISPLAYED MX60 Status Meter Screens MATE-DISPLAYED MX60 Status Setpt Setpoint Screens Troubleshooting Guide OutBack Power Systems Inc OutBack Power Systems Inc OutBack Power Systems Inc Typical Array Sizing Guide Standard vs. Australian Default Settings Standard version% Voltage Drop 12, 24 or 48 Volt Battery System Volt PV Array 80V MPP Typical Wire and Disconnect Sizing MX60 MULTI-STAGE Battery Charging OutBack Power Systems Inc Average = 95˚ F / 35˚ C Battery Temperature Compensated Volatge SET PointAverage = 86˚ F / 30˚ C Suggested Battery Charger SET Points TWO Year Limited Warranty Information OutBack Power Systems Inc EU Declaration of Conformity OWNER’S System Information Inverter/Chargers Product RegistrationProducts Covered Serial Number REV B