Carrier GT-PX, GT-S, GT-G specifications CXM Controls, Safety Features CXM Control

Page 43

CXM Controls

Indoor & Outdoor Split Geothermal Comfort Systems

Safety Features – CXM Control

The safety features below are provided to protect the compressor, heat exchangers, wiring and other components from damage caused by operation outside of design conditions.

Anti-short cycle protection: The control features a 5 minute anti-short cycle protection for the compressor. Note: The 5 minute anti-short cycle also occurs at power up. Random start: The control features a random start upon power up of 5-80 seconds.

Fault Retry: In Fault Retry mode, the Status LED begins slowly flashing to signal that the control is trying to recover from a fault input. The control will stage off the outputs and then “try again” to satisfy the thermostat input call. Once the thermostat input call is satisfied, the control will continue on as if no fault occurred.

If 3 consecutive faults occur without satisfying the thermostat input call, the control will go into “lockout” mode. The last fault causing the lockout will be stored in memory and can be viewed by going into test mode. Note: FP1/FP2 faults are factory set at only one try. Lockout: In lockout mode, the status LED will begin fast flashing. The compressor relay is turned off immediately. Lockout mode can be “soft” reset by turning off the thermostat (or satisfying the call). A “soft” reset keeps the fault in memory but resets the control. A “hard” reset (disconnecting power to the control) resets the control and erases fault memory.

Lockout with emergency heat: While in lockout mode, if W becomes active (CXM), emergency heat mode will occur. High pressure switch: When the high pressure switch opens due to high refrigerant pressures, the compressor relay is de-energized immediately since the high pressure switch is in series with the compressor contactor coil. The high pressure fault recognition is immediate (does not delay for 30 continuous seconds before de-energizing the compressor).

High pressure lockout code = 2

Example: 2 quick flashes, 10 sec pause, 2 quick flashes, 10 sec. pause, etc.

Low pressure switch: The low pressure switch must be open and remain open for 30 continuous seconds during “on” cycle to be recognized as a low pressure fault. If the low pressure switch is open for 30 seconds prior to compressor power up it will be considered a low pressure (loss of charge) fault. The low pressure switch input is bypassed for the initial 60 seconds of a compressor run cycle.

Low pressure lockout code = 3

Water coil low temperature (FP1): The FP1 thermistor temperature must be below the selected low temperature limit setting for 30 continuous seconds during a compressor run cycle to be recognized as a FP1 fault. The FP1 input is bypassed for the initial 60 seconds of a compressor run cycle. FP1 is set at the factory for one try. Therefore, the control will go into lockout mode once the FP1 fault has occurred.

FP1 lockout code = 4

Air coil low temperature (FP2): The FP2 thermistor temperature must be below the selected low temperature limit setting for 30 continuous seconds during a compressor run cycle to be recognized as a FP2 fault. The FP2 input is bypassed for the initial 60 seconds of a compressor run cycle. FP2 is set at the factory for one try. Therefore, the control will go into lockout mode once the FP2 fault has occurred.

FP2 lockout code = 5

Condensate overflow: The condensate overflow sensor must sense overflow level for 30 continuous seconds to be recognized as a CO fault. Condensate overflow will be monitored at all times.

CO lockout code = 6

Over/under voltage shutdown: An over/under voltage condition exists when the control voltage is outside the range of 19VAC to 30VAC. Over/under voltage shut down is a self-resetting safety. If the voltage comes back within range for at least 0.5 seconds, normal operation is restored. This is not considered a fault or lockout. If the CXM is in over/under voltage shutdown for 15 minutes, the alarm relay will close.

Over/under voltage shut down code = 7

Unit Performance Sentinel-UPS (patent pending): The UPS feature indicates when the heat pump is operating inefficiently. A UPS condition exists when:

a)In heating mode with compressor energized, FP2 is greater than 125°F [52°C] for 30 continuous seconds, or:

b)In cooling mode with compressor energized, FP1 is greater than 125°F [52°C] for 30 continuous seconds, or:

c)In cooling mode with compressor energized, FP2 is less than 40°F [4.5°C] for 30 continuous seconds. If a UPS condition occurs, the control will immediately go to UPS warning. The status LED will remain on as if the control is in normal mode. Outputs of the control, excluding LED and alarm relay, will NOT be affected by UPS. The UPS condition cannot occur during a compressor off cycle. During UPS warning, the alarm relay will cycle on and off. The cycle rate will be “on” for 5 seconds, “off” for 25 seconds, “on” for 5 seconds, “off” for 25 seconds, etc.

UPS warning code = 8

Swapped FP1/FP2 thermistors: During test mode, the control monitors to see if the FP1 and FP2 thermistors are in the appropriate places. If the control is in test mode, the control will lockout, with code 9, after 30 seconds if:

a)The compressor is on in the cooling mode and the FP1 sensor is colder than the FP2 sensor, or:

b)The compressor is on in the heating mode and the

FP2 sensor is colder than the FP1 sensor. Swapped FP1/FP2 thermistor code = 9.

Carrier Indoor & Outdoor Split Geothermal Heat Pumps - Rev.: 08/10/05

41

Image 43
Contents Geothermal Split Systems Carrier Page Table of Contents Environmentally Friendly Geothermal AdvantagesHighest Efficiency Maximum ComfortGround Water Systems Closed Loop SystemsPuron Refrigerant Rounding Out the Product LineFactory Quality Other New FeaturesService Advantages Application FlexibilityOptions & Accessories Features and Benefits Operating Efficiencies GT-GSSingle-Stage Indoor Split R22 Systems Why Paradigm Shift? What is the GT-S?GT-S Concept Typical GT-S / Add-on Coil Installation Typical GT-S / Air Handler InstallationInternally-mounted field installed Flow Controller Copeland Scroll Compressor Rotary GT-PX 50YDS Performance Data Metric SI Units GT-PX 50YDS Performance Data English IP UnitsGT-GS 50YCS & GT-S 38WQS Performance Data Metric SI Units GT-GS 50YCS & GT-S 38WQS Performance Data English IP UnitsModel Nomenclature 38WQS NomenclatureGT-GS & GT-S Performance Correction Factors CoolingEntering Air Correction Factors Airflow Correction FactorsPSI EER HWC LAT COP 50YDS026 Part Load With FV4003EER HWC LAT COP 50YDS026 Full Load With FV400350YDS038 Part Load With FV4005 PSI EER HWC LAT COP 50YDS038 Full Load With FV400550YDS049 Part Load With FV4006 50YDS049 Full Load With FV4006 GT-PX50YDS064 Part Load With FV4006 50YDS064 Full Load With FV4006 Cooling EAT 80/67 F 50YCS018 / 38WQS018 With GAH01850YCS024 / 38WQS024 With GAH024 CarrierEWT F GPM CFM PSI LAT COP HWC EER 50YCS030 / 38WQS030 With GAH030CFM PSI LAT COP HWC EER 50YCS036 / 38WQS036 With GAH036110 50YCS042 / 38WQS042 With GAH04250YCS048 / 38WQS048 With GAH048 2000 53.6 50YCS060 / 38WQS060 With GAH060GT-GS 50YCS Physical Data GT-PX 50YDS Physical DataGT-S 38WQS Physical Data GT-PX 50YDS Dimensional Data GT-PX Dimensional DataGT-GS 50YCS Dimensional Data GT-GS Dimensional DataGT-S 38WQS Dimensional Data GT-S Dimensional DataGT-S 38WQS Electrical Data Electrical DataGT-PX 50YDS Electrical Data GT-GS 50YCS Electrical DataThermostat Installation Thermostat WiringTypical Thermostat Wiring, Two-Stage Units 3 Heat / 2 Cool Typical Thermostat Wiring Infinity / Evolution ControlsCXM Controls CXM LED And Alarm Relay OperationsCXM Controls Safety Features CXM ControlCXM Control Start-up Operation Diagnostic FeaturesStat signal Unit OperationGT-PX Split Wiring Diagram GT-GS Split Wiring Diagram GT-S Split Wiring Diagram General Equipment SelectionEquipment Selection 22 Air Handler CharacteristicsAir Handler Selection Example Selecting Air HandlerElectrical GT-PX Split 50YDS SeriesCasing & Cabinet Refrigerant CircuitGT-GS GT-S Outdoor Split 38WQS Series Cooling TXV Kit field installed R-22 GT-GS & GT-S units only Thermostat field installedFlow Controller field installed Hose Kits field installed GT-PX & GT-GS onlyPage 7300 S.W th Street Oklahoma City, OK Phone Fax