Carrier GT-S, GT-PX, GT-G specifications CXM Controls, CXM LED And Alarm Relay Operations

Page 42

Carrier

CXM Controls

 

 

CXM Control

For detailed control information, see CXM/DXM Application, Operation and Maintenance (AOM) manual (part #97B0003N08).

Field Selectable Inputs

Test mode: Test mode allows the service technician to check the operation of the control in a timely manner. By momentarily shorting the test terminals, the CXM control enters a 20 minute test mode period in which all time delays are sped up 15 times. Upon entering test mode, the status LED will flash a code representing the last fault. For diagnostic ease at the thermostat, the alarm relay will also cycle during test mode. The alarm relay will cycle on and off similar to the status LED to indicate a code representing the last fault, at the thermostat. Test mode can be exited by shorting the test terminals for 3 seconds.

Retry Mode: If the control is attempting a retry of a fault, the status LED will slow flash (slow flash = one flash every 2 seconds) to indicate the control is in the process of retrying.

Field Configuration Options

Note: In the following field configuration options, jumper wires should be clipped ONLY when power is removed from the CXM control.

Water coil low temperature limit setting: Jumper 3 (JW3- FP1 Low Temp) provides field selection of temperature limit setting for FP1 of 30°F or 10°F [-1°F or -12°C] (refrigerant temperature).

Not Clipped = 30°F [-1°C]. Clipped = 10°F [-12°C]. Air coil low temperature limit setting: Jumper 2 (JW2- FP2 Low Temp) provides field selection of temperature limit setting for FP2 of 30°F or 10°F [-1°F or -12°C] (refrigerant temperature). Note: This jumper should only be clipped under extenuating circumstances, as recommended by the factory.

Not Clipped = 30°F [-1°C]. Clipped = 10°F [-12°C]. Alarm relay setting: Jumper 1 (JW1-AL2 Dry) provides field selection of the alarm relay terminal AL2 to

be jumpered to 24VAC or to be a dry contact (no connection).

Not Clipped = AL2 connected to R. Clipped = AL2 dry contact (no connection).

DIP Switches

Note: In the following field configuration options, DIP switches should only be changed when power is removed from the CXM control.

DIP switch 1: Unit Performance Sentinel Disable - provides field selection to disable the UPS feature. On = Enabled. Off = Disabled.

DIP switch 2: Stage 2 Selection - provides selection of whether compressor has an “on” delay. If set to stage

2, the compressor will have a 3 second delay before energizing. Also, if set for stage 2, the alarm relay will NOT cycle during test mode.

On = Stage 1. Off = Stage 2

DIP switch 3: Not Used.

DIP switch 4: DDC Output at EH2 - provides selection for DDC operation. If set to “DDC Output at EH2,” the EH2 terminal will continuously output the last fault code of the controller. If set to “EH2 normal,” EH2 will operate as standard electric heat output.

On = EH2 Normal. Off = DDC Output at EH2.

NOTE: Some CXM controls only have a 2 position DIP switch package. If this is the case, this option can be selected by clipping the jumper which is in position 4 of SW1.

Jumper not clipped = EH2 Normal. Jumper clipped = DDC Output at EH2.

DIP switch 5: Factory Setting - Normal position is “On.” Do not change selection unless instructed to do so by the factory.

CXM LED And Alarm Relay Operations

Description of Operation

LED

Alarm Relay

 

Normal Mode

On

Open

 

Normal Mode with UPS Warning

On

Cycle (closed 5 sec., Open 25 sec.)

 

CXM is non-functional

Off

Open

 

Fault Retry

Slow Flash

Open

 

Lockout

Fast Flash

Closed

 

Over/Under Voltage Shutdown

Slow Flash

Open (Closed after 15 minutes)

 

Test Mode - No fault in memory

Flashing Code 1

Cycling Code 1

 

 

 

 

 

Test Mode - HP Fault in memory

Flashing Code 2

Cycling Code 2

 

 

 

 

 

Test Mode - LP Fault in memory

Flashing Code 3

Cycling Code 3

 

 

 

 

 

Test Mode - FP1 Fault in memory

Flashing Code 4

Cycling Code 4

 

 

 

 

 

Test Mode - FP2 Fault in memory

Flashing Code 5

Cycling Code 5

 

 

 

 

 

Test Mode - CO Fault in memory

Flashing Code 6

Cycling Code 6

 

 

 

 

 

Test Mode - Over/Under

Flashing Code 7

Cycling Code 7

 

shutdown in memory

 

 

 

 

Test Mode - UPS in memory

Flashing Code 8

Cycling Code 8

 

 

 

 

 

Test Mode - Swapped Thermistor

Flashing Code 9

Cycling Code 9

 

 

 

 

 

 

 

 

 

-Slow Flash = 1 flash every 2 seconds -Fast Flash = 2 flashes every 1 second

-Flash code 2 = 2 quick flashes, 10 second pause, 2 quick flashes, 10 second pause, etc.

-On pulse 1/3 second; off pulse 1/3 second

40

Carrier Indoor & Outdoor Split Geothermal Heat Pumps - Rev.: 08/10/05

Image 42
Contents Geothermal Split Systems Carrier Page Table of Contents Maximum Comfort Geothermal AdvantagesHighest Efficiency Environmentally FriendlyClosed Loop Systems Ground Water SystemsRounding Out the Product Line Puron RefrigerantApplication Flexibility Other New FeaturesService Advantages Factory QualityOptions & Accessories Features and Benefits GT-GS Operating EfficienciesSingle-Stage Indoor Split R22 Systems What is the GT-S? Why Paradigm Shift?GT-S Concept Typical GT-S / Air Handler Installation Typical GT-S / Add-on Coil InstallationInternally-mounted field installed Flow Controller Copeland Scroll Compressor Rotary GT-PX 50YDS Performance Data English IP Units GT-PX 50YDS Performance Data Metric SI UnitsGT-GS 50YCS & GT-S 38WQS Performance Data English IP Units GT-GS 50YCS & GT-S 38WQS Performance Data Metric SI Units38WQS Nomenclature Model NomenclatureCooling GT-GS & GT-S Performance Correction FactorsAirflow Correction Factors Entering Air Correction Factors50YDS026 Part Load With FV4003 PSI EER HWC LAT COP50YDS026 Full Load With FV4003 EER HWC LAT COP50YDS038 Part Load With FV4005 50YDS038 Full Load With FV4005 PSI EER HWC LAT COP50YDS049 Part Load With FV4006 GT-PX 50YDS049 Full Load With FV400650YDS064 Part Load With FV4006 50YDS064 Full Load With FV4006 50YCS018 / 38WQS018 With GAH018 Cooling EAT 80/67 FCarrier 50YCS024 / 38WQS024 With GAH02450YCS030 / 38WQS030 With GAH030 EWT F GPM CFM PSI LAT COP HWC EER50YCS036 / 38WQS036 With GAH036 CFM PSI LAT COP HWC EER50YCS042 / 38WQS042 With GAH042 11050YCS048 / 38WQS048 With GAH048 50YCS060 / 38WQS060 With GAH060 2000 53.6GT-PX 50YDS Physical Data GT-GS 50YCS Physical DataGT-S 38WQS Physical Data GT-PX Dimensional Data GT-PX 50YDS Dimensional DataGT-GS Dimensional Data GT-GS 50YCS Dimensional DataGT-S Dimensional Data GT-S 38WQS Dimensional DataGT-GS 50YCS Electrical Data Electrical DataGT-PX 50YDS Electrical Data GT-S 38WQS Electrical DataTypical Thermostat Wiring Infinity / Evolution Controls Thermostat WiringTypical Thermostat Wiring, Two-Stage Units 3 Heat / 2 Cool Thermostat InstallationCXM LED And Alarm Relay Operations CXM ControlsSafety Features CXM Control CXM ControlsUnit Operation Diagnostic FeaturesStat signal CXM Control Start-up OperationGT-PX Split Wiring Diagram GT-GS Split Wiring Diagram GT-S Split Wiring Diagram Equipment Selection General22 Air Handler Characteristics Equipment SelectionSelecting Air Handler Air Handler Selection ExampleRefrigerant Circuit GT-PX Split 50YDS SeriesCasing & Cabinet ElectricalGT-GS GT-S Outdoor Split 38WQS Series Hose Kits field installed GT-PX & GT-GS only Thermostat field installedFlow Controller field installed Cooling TXV Kit field installed R-22 GT-GS & GT-S units onlyPage 7300 S.W th Street Oklahoma City, OK Phone Fax