Carrier GT-S, GT-PX, GT-G specifications Equipment Selection, General

Page 48

Carrier

Equipment Selection

 

 

The installation of geothermal heat pump units and all associated components, parts, and accessories which make up the installation shall be in accordance with the regulations of ALL authorities having jurisdiction and MUST conform to all applicable codes. It is the responsibility of the installing contractor to determine and comply with ALL applicable codes and regulations.

General

Proper indoor coil selection is critical to system efficiency. Using an older-model coil can affect efficiency and may not provide the customer with rated or advertised EER and COP. Coil design and technology have dramatically improved operating efficiency and capacity in the past 20 years. Homeowners using an older coil are not reaping these cost savings and comfort benefits. NEVER MATCH AN R-22 INDOOR COIL WITH AN R-410A

COMPRESSOR SECTION.

Newer indoor coils have a larger surface area, enhanced fin design, and grooved tubing. These features provide a larger area for heat transfer, improving efficiency and expanding capacity. Typical older coils may only have one-third to one-half the face area of these redesigned coils.

Indoor Coil Selection - GT-PX (50YDS) Puron® Geothermal Split System

Geothermal split system heat pumps are rated in the ARI directory with a specific indoor coil match. GT- PX Puron split system (50YDS) models are rated with Carrier/Bryant FV4 or FE4 series variable speed air handlers as shown in Table 1a. Other combinations (e.g. variable speed furnace with cased coil) may attain the same ARI ratings providing that the specifications meet or exceed those listed in Table 1a AND Table

1b. An ECM motor and TXV is required. Cap tubes and fixed orifices are not acceptable. PSC fans may be used if matched to Table 1b, but will not meet ARI ratings. If using PSC fan, compressor section must be operated as a single stage unit (i.e. wired for either 1st stage or 2nd stage). Without the ability to vary the airflow, supply air temperatures may not be acceptable if the compressor is allowed to change stages when used with a PSC fan motor.

GTTable-PX1a:AirGTHandler-PX (50YDS)MatchesPuron®for ARIGeothermalRatings Split System Air Handler Matches for ARI Ratings

Compressor Section

026

038

049

064

Air Handler

003

005

006

006

Model FV4 or FE4

 

 

 

 

Refrigerant

 

R-410A

 

Metering Device

 

TXV (required)

 

 

 

 

 

 

Air Coil

 

 

 

 

Type

Slope

A

A

A

Rows - Fins/in.

3 - 14.5

3 - 14.5

3 - 14.5

3 - 14.5

Face Area (sq. ft.)

3.46

5.93

7.42

7.42

 

 

 

 

 

Cabinet Configuration

Upflow / Downflow / Horizontal (Multipoise)

 

 

 

 

 

 

ECM Settings for

AC/HP size: 036

AC/HP size: 036

AC/HP size: 048

AC/HP size: 060

System Type:

System Type:

System Type:

System Type:

ARI Ratings

Comfort AC/HP

HP-Effic AC/HP

Comfort AC/HP

Comfort AC/HP

(FV4 Fan Coil)

CFM Adjust: Nom

CFM Adjust: High

CFM Adjust: High

CFM Adjust: High

 

 

 

 

 

 

Fan Motor Type - HP

ECM - 1/2

ECM - 1/2

ECM - 3/4

ECM - 3/4

 

 

 

 

 

46

Carrier Indoor & Outdoor Split Geothermal Heat Pumps - Rev.: 08/10/05

Image 48
Contents Geothermal Split Systems Carrier Page Table of Contents Geothermal Advantages Highest EfficiencyMaximum Comfort Environmentally FriendlyClosed Loop Systems Ground Water SystemsRounding Out the Product Line Puron RefrigerantOther New Features Service AdvantagesApplication Flexibility Factory QualityOptions & Accessories Features and Benefits GT-GS Operating EfficienciesSingle-Stage Indoor Split R22 Systems What is the GT-S? Why Paradigm Shift?GT-S Concept Typical GT-S / Air Handler Installation Typical GT-S / Add-on Coil InstallationInternally-mounted field installed Flow Controller Copeland Scroll Compressor Rotary GT-PX 50YDS Performance Data English IP Units GT-PX 50YDS Performance Data Metric SI UnitsGT-GS 50YCS & GT-S 38WQS Performance Data English IP Units GT-GS 50YCS & GT-S 38WQS Performance Data Metric SI Units38WQS Nomenclature Model NomenclatureCooling GT-GS & GT-S Performance Correction FactorsAirflow Correction Factors Entering Air Correction Factors50YDS026 Part Load With FV4003 PSI EER HWC LAT COP50YDS026 Full Load With FV4003 EER HWC LAT COP50YDS038 Part Load With FV4005 50YDS038 Full Load With FV4005 PSI EER HWC LAT COP50YDS049 Part Load With FV4006 GT-PX 50YDS049 Full Load With FV400650YDS064 Part Load With FV4006 50YDS064 Full Load With FV4006 50YCS018 / 38WQS018 With GAH018 Cooling EAT 80/67 FCarrier 50YCS024 / 38WQS024 With GAH02450YCS030 / 38WQS030 With GAH030 EWT F GPM CFM PSI LAT COP HWC EER50YCS036 / 38WQS036 With GAH036 CFM PSI LAT COP HWC EER50YCS042 / 38WQS042 With GAH042 11050YCS048 / 38WQS048 With GAH048 50YCS060 / 38WQS060 With GAH060 2000 53.6GT-PX 50YDS Physical Data GT-GS 50YCS Physical DataGT-S 38WQS Physical Data GT-PX Dimensional Data GT-PX 50YDS Dimensional DataGT-GS Dimensional Data GT-GS 50YCS Dimensional DataGT-S Dimensional Data GT-S 38WQS Dimensional DataElectrical Data GT-PX 50YDS Electrical DataGT-GS 50YCS Electrical Data GT-S 38WQS Electrical DataThermostat Wiring Typical Thermostat Wiring, Two-Stage Units 3 Heat / 2 CoolTypical Thermostat Wiring Infinity / Evolution Controls Thermostat InstallationCXM LED And Alarm Relay Operations CXM ControlsSafety Features CXM Control CXM ControlsDiagnostic Features Stat signalUnit Operation CXM Control Start-up OperationGT-PX Split Wiring Diagram GT-GS Split Wiring Diagram GT-S Split Wiring Diagram Equipment Selection General22 Air Handler Characteristics Equipment SelectionSelecting Air Handler Air Handler Selection ExampleGT-PX Split 50YDS Series Casing & CabinetRefrigerant Circuit ElectricalGT-GS GT-S Outdoor Split 38WQS Series Thermostat field installed Flow Controller field installedHose Kits field installed GT-PX & GT-GS only Cooling TXV Kit field installed R-22 GT-GS & GT-S units onlyPage 7300 S.W th Street Oklahoma City, OK Phone Fax