Carrier GT-G, GT-S, GT-PX specifications Closed Loop Systems, Ground Water Systems

Page 5

Indoor & Outdoor Split Geothermal Comfort Systems

Closed Loop Systems

Closed Loop Systems consist of an underground heat exchange network of sealed, high strength polyethylene plastic pipe and a Flow Controller pumping module. When cooling, the loop fluid temperature will rise, and rejected heat is dissipated into the cooler earth. Conversely, while heating, the loop fluid temperatures fall, and heat is absorbed from the earth. Carrier Flow Controller pumping modules utilize small wattage pumps to circulate the water/antifreeze fluid within the piping system. The plastic heat exchange loop is closed and thermally fusion-welded at all connections in the same manner as natural gas distribution lines. Closed loops do not require a ground water supply or drain, and they are not subject to mineral build up.

Closed Loops can be installed in vertical or horizontal configurations, or submerged in a pond or lake. When designed properly, all three alternatives operate with similar efficiency. Carrier high density polyethylene plastic pipe is used for all closed loop installations. Pipe connections are heat fused to form joints that are stronger than the pipe itself. Carrier loop piping has a life expectancy in excess of 50 years.

Horizontal Loops are often considered when adequate land space

is available. The pipes are placed in trenches, excavated by a backhoe or chain trencher to a depth of 4-6 feet. Depending on design, from 1-6

pipes are installed in each trench. Multiple pipe and coiled “slinky” configurations are often used to conserve land requirements and reduce overall installed loop costs. Horizontal boring technology can also be used to install u-bend loops 10-15 feet deep with minimal landscaping disruption. Trench lengths range from 100-400 feet per system ton. Trenches must be spaced from 6-10 feet apart. The overall land area required ranges from 750-1,500 square feet per system ton.

Vertical Loops are the ideal choice when available land area is limited.

Drilling equipment is used to bore small- diameter vertical holes. Two pipes joined together with

au-bend fitting are inserted into the

vertical bore. Bore hole depth ranges from 100-300 feet per system ton. Bores must be spaced from 10-15 feet apart and properly grouted. The land space required ranges from 100-200 square feet per system ton.

Pond (Lake) Loops are very economical to install when a body of

surface water is available, because excavation costs are mostly eliminated. Coils or “slinky” mats of pipe are simply placed on the bottom

of the pond (lake). In most cases, 1/4 to 1/2 acre of water surface, with a minimum depth of 8-10 feet, is needed for a typical residence.

Ground Water Systems

Open loop systems utilize ground water as a direct energy source when

good quality water is available at a reasonable pumping depth. A well must have enough capacity to deliver a minimum of 1.5 gpm per system ton during peak

operation. Ditches, field tiles, ponds and streams are the most common discharge systems. Reinjection or semi-closed recirculation wells can also be utilized in some regions. In ideal conditions, an open loop application can be the most economical type of system to install.

Carrier Indoor & Outdoor Split Geothermal Heat Pumps - Rev.: 08/10/05

3

Image 5
Contents Geothermal Split Systems Carrier Page Table of Contents Highest Efficiency Geothermal AdvantagesMaximum Comfort Environmentally FriendlyGround Water Systems Closed Loop SystemsPuron Refrigerant Rounding Out the Product LineService Advantages Other New FeaturesApplication Flexibility Factory QualityOptions & Accessories Features and Benefits Operating Efficiencies GT-GSSingle-Stage Indoor Split R22 Systems GT-S Concept What is the GT-S?Why Paradigm Shift? Typical GT-S / Add-on Coil Installation Typical GT-S / Air Handler InstallationInternally-mounted field installed Flow Controller Copeland Scroll Compressor Rotary GT-PX 50YDS Performance Data Metric SI Units GT-PX 50YDS Performance Data English IP UnitsGT-GS 50YCS & GT-S 38WQS Performance Data Metric SI Units GT-GS 50YCS & GT-S 38WQS Performance Data English IP UnitsModel Nomenclature 38WQS NomenclatureGT-GS & GT-S Performance Correction Factors CoolingEntering Air Correction Factors Airflow Correction FactorsPSI EER HWC LAT COP 50YDS026 Part Load With FV4003EER HWC LAT COP 50YDS026 Full Load With FV400350YDS038 Part Load With FV4005 PSI EER HWC LAT COP 50YDS038 Full Load With FV400550YDS049 Part Load With FV4006 50YDS049 Full Load With FV4006 GT-PX50YDS064 Part Load With FV4006 50YDS064 Full Load With FV4006 Cooling EAT 80/67 F 50YCS018 / 38WQS018 With GAH01850YCS024 / 38WQS024 With GAH024 CarrierEWT F GPM CFM PSI LAT COP HWC EER 50YCS030 / 38WQS030 With GAH030CFM PSI LAT COP HWC EER 50YCS036 / 38WQS036 With GAH036110 50YCS042 / 38WQS042 With GAH04250YCS048 / 38WQS048 With GAH048 2000 53.6 50YCS060 / 38WQS060 With GAH060GT-S 38WQS Physical Data GT-PX 50YDS Physical DataGT-GS 50YCS Physical Data GT-PX 50YDS Dimensional Data GT-PX Dimensional DataGT-GS 50YCS Dimensional Data GT-GS Dimensional DataGT-S 38WQS Dimensional Data GT-S Dimensional DataGT-PX 50YDS Electrical Data Electrical DataGT-GS 50YCS Electrical Data GT-S 38WQS Electrical DataTypical Thermostat Wiring, Two-Stage Units 3 Heat / 2 Cool Thermostat WiringTypical Thermostat Wiring Infinity / Evolution Controls Thermostat InstallationCXM Controls CXM LED And Alarm Relay OperationsCXM Controls Safety Features CXM ControlStat signal Diagnostic FeaturesUnit Operation CXM Control Start-up OperationGT-PX Split Wiring Diagram GT-GS Split Wiring Diagram GT-S Split Wiring Diagram General Equipment SelectionEquipment Selection 22 Air Handler CharacteristicsAir Handler Selection Example Selecting Air HandlerCasing & Cabinet GT-PX Split 50YDS SeriesRefrigerant Circuit ElectricalGT-GS GT-S Outdoor Split 38WQS Series Flow Controller field installed Thermostat field installedHose Kits field installed GT-PX & GT-GS only Cooling TXV Kit field installed R-22 GT-GS & GT-S units onlyPage 7300 S.W th Street Oklahoma City, OK Phone Fax