Analog Input Operation

Analog Input Operation

The L100 inverters provide for analog input to command the inverter frequency output value. The analog input terminal group includes the L, OI, O, and H terminals on the control connector, which provide for Voltage [O] or Current [OI] input. All analog input signals must use the analog ground [L].

If you use either the voltage or current analog input, you must select one of them using the logic input terminal function [AT] analog type. If terminal [AT] is Off, the voltage input

[O]can command the inverter output frequency. If terminal [AT] is On, the current input [OI] can command the inverter output frequency. The [AT] terminal function is covered in the logic input section on page 4–15. Remember that you must also set A01 = 01 to select analog input as the frequency source.

H O OI L FM CM2 12 11

+V Ref.

Voltage input

Current input

A GND

V/I input

A01

 

 

 

select

 

 

 

Frequency

 

 

 

[AT]

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

setting

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

H O OI L FM CM2 12 11

4-20 mA, AT= On

+ –

0-10 V, AT= Off

 

Operations and Monitoring

NOTE: If no logic input terminal is configured for the [AT] function, then inverter sums the voltage and current input to determine the desired input value.

Using an external potentiometer is a popular

 

H

 

O

OI

L

FM

CM2

12

11

way to control the inverter output frequency

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(and a good way to learn how to use the

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

analog inputs). The potentiometer uses the

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

10V reference [H] and the analog ground [L]

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

for excitation, and the voltage input for the

1 to 2 k Ohms, 2 Watts

signal. By default, the [AT] terminal selects

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

the voltage input when it is Off. Take care to

use the proper resistance for the potentiometer, which is 1 to 2 k Ohms, 2 Watts.

Voltage Input – The voltage input circuit

 

 

H O OI L

FM CM2 12 11

uses terminals [L] and [O]. Attach the cable

 

 

shield wire only to terminal [L] on the

 

 

 

 

 

 

 

 

 

 

 

0 to 9.6 VDC,

 

 

 

 

 

 

 

 

 

 

 

 

inverter. Maintain the voltage within specifi-

 

 

 

 

 

 

 

 

 

 

 

0 to 10V nominal

cations (do not apply negative voltage).

 

 

 

 

+ –

 

 

 

 

 

 

 

 

 

 

 

Current Input – The current input circuit

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

H

O

OI

L

FM

CM2

12

11

 

uses terminals [OI] and [L]. The current come

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

from a sourcing type transmitter; a sinking

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

type will not work! This means the current

 

 

 

 

 

 

 

 

 

 

 

4 to 19.6 mA DC,

must flow into terminal [OI], and terminal [L]

 

 

 

 

 

 

 

 

 

 

 

4 to 20 mA nominal

 

 

 

 

 

 

 

 

 

is the return back to the transmitter. The input

See I/O specs on page 4–5.

impedance from [OI] to [L] is 250 Ohms.

 

Attach the cable shield wire only to terminal [L] on the inverter.

Page 115
Image 115
Hitachi L100 instruction manual Analog Input Operation

L100 specifications

The Hitachi L100 series is a versatile range of variable frequency drives (VFDs) designed to enhance performance in various industrial applications. Known for their reliability and efficiency, these drives are widely used in motors for pumps, fans, compressors, and conveyors.

One of the main features of the Hitachi L100 is its impressive control capabilities. The drive supports both scalar and vector control modes, allowing for precise speed and torque management. This flexibility ensures optimal motor performance across different load conditions. Additionally, the L100 series offers an impressive speed range, which can accommodate a wide variety of applications, from low-speed to high-speed requirements.

The L100 is equipped with built-in functionality for energy saving. By utilizing advanced control algorithms and auto-tuning features, the drive optimizes energy consumption, reducing operational costs and contributing to improved overall system efficiency. The energy-saving mode is particularly beneficial in applications where load conditions frequently change.

Another hallmark of the Hitachi L100 is its robust communication capabilities. The drive supports various communication protocols including Modbus and Ethernet, making it easy to integrate into existing control systems. This connectivity allows for real-time monitoring and diagnostics, which aids in predictive maintenance and minimizes downtime.

In terms of user-friendliness, the L100 series includes a clear, intuitive keypad that simplifies programming and operation. The drive also features a wide range of customizable parameters, enabling users to easily tailor the settings to suit specific application requirements. Additionally, the inclusion of a customizable PID controller allows users to refine process control automatically.

Safety is a priority in the design of the Hitachi L100. The drive comes with various built-in safety features such as overvoltage, overload, and short-circuit protection, ensuring reliable operation in challenging environments. Furthermore, it complies with global safety standards, making it suitable for international applications.

Lastly, the L100's compact design ensures easy installation and minimizes the space required in control cabinets. This is especially advantageous in facilities where space is at a premium. Overall, the Hitachi L100 series represents a combination of advanced technology, user-friendly features, and reliable performance, making it a popular choice for industrial automation solutions.