Hitachi L100 instruction manual Output Function Adjustment Parameters, Arv Acc, Arv Dec, Ov Pid

Models: L100

1 163
Download 163 pages 3.67 Kb
Page 90
Image 90

3–34

“C” Group: Intelligent Terminal Functions

Output Function Adjustment Parameters

The overload level parameter (C41)sets the motor current level at which the overload signal becomes true. The range of settings is from 0% to 200% of the rated current for the inverter. This function is for gener- ating an early warning logic output, without causing either a trip event or a restriction of the motor current (those effects are available on other functions).

Motor

C41

current

 

Overload

 

signal 1

0

time

Configuring

Drive Parameters

 

 

The frequency arrival signal is intended to indicate when the inverter output has reached (arrived at) the target frequency. You can adjust the timing of the leading and trailing edges of the signal via two parameters specific to acceleration and deceleration ramps, C42 and C43.

The Error for the PID loop is the magni- tude (absolute value) of the difference between the Setpoint (desired value) and Process Variable (actual value). The PID output deviation signal (output terminal function option code 04) indicates when the error magnitude has exceeded a magni- tude you define.

Output

C42

C43

frequency

 

Arrival

 

 

signal 1

0

time

PID Error

SP

 

(PV-SP)

C44

 

Deviation

Signal 1

0

time

 

 

“C” Function

Run-

Defaults

DOP,DRW,DOP+

 

 

 

 

 

 

 

 

 

 

 

Func.

Name

Description

time

EU/

Units

Func.

Name

 

 

Edit

 

 

Code

US

Code

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

C41

Overload level setting

Sets the overload signal level

(rated current

F-33

OV Load

 

 

 

 

between 0% and 200% (from 0

 

for each

 

 

 

 

 

 

to two times the rated current

 

inverter)

 

 

 

 

 

 

of the inverter)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

C42

Frequency arrival

Sets the frequency arrival

0.0

Hz

F-32

ARV ACC

 

 

 

setting for accel.

setting threshold for the output

 

 

 

 

 

 

 

 

 

frequency during acceleration

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

C43

Arrival frequency

Sets the frequency arrival

0.0

Hz

F-32

ARV DEC

 

 

 

setting for decel.

setting threshold for the output

 

 

 

 

 

 

 

 

 

frequency during deceleration

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

C44

PID deviation level

Sets the allowable PID loop

3.0

%

F-33

OV PID

 

 

 

setting

error magnitude (absolute

 

 

 

 

 

 

 

 

 

value), SP - PV, range is 0.0 to

 

 

 

 

 

 

 

 

 

100%, resolution is 0.1%

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Page 90
Image 90
Hitachi L100 instruction manual Output Function Adjustment Parameters, Arv Acc, Arv Dec, Ov Pid

L100 specifications

The Hitachi L100 series is a versatile range of variable frequency drives (VFDs) designed to enhance performance in various industrial applications. Known for their reliability and efficiency, these drives are widely used in motors for pumps, fans, compressors, and conveyors.

One of the main features of the Hitachi L100 is its impressive control capabilities. The drive supports both scalar and vector control modes, allowing for precise speed and torque management. This flexibility ensures optimal motor performance across different load conditions. Additionally, the L100 series offers an impressive speed range, which can accommodate a wide variety of applications, from low-speed to high-speed requirements.

The L100 is equipped with built-in functionality for energy saving. By utilizing advanced control algorithms and auto-tuning features, the drive optimizes energy consumption, reducing operational costs and contributing to improved overall system efficiency. The energy-saving mode is particularly beneficial in applications where load conditions frequently change.

Another hallmark of the Hitachi L100 is its robust communication capabilities. The drive supports various communication protocols including Modbus and Ethernet, making it easy to integrate into existing control systems. This connectivity allows for real-time monitoring and diagnostics, which aids in predictive maintenance and minimizes downtime.

In terms of user-friendliness, the L100 series includes a clear, intuitive keypad that simplifies programming and operation. The drive also features a wide range of customizable parameters, enabling users to easily tailor the settings to suit specific application requirements. Additionally, the inclusion of a customizable PID controller allows users to refine process control automatically.

Safety is a priority in the design of the Hitachi L100. The drive comes with various built-in safety features such as overvoltage, overload, and short-circuit protection, ensuring reliable operation in challenging environments. Furthermore, it complies with global safety standards, making it suitable for international applications.

Lastly, the L100's compact design ensures easy installation and minimizes the space required in control cabinets. This is especially advantageous in facilities where space is at a premium. Overall, the Hitachi L100 series represents a combination of advanced technology, user-friendly features, and reliable performance, making it a popular choice for industrial automation solutions.