GE EPM 6000 Multi-function Power Metering System instruction manual Hex

Page 72

CHAPTER 5: COMMUNICATIONS

HEX

DESCRIPTION1

FORMAT

RANGE6

UNITS OR

COMMENTS

# REG

ADDRESS

 

 

 

RESOLUTION

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

FIXED DATA SECTION

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Identification Block

 

 

 

 

read-only

 

0000

-

0007

Meter Name

ASCII

16 char

 

none

 

8

0008

-

000F

Meter Serial Number

ASCII

16 char

 

none

 

8

0010

-

0010

Meter Type

UINT16

bit-mapped

 

-------t -----vvv

t = transducer model (1=yes, 0=no),

1

 

vvv = V-switch(1 to 4)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0011

-

0012

Firmware Version

ASCII

4 char

 

none

 

2

0013

-

0013

Map Version

UINT16

0 to 65535

 

none

 

1

0014

-

0014

Meter Configuration

UINT16

bit-mapped

 

-------- --ffffff

ffffff = calibration frequency (50 or 60)

1

 

 

 

 

 

 

 

 

 

 

 

 

0015

-

0015

ASIC Version

UINT16

0-65535

 

none

 

1

0016

-

0026

Reserved

 

 

 

 

 

17

0027

-

002E

GE Part Number

ASCII

16 char

 

none

 

8

 

 

 

 

 

 

 

 

Block Size:

47

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

METER DATA SECTION2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Primary Readings Block, 6 cycles (IEEE Floating Point)

 

 

read-only

 

0383

-

0384

Watts, 3-Ph total

FLOAT

-9999 M to +9999 M

 

watts

 

2

0385

-

0386

VARs, 3-Ph total

FLOAT

-9999 M to +9999 M

 

VARs

 

2

0387

-

0388

VAs, 3-Ph total

FLOAT

-9999 M to +9999 M

 

VAs

 

2

 

 

 

 

 

 

 

 

Block Size:

6

 

 

 

 

 

 

 

 

 

 

Primary Readings Block, 60 cycles (IEEE Floating Point)

 

 

read-only

 

03E7

-

03E8

Volts A-N

FLOAT

0 to 9999 M

 

volts

 

2

03E9

-

03EA

Volts B-N

FLOAT

0 to 9999 M

 

volts

 

2

03EB

-

03EC

Volts C-N

FLOAT

0 to 9999 M

 

volts

 

2

03ED

-

03EE

Volts A-B

FLOAT

0 to 9999 M

 

volts

 

2

03EF

-

03F0

Volts B-C

FLOAT

0 to 9999 M

 

volts

 

2

03F1

-

03F2

Volts C-A

FLOAT

0 to 9999 M

 

volts

 

2

03F3

-

03F4

Amps A

FLOAT

0 to 9999 M

 

amps

 

2

03F5

-

03F6

Amps B

FLOAT

0 to 9999 M

 

amps

 

2

03F7

-

03F8

Amps C

FLOAT

0 to 9999 M

 

amps

 

2

03F9

-

03FA

Watts, 3-Ph total

FLOAT

-9999 M to +9999 M

 

watts

 

2

03FB

-

03FC

VARs, 3-Ph total

FLOAT

-9999 M to +9999 M

 

VARs

 

2

03FD

-

03FE

VAs, 3-Ph total

FLOAT

-9999 M to +9999 M

 

VAs

 

2

03FF

-

0400

Power Factor, 3-Ph total

FLOAT

-1.00 to +1.00

 

none

 

2

0401

-

0402

Frequency

FLOAT

0 to 65.00

 

Hz

 

2

0403

-

0404

Neutral Current

FLOAT

0 to 9999 M

 

amps

 

2

 

 

 

 

 

 

 

 

Block Size:

30

 

 

 

 

 

 

 

 

 

 

Primary Energy Block

 

 

 

 

read-only

 

044B

-

044C

W-hours, Received

SINT32

0 to 99999999 or

0 to

Wh per energy format

* Wh received & delivered always

2

 

 

 

 

 

 

-99999999

 

 

have opposite signs

 

044D

-

044E

W-hours, Delivered

SINT32

0 to 99999999 or

0 to

Wh per energy format

* Wh received is positive for "view as

2

 

 

 

 

 

 

-99999999

 

 

load", delivered is positive for "view as

 

 

 

 

 

 

 

 

generator"

 

044F

-

0450

W-hours, Net

SINT32

-99999999 to 99999999

Wh per energy format

2

 

 

 

 

 

 

 

 

* 5 to 8 digits

 

0451

-

0452

W-hours, Total

SINT32

0 to 99999999

 

Wh per energy format

2

0453

-

0454

VAR-hours, Positive

SINT32

0 to 99999999

 

VARh per energy format

* decimal point implied, per energy

2

 

format

 

 

 

 

 

 

 

 

 

* resolution of digit before decimal

 

0455

-

0456

VAR-hours, Negative

SINT32

0 to -99999999

 

VARh per energy format

2

 

 

 

 

 

 

 

 

point = units, kilo, or mega, per energy

 

0457

-

0458

VAR-hours, Net

SINT32

-99999999 to 99999999

VARh per energy format

format

2

5–2

EPM 6000 MULTI-FUNCTION POWER METERING SYSTEM – USER GUIDE

Image 72
Contents Chapter Page Table of Contents Using the Meter Miscellaneous TOC-4 Introduction DescriptionHighlights EPM 6000 Highlights Features Universal Voltage InputsCurrent Inputs Utility Peak DemandMeasured Values EPM 6000 Measured ValuesOrdering Order CodesEPM 6000 Order Codes Specifications Inputs/OutputsMetering Environmental CommunicationsMechanical Parameters Type Testing ApprovalsThree-Phase Power Measurement Three-Phase System Configurations Wye ConnectionCommon Phase Voltages on Wye Services VcnThree-Phase Delta Winding Relationship Delta ConnectionBlondells Theorem and Three-Phase Measurement Three-Phase, Four-Wire Delta PhasorsPhase B Phase C Node n Phase a Electrical Background Power, Energy, and Demand PowerEnergy Power Use Over Time Power and Energy Relationship Over Time DemandEnergy Use and Demand Intervals Reactive Energy and Power Factor Real, Reactive, and Apparent PowerPower Factor Apparent powerHarmonic Distortion Harmonics of a Non-Sinusoidal WaveformInductive and Capacitive Impedance Voltage and Current MonitoringWaveform Capture Power Quality Typical Power Quality ProblemsElectrical Background Mechanical Installation DimensionsAnsi Installation Steps Ansi and DIN Mounting Panel CutoutsDIN Installation Steps Ansi Mounting ProcedureDIN Mounting Procedure Electrical Installation Installation ConsiderationsCT Leads Terminated to Meter CT Leads Pass-Through No Meter TerminationVoltage and Power Supply Connections Quick Connect Crimp CT TerminationsGround Connections Voltage ConnectionWiring Diagrams 2 Wye, 4-Wire with no PTs and 3 CTs, 3 Element 4-Wire Wye with no PTs and 3 CTs, 3 Element3 Wye, 4-Wire with no PTs and 3 CTs, 2.5 Element 10 4-Wire Wye with no PTs and 3 CTs, 2.5 Element4 Wye, 4-Wire with 3 PTs and 3 CTs, 3 Element 11 4-Wire Wye with 3 PTs and 3 CTs, 3 Element5 Wye, 4-Wire with 2 PTs and 3 CTs, 2.5 Element 12 4-Wire Wye with 2 PTs and 3 CTs, 2.5 ElementDelta, 3-Wire with no PTs and 2 CTs 13 3-Wire Delta with no PTs and 2 CTsDelta, 3-Wire with 2 PTs and 2 CTs 14 3-Wire Delta with 2 PTs and 2 CTsCurrent-Only Measurement Three-Phase Current-Only Measurement Dual-Phase Current-Only Measurement Single-Phase Communications Setup IrDA COM1 Port3 RS485 COM2 Port 16 RS485 Communications Installation Front Panel Interface Faceplate ElementsUsing the Meter Faceplate ButtonsPercentage of Load Bar % of Load Bar SegmentsWatt-Hour Accuracy Testing Verification EPM 6000 Accuracy Test ConstantsConfiguring the Meter via the Front Panel OverviewStart Up Reset Mode and Password Entry Main MenuUsing the Meter Using the Meter Changing Settings in Configuration Mode Configuring the Scroll FeatureProgramming the Configuration Mode Screens Configuring the CT Setting Configuring the PT Setting Value for amps is a product of the Ct-nand the Ct-SvaluesConfiguring the Connection Setting Configuring the Communication Port Setting Address Using the Meter Operating Mode Operating Mode Parameter ReadingsUsing the Meter Modbus Communications Memory Map DescriptionMemory Map HEX Range Units or Comments THD Block7 Description 1 Format Range 7532 PT denominator Modbus Memory Map Notes Secondary Readings SectionCommunications Modbus Memory Map Data Formats DNP Point Mapping DNP Point MapsDNP Point Mapping Sheet 1 DNP Point Mapping Sheet 2 DNP Point Map Notes DNP Implementation Data Link LayerTransport Layer Application Layer Following function codes are implemented on the EPMDNP Objects and Variations Binary Output Status Object 10, VariationControl Relay Output Object 12, Variation 4 32-Bit Binary Counter Without Flag Object 20, Variation 5 16-Bit Analog Input Without Flag Object 30, VariationClass 0 Data Object 60, Variation Internal Indications Object 80, VariationCommunications Navigation Maps IntroductionMain Menu Screens Main Menu NavigationOperating Mode Screens Operating Mode NavigationReset Mode Screens Reset Mode NavigationConfiguration Mode Screens Revision History Release DatesChanges to the Manual Major Updates for 1601-0215-A2 Warranty GE Multilin WarrantyIndex Irda Power Supply Wiring