CHAPTER 5: COMMUNICATIONS
5.3.4Application Layer
The application layer contains a header (request or response header, depending on direction) and data.
Application headers contain the application control field and the function code. For the application control field,
The following function codes are implemented on the EPM 6000.
•Read (function 1): Objects supporting the READ function are Binary Outputs (object 10), Counters (object 20), Analog Inputs (object 30), and Class (object 60). These Objects may be read either by requesting a specific variation available as listed in DNP Point Mapping on page
•Write (function 2): The Internal Indications object (object 80), supports the WRITE function.
•Direct Operate (function 5): The Control Relay Output object (object 12) supports the DIRECT OPERATE function.
•Direct Operate - No Acknowledgment (function 6): the Change to Modbus RTU protocol (object 12, point 1) supports the DIRECT OPERATE - NO ACKNOWLEDGMENT function.
•Response (function 129): Application responses from the EPM 6000 use the RESPONSE function.