| Performance Correction Factors | |||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Airflow Correction Factors |
|
|
|
|
|
|
| ||||||||
TT Full Load Air Flow Corrections |
|
|
|
|
|
|
|
| |||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| Airflow |
|
|
| Cooling |
|
|
| Heating |
|
|
| ||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| CFM Per | % of |
|
| Total Cap | Sens Cap | Power | Heat of Rej |
| Htg Cap | Power | Heat of Ext |
| |
|
| Ton of Clg | Nominal |
|
|
|
| ||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||
240 | 60 | 0.925 | 0.788 | 0.913 | 0.922 | 0.946 | 1.153 | 0.896 |
|
| |||||
|
| 275 | 69 |
|
| 0.946 | 0.829 | 0.926 | 0.942 |
| 0.959 | 1.107 | 0.924 |
|
|
|
| 300 | 75 |
|
| 0.960 | 0.861 | 0.937 | 0.955 |
| 0.969 | 1.078 | 0.942 |
|
|
|
| 325 | 81 |
|
| 0.972 | 0.895 | 0.950 | 0.968 |
| 0.977 | 1.053 | 0.959 |
|
|
|
| 350 | 88 |
|
| 0.983 | 0.930 | 0.965 | 0.979 |
| 0.985 | 1.032 | 0.974 |
|
|
|
| 375 | 94 |
|
| 0.992 | 0.965 | 0.982 | 0.990 |
| 0.993 | 1.014 | 0.988 |
|
|
|
| 400 | 100 |
|
| 1.000 | 1.000 | 1.000 | 1.000 |
| 1.000 | 1.000 | 1.000 |
|
|
|
| 425 | 106 |
|
| 1.007 | 1.033 | 1.020 | 1.009 |
| 1.006 | 0.989 | 1.011 |
|
|
|
| 450 | 113 |
|
| 1.012 | 1.064 | 1.042 | 1.018 |
| 1.012 | 0.982 | 1.019 |
|
|
|
| 475 | 119 |
|
| 1.016 | 1.092 | 1.066 | 1.025 |
| 1.018 | 0.979 | 1.027 |
|
|
|
| 500 | 125 |
|
| 1.018 | 1.116 | 1.091 | 1.032 |
| 1.022 | 0.977 | 1.033 |
|
|
520 | 130 | 1.019 | 1.132 | 1.112 | 1.037 | 1.026 | 0.975 | 1.038 |
|
| |||||
TT Part Load Air Flow Corrections |
|
|
|
|
|
|
|
| |||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||
|
| Airflow |
|
|
| Cooling |
|
|
| Heating |
|
|
| ||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| CFM Per | % of |
|
| Total Cap | Sens Cap | Power | Heat of Rej |
| Htg Cap | Power | Heat of Ext |
| |
|
| Ton of Clg | Nominal |
|
|
|
| ||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||
240 | 60 | 0.920 | 0.781 | 0.959 | 0.927 | 0.946 | 1.241 | 0.881 |
|
| |||||
| 275 | 69 |
| 0.942 | 0.832 | 0.964 | 0.946 | 0.960 | 1.163 | 0.915 |
|
| |||
| 300 | 75 |
| 0.956 | 0.867 | 0.969 | 0.959 | 0.969 | 1.115 | 0.937 |
|
| |||
| 325 | 81 |
| 0.969 | 0.901 | 0.975 | 0.970 | 0.978 | 1.076 | 0.956 |
|
| |||
| 350 | 88 |
| 0.981 | 0.934 | 0.982 | 0.981 | 0.986 | 1.043 | 0.973 |
|
| |||
| 375 | 94 |
| 0.991 | 0.967 | 0.990 | 0.991 | 0.993 | 1.018 | 0.988 |
|
| |||
| 400 | 100 |
| 1.000 | 1.000 | 1.000 | 1.000 | 1.000 | 1.000 | 1.000 |
|
| |||
| 425 | 106 |
| 1.007 | 1.033 | 1.011 | 1.008 | 1.006 | 0.990 | 1.010 |
|
| |||
| 450 | 113 |
| 1.013 | 1.065 | 1.023 | 1.015 | 1.012 | 0.986 | 1.017 |
|
| |||
| 475 | 119 |
| 1.018 | 1.098 | 1.036 | 1.021 | 1.017 | 0.983 | 1.024 |
|
| |||
| 500 | 125 |
| 1.021 | 1.131 | 1.051 | 1.026 | 1.021 | 0.981 | 1.030 |
|
| |||
520 | 130 | 1.023 | 1.159 | 1.063 | 1.030 | 1.024 | 0.979 | 1.034 |
|
|
Entering Air Correction Factors
TT Full Load Entering Air Corrections
Full Load Heating Corrections
Ent Air DB | Htg Cap | Power | Heat of | |
°F | Ext | |||
|
| |||
|
|
|
| |
40 | 1.052 | 0.779 | 1.120 | |
45 | 1.043 | 0.808 | 1.102 | |
50 | 1.035 | 0.841 | 1.084 | |
55 | 1.027 | 0.877 | 1.065 | |
60 | 1.019 | 0.915 | 1.045 | |
65 | 1.010 | 0.957 | 1.023 | |
68 | 1.004 | 0.982 | 1.010 | |
70 | 1.000 | 1.000 | 1.000 | |
75 | 0.989 | 1.045 | 0.974 | |
80 | 0.976 | 1.093 | 0.946 |
|
|
|
|
|
| Full Load Cooling Corrections |
|
|
|
|
| |||
|
|
|
|
|
|
|
|
|
|
|
| |||
|
|
|
| Sens Clg Cap Multipliers- Entering DB °F |
|
|
|
| ||||||
Ent Air | Total Clg |
|
|
|
|
|
|
|
|
|
|
| Power | Heat of |
|
|
|
|
|
|
|
|
|
|
| ||||
WB °F | Cap | 60 | 65 | 70 | 75 | 80 | 80.6 | 85 | 90 | 95 | 100 |
| Rej | |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
45 | 0.832 | 1.346 | 1.461 | 1.603 | * | * | * | * | * | * | * | 0.946 | 0.853 | |
50 | 0.850 | 1.004 | 1.174 | 1.357 | * | * | * | * | * | * | * | 0.953 | 0.870 | |
55 | 0.880 | 0.694 | 0.902 | 1.115 | 1.331 | * | * | * | * | * | * | 0.964 | 0.896 | |
60 | 0.922 |
| 0.646 | 0.875 | 1.103 | 1.329 | 1.356 | * | * | * | * | 0.977 | 0.932 | |
65 | 0.975 |
|
| 0.639 | 0.869 | 1.096 | 1.123 | 1.320 | * | * | * | 0.993 | 0.979 | |
66.2 | 0.990 |
|
| 0.582 | 0.812 | 1.039 | 1.066 | 1.262 | 1.482 | * | * | 0.997 | 0.991 | |
67 | 1.000 |
|
| 0.545 |
| 0.774 | 1.000 | 1.027 | 1.223 | 1.444 | * | * | 1.000 | 1.000 |
70 | 1.040 |
|
|
| 0.630 | 0.853 | 0.880 | 1.075 | 1.297 | 1.517 | * | 1.011 | 1.035 | |
75 | 1.117 |
|
|
|
|
| 0.601 | 0.627 | 0.821 | 1.046 | 1.275 | 1.510 | 1.033 | 1.101 |
* Sensible capacity equals total capacity (no latent capacity) at conditions shown as "*" |
|
|
|
| Rev.: 03/29/04 | |||||||||
ARI/ISO/ASHRAE |
|
|
|
TT Part Load Entering Air Corrections
Part Load Heating Corrections
Ent Air DB | Htg Cap | Power | Heat of | |
°F | Ext | |||
|
| |||
|
|
|
| |
40 | 1.084 | 0.732 | 1.161 | |
45 | 1.073 | 0.764 | 1.140 | |
50 | 1.060 | 0.802 | 1.117 | |
55 | 1.046 | 0.846 | 1.090 | |
60 | 1.031 | 0.893 | 1.061 | |
65 | 1.016 | 0.945 | 1.031 | |
68 | 1.006 | 0.978 | 1.013 | |
70 | 1.000 | 1.000 | 1.000 | |
75 | 0.984 | 1.058 | 0.968 | |
80 | 0.968 | 1.117 | 0.936 |
|
|
|
|
|
| Part Load Cooling Corrections |
|
|
|
|
| |||
|
|
|
|
|
|
|
|
|
|
|
| |||
|
|
|
| Sens Clg Cap Multipliers- Entering DB °F |
|
|
|
| ||||||
Ent Air | Total Clg |
|
|
|
|
|
|
|
|
|
|
| Power | Heat of |
|
|
|
|
|
|
|
|
|
|
| ||||
WB °F | Cap | 60 | 65 | 70 | 75 | 80 | 80.6 | 85 | 90 | 95 | 100 |
| Rej | |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
45 | 0.876 | 1.286 | 1.302 | 1.389 | * | * | * | * | * | * | * | 0.981 | 0.895 | |
50 | 0.883 | 1.002 | 1.099 | 1.241 | * | * | * | * | * | * | * | 0.985 | 0.901 | |
55 | 0.903 | 0.706 | 0.871 | 1.060 | 1.271 | * | * | * | * | * | * | 0.989 | 0.918 | |
60 | 0.935 |
| 0.617 | 0.844 | 1.079 | 1.319 | 1.349 | * | * | * | * | 0.993 | 0.945 | |
65 | 0.979 |
|
| 0.595 | 0.849 | 1.098 | 1.128 | 1.342 | * | * | * | 0.998 | 0.982 | |
66.2 | 0.991 |
|
| 0.531 | 0.789 | 1.040 | 1.070 | 1.284 | 1.522 | * | * | 0.999 | 0.993 | |
67 | 1.000 |
|
| 0.486 |
| 0.747 | 1.000 | 1.030 | 1.245 | 1.481 | * | * | 1.000 | 1.000 |
70 | 1.035 |
|
|
| 0.583 | 0.842 | 0.873 | 1.090 | 1.327 | 1.552 | * | 1.003 | 1.030 | |
75 | 1.105 |
|
|
|
|
| 0.552 | 0.584 | 0.811 | 1.057 | 1.290 | 1.510 | 1.008 | 1.088 |
* Sensible capacity equals total capacity (no latent capacity) at conditions shown as "*" |
|
|
|
| Rev.: 03/29/04 | |||||||||
ARI/ISO/ASHRAE |
|
|
|
18