L100 Inverter

2–23

Select the Potentiometer for Speed Command - the motor speed may be controlled from the following sources:

Potentiometer on front panel keypad

Control terminals

Remote panel

Then follow the steps in the table below to select the potentiometer for the speed command (the table resumes action from the end of the previous table).

 

 

Action

Display

 

Func./Parameter

 

 

 

 

 

 

 

 

 

 

Press the

2

key twice.

A 01

Speed command source setting

 

 

 

 

 

 

 

 

 

 

 

 

 

Press the FUNC. key.

01

0

= potentiometer

1

= control terminals (default)

 

 

 

 

2

= keypad

 

 

 

 

 

 

Press the

2

key.

00

0

= potentiometer (selected)

 

 

 

 

 

 

 

 

 

 

 

 

Press the STR

key.

A 01

Stores parameter, returns to “A”

group list

 

 

 

 

 

 

Select the Keypad for the RUN Command - the RUN command causes the inverter to accelerate the motor to the selected speed. You can program the inverter to respond to either the control terminal signal or the keypad RUN key.

Follow the steps in the table below to select the front panel RUN key as the source for the RUN Command (the table resumes action from the end of the previous table).

 

 

Action

Display

 

Func./Parameter

 

 

 

 

 

 

 

 

 

 

Press the

1

key.

A 02

Run command source

 

 

 

 

 

 

 

 

 

 

 

 

 

Press the FUNC. key.

01

1

= control terminals (default)

2

= keypad

 

 

 

 

 

 

Press the

1

key.

02

2

= keypad (selected)

 

 

 

 

 

 

 

 

 

 

 

 

Press the STR

key.

A 02

Stores parameter, returns to “A”

group list

 

 

 

 

 

 

 

 

 

 

 

 

NOTE: When you press the STR key in the last step above (and the display = 02), the Run Enable LED above the RUN switch on the keypad will turn ON. This is normal, and does not mean the motor is trying to run. It means that the RUN key is now enabled. DO NOT press the RUN key at this time — finish out the programming exercise first.

TIP: If you became lost during any of these steps, first observe the state of the PRG LED. Then study the keypad navigation on page 21 to determine the current state of the keypad controls and display. As long as you do not press the STR key, no parameters will be changed by keypad entry errors.

and Installation

Inverter Mounting

 

 

Page 54
Image 54
Hitachi L100 instruction manual Speed command source setting

L100 specifications

The Hitachi L100 series is a versatile range of variable frequency drives (VFDs) designed to enhance performance in various industrial applications. Known for their reliability and efficiency, these drives are widely used in motors for pumps, fans, compressors, and conveyors.

One of the main features of the Hitachi L100 is its impressive control capabilities. The drive supports both scalar and vector control modes, allowing for precise speed and torque management. This flexibility ensures optimal motor performance across different load conditions. Additionally, the L100 series offers an impressive speed range, which can accommodate a wide variety of applications, from low-speed to high-speed requirements.

The L100 is equipped with built-in functionality for energy saving. By utilizing advanced control algorithms and auto-tuning features, the drive optimizes energy consumption, reducing operational costs and contributing to improved overall system efficiency. The energy-saving mode is particularly beneficial in applications where load conditions frequently change.

Another hallmark of the Hitachi L100 is its robust communication capabilities. The drive supports various communication protocols including Modbus and Ethernet, making it easy to integrate into existing control systems. This connectivity allows for real-time monitoring and diagnostics, which aids in predictive maintenance and minimizes downtime.

In terms of user-friendliness, the L100 series includes a clear, intuitive keypad that simplifies programming and operation. The drive also features a wide range of customizable parameters, enabling users to easily tailor the settings to suit specific application requirements. Additionally, the inclusion of a customizable PID controller allows users to refine process control automatically.

Safety is a priority in the design of the Hitachi L100. The drive comes with various built-in safety features such as overvoltage, overload, and short-circuit protection, ensuring reliable operation in challenging environments. Furthermore, it complies with global safety standards, making it suitable for international applications.

Lastly, the L100's compact design ensures easy installation and minimizes the space required in control cabinets. This is especially advantageous in facilities where space is at a premium. Overall, the Hitachi L100 series represents a combination of advanced technology, user-friendly features, and reliable performance, making it a popular choice for industrial automation solutions.