Inverter Mounting
and Installation
2–13

Determination of Wire and Fuse Sizes

The maximum motor currents in your application determines the recommended wire
size. The following table gives the wire size in AWG. The Power Lines column applies
to the inverter input power, output wires to the motor, the earth ground connection, and
any other component shown in the system wiring diagram on page 25. The “Signal
Lines column applies to any wire connecting to the two green 7 and 8-position connec-
tors just inside the front panel half-door.
Note 1: Field wiring must be made by a UL-listed and CSA-certified closed-loop
terminal connector sized for the wire gauge involved. Connector must be fixed by using
the crimping tool specified by the connector manufacturer.
Note 2: Be sure to consider the capacity of the circuit breaker to be used.
Note 3: Be sure to use larger wires for the power lines if the distance exceeds 20 meters.
(*) Use 18 AWG / 0.75 mm2 wire for the alarm signal wire (AL0, AL1, AL2 terminals).
Motor Output
(kW/HP) Inverter Model
Wiring Applicable
equipment
kW HP Power Lines Signal Lines Fuse (class J)
rated 600V
0.2 1/4 L100-002NFE/NFU
AWG16 / 1.3 mm2
(*)
18 to 28 AWG /
0.14 to 0.75 mm2
shielded wire
10A0.4 1/2 L100-004NFE/NFU
0.55 3/4 L100-005NFE
.75 1 L100-007NFE/NFU AWG14 / 2.1 mm215A
1.1 1 1/2 L100-011NFE
1.5 2 L100-015NFE/NFU AWG12 / 3.3 mm220 A (single ph.)
15A (three ph.)
2.2 3 L100-022NFE/NFU AWG10 / 5.3 mm230A (single ph.)
20A (three ph.)
3.7 5 L100-037LFU AWG12 / 3.3 mm230A
5.5 7 1/2 L100-055LFU AWG10 / 5.3 mm240A
7.5 10 L100-075LFU AWG8 / 8.4 mm250A
0.4 1/2 L100-004HFE/HFU
AWG16 / 1.3 mm2
3A
0.75 1 L100-007HFE/HFU 6A
1.5 2 L100-015HFE/HFU 10A
2.2 3 L100-022HFE/HFU
3.0 4 L100-030HFE AWG14 / 2.1 mm215A
4.0 5 L100-040HFE/HFU
5.5 7 1/2 L100-055HFE/HFU AWG12 / 3.3 mm220A
7.5 10 L100-075HFE/HFU 25A