CHAPTER 5: COMMUNICATIONS
5.2.2DNP Point Map Notes
1.Responds to Function 5 (direct operate), Qualifier Code 7 or 8, Control Code 3, Count 0, On 1 ms, Off 0 ms ONLY.
2.Responds to Function 6 (direct operate - no acknowledge), Qualifier Code 7, Control Code 3, Count 0, On 1 ms, Off 0 ms ONLY.
3.The multiplier =
4.Example: If energy format = 7.2 K and
5.Values greater than 150 V secondary read 32767.
6.Values greater than 300 V secondary read 32767.
7.Values greater than 10 A secondary read 32767. For the 1 A model, the multiplier is (2/ 32768) and values above 2 A secondary read 32767.
8.CT ratio = (numerator × multiplier) / denominator.
9.PT ratio = (numerator × multiplier) / denominator.
10.Clear via Function 2 (write), Qualifier Code 0.
EPM 6000 |