Carrier GT-G, GT-PX specifications GT-S Outdoor Split 38WQS Series

Page 53

GT-S Outdoor Split (38WQS) Series

Single-Stage Outdoor Split R22 Systems

General

The liquid source heating/cooling split condensing units shall be ARI/ASHRAE/ISO 13256-1 loop performance certified and listed by a nationally recognized safety- testing laboratory or agency, such as Underwriter’s Laboratory (UL), or Canadian Standards Association (CSA-US). Each unit shall be water run-tested at the factory. Each unit shall be pallet mounted and shipped in clear shrink wrap for visual shipping damage inspection. The units shall be warranted by the manufacturer against defects in materials and workmanship for a period of five years on all parts, and ten years on the compressor and refrigerant circuit parts with a service labor allowance during the first 30 days. An optional extended warranty is available for the GT-S Split Series units, which adds a labor allowance and trip charge. The liquid source units shall be designed to operate with entering liquid temperature between 20°F and 120°F.

Casing & Cabinet

The cabinet shall be weather resistant and designed for outdoor installations. The cabinet shall be fabricated from heavy-gauge galvanized steel painted with a epoxy powder coat paint with a 1000 hr. salt spray test rating. The interior shall be insulated with 1/2" thick, multi-density, coated glass fiber with edges sealed or tucked under flanges. Two compressor compartment access panels shall be provided and shall be removable with linesets and water piping in place. The internal component layout shall provide for major service with the unit in-place for restricted access installations. The cabinet shall provide adequate space to house the one or two pump Flow Controller pumping module within the cabinet.

Refrigerant Circuit

All units shall contain split refrigerant circuits employing a hermetically sealed compressor, thermal expansion valve, reversing valve, coaxial tube water-to-refrigerant heat exchanger, service ports, and backseating service valves. Compressors shall be high-efficiency advanced scroll or rotary type designed for heat pump duty and mounted on vibration isolators. Compressor motors shall be single phase PSC with internal overload protection. A factory installed bidirectional filter drier shall be provided. The coaxial water-to-refrigerant heat exchanger shall be designed for close approach temperatures and be constructed of a convoluted copper (optional cupronickel) inner tube and a steel outer tube. The thermal expansion valve shall provide proper superheat over the entire liquid temperature range with minimal “hunting”. The valve shall operate only in the heating mode with the use of an internal check valve. The water-to-refrigerant heat exchanger and refrigerant suction lines shall be insulated to prevent condensation at low liquid temperatures. Air coil connections shall

be made through brass backseating service valves with built-in Schrader ports. Hot Water Generator (desuperheater) connections shall be accomplished with 1/2” backseating service valves.

Electrical

CXM Control - A microprocessor-based compressor controller (CXM) shall be provided to monitor and control unit operation. The control shall provide high and low pressure monitoring, field selectable low water temperature sensing, over/under voltage monitoring, and unit performance sentinel (UPS). The control shall also provide for water valve connection, a test mode, short cycle protection, random start-up, as well as fault LED, fault memory, and intelligent fault retry.

The control shall employ quick attach harness assemblies for low voltage connections to the control board to aid in troubleshooting or replacement. An integral terminal block with screw terminals shall

be provided on the control for all field low voltage connections. Line voltage lugs shall be provided for unit wiring. Units shall have knockouts for entrance of low and line voltage wiring. The control box shall be harness plug-connected for easy removal.

Piping

Supply and return water connections shall be 1-1/4" MPT fittings. All water piping shall be insulated to prevent condensation at low liquid temperatures.

Carrier Indoor & Outdoor Split Geothermal Heat Pumps - Rev.: 08/10/05

51

Image 53
Contents Geothermal Split Systems Carrier Page Table of Contents Highest Efficiency Geothermal AdvantagesMaximum Comfort Environmentally FriendlyGround Water Systems Closed Loop SystemsPuron Refrigerant Rounding Out the Product LineService Advantages Other New FeaturesApplication Flexibility Factory QualityOptions & Accessories Features and Benefits Operating Efficiencies GT-GSSingle-Stage Indoor Split R22 Systems GT-S Concept What is the GT-S?Why Paradigm Shift? Typical GT-S / Add-on Coil Installation Typical GT-S / Air Handler InstallationInternally-mounted field installed Flow Controller Copeland Scroll Compressor Rotary GT-PX 50YDS Performance Data Metric SI Units GT-PX 50YDS Performance Data English IP UnitsGT-GS 50YCS & GT-S 38WQS Performance Data Metric SI Units GT-GS 50YCS & GT-S 38WQS Performance Data English IP UnitsModel Nomenclature 38WQS NomenclatureGT-GS & GT-S Performance Correction Factors CoolingEntering Air Correction Factors Airflow Correction FactorsPSI EER HWC LAT COP 50YDS026 Part Load With FV4003EER HWC LAT COP 50YDS026 Full Load With FV400350YDS038 Part Load With FV4005 PSI EER HWC LAT COP 50YDS038 Full Load With FV400550YDS049 Part Load With FV4006 50YDS049 Full Load With FV4006 GT-PX50YDS064 Part Load With FV4006 50YDS064 Full Load With FV4006 Cooling EAT 80/67 F 50YCS018 / 38WQS018 With GAH01850YCS024 / 38WQS024 With GAH024 CarrierEWT F GPM CFM PSI LAT COP HWC EER 50YCS030 / 38WQS030 With GAH030CFM PSI LAT COP HWC EER 50YCS036 / 38WQS036 With GAH036110 50YCS042 / 38WQS042 With GAH04250YCS048 / 38WQS048 With GAH048 2000 53.6 50YCS060 / 38WQS060 With GAH060GT-S 38WQS Physical Data GT-PX 50YDS Physical DataGT-GS 50YCS Physical Data GT-PX 50YDS Dimensional Data GT-PX Dimensional DataGT-GS 50YCS Dimensional Data GT-GS Dimensional DataGT-S 38WQS Dimensional Data GT-S Dimensional DataGT-PX 50YDS Electrical Data Electrical DataGT-GS 50YCS Electrical Data GT-S 38WQS Electrical DataTypical Thermostat Wiring, Two-Stage Units 3 Heat / 2 Cool Thermostat WiringTypical Thermostat Wiring Infinity / Evolution Controls Thermostat InstallationCXM Controls CXM LED And Alarm Relay OperationsCXM Controls Safety Features CXM ControlStat signal Diagnostic FeaturesUnit Operation CXM Control Start-up OperationGT-PX Split Wiring Diagram GT-GS Split Wiring Diagram GT-S Split Wiring Diagram General Equipment SelectionEquipment Selection 22 Air Handler CharacteristicsAir Handler Selection Example Selecting Air HandlerCasing & Cabinet GT-PX Split 50YDS SeriesRefrigerant Circuit ElectricalGT-GS GT-S Outdoor Split 38WQS Series Flow Controller field installed Thermostat field installedHose Kits field installed GT-PX & GT-GS only Cooling TXV Kit field installed R-22 GT-GS & GT-S units onlyPage 7300 S.W th Street Oklahoma City, OK Phone Fax