Omega CN1166 manual Entry Into Configuration Mode, Hardware Definition Code

Page 18

3CONFIGURATION MODE

3.1ENTRY INTO CONFIGURATION MODE

Powe r-up the Profile Controlle r.

Within 30 secs. as 1st

key action after power-up.

 

 

To display

Value

 

 

 

Identifier

 

 

Profile Controller is in

HO LD DO WN

 

Configuration Mode and

SIMU LTAN EO U SLY

displays current input code

 

 

For five seconds

 

 

In Configurat ion Mode:

 

 

 

 

To confirm new

To select

 

To change value

value (upper

parameter

(upper display flashes)

display is static)

Figure 3-1 Entry into Configuration Mode

NOTE: Changes to the value/setting of certain Configuration Mode parameters (e.g. input range, output use and type) will cause the Set Up Mode parameters to be automatically set to their default values the next time Set Up Mode is entered (see also Volume II, beginning of Section 2).

3.2HARDWARE DEFINITION CODE

This parameter is a special facility in Configuration Mode, which is used to represent the hardware fitted (input type, Output 1 type, Output 2 type and Output 3 type); this must be compatible with the hardware actually fitted. For access to, and adjustment of, the Hardware Definition Code, see Figure 3-2 and Table 3-1.

S077-3

Volume I

3-1

Image 18
Contents Page Page RAMP/SOAK Profile Volume Installation & Configuration Instructions Volume Operating InstructionsContents Unpacking Procedure PANEL-MOUNTING the ControllerConnections and Wiring Rear Terminal Connections Thermocouple Input Mains Line Input2 24V Nominal AC/DC Supply RTD InputsRelay Outputs Linear InputsRemote Run/Hold Input SSR Drive OutputsDC Outputs 11 RS485 Serial Communications LinkInternal Links and Switches Removing the Profile Controller from ITS HousingRemoving the Output 2/Output 3 Option PCBs Replacing the Instrument in ITS Housing REMOVING/REPLACING the Output 2/OUTPUT 3 Option PCBsSelection of Input Type and Output 1 Type Input TypePrimary Output Output 1 Type CPU PCB Relay/SSR Drive/Solid State OutputOutput 2 TYPE/OUTPUT 3 Type Entry Into Configuration Mode Hardware Definition CodeConfigurat ion Mode Wit h Hardw are Definit ion Code displayedOption Selection Hardware Definition Code Input/Output Type SelectionConfiguration Mode Parameters Wit h Hardw are Definit ion Code displayedParameter AL1 OFF, AL2 OFF Parameter Page Exit from Configuration Mode Base Mode Modbus Communications Controller SET-UP ModeProgram Definition Mode CREATING/EDITING a Program Alphabetic IndexBase Mode Display Sequence no Program RunningReleasing a Program from Hold Starting a ProgramPutting a Program in Hold Aborting a ProgramDisplay Sequence Program Running Read Only whilst Program is running/heldRaPID Control Feature PRE-TUNE FeatureEngaging Both PRE-TUNE and RaPID Features Indication of PRE-TUNE and RaPID StatusRaPID Status when Viewing the Hardware Definition Code Hardware Definition Code has the following significanceManual Control Press till front panel shows Press or to change display toController SET-UP Mode Lower display = Parameter Function Adjustment Range Default Value Parameter DetailsON/OFF Parameter Function Adjustment Range Default Value Power Alarm Operation Deviation Exit from Controller SET-UP Mode When this display showsProgram Definition Mode CREATING/EDITING a Program EntryCreating a Program Basic GuidelinesDefining Segments Rate Mode To make a Soak segmentDefining Segments Time Mode Program Options Guaranteed Soak Band T p o i n tSegment Event Status Press key To display Default Values and Adjustment Ranges Exit from Program Define ModeIntroduction Modbus Functions SupportedMessage Formats Read Coil Status Read n Bits 01/02 CRC16Read Holding Registers Read n Words 03/04 Force Single Coil Write 1 BitPreset Single Register Write 1 Word 06 B Loopback Diagnostic TestPreset Multiple Registers Write n Words 16 B Error and Exception Responses CRC16 CalculationReversed BIT Order Used Parameter Numbers Bit Parameters Controller Status ByteWord Parameters Controller ParametersInstrument ID Parameters Volume O077-4 Profiler Commands Profiler Status ByteUniversal Input GeneralInput Range Remote RUN/HOLD Input Option SSR Drive/TTL OutputRelay Solid StateTypes Available Relay, SSR drive, solid state and DC Solid State SSR Drive/TTL Alarm Control Loop ControlPerformance Reference ConditionsPerformance Under Reference Conditions S077-A Volume Environmental See PerformancePhysical Appendix B Summary of Displays Program Define Mode Parameters Configuration Mode Parameters AppendixC RaPID Control Feature AT OFF Alphabetical Index S077-IDX Volume Making a Soak Segment S077-IDX Volume Unpacking Procedure Word Parameters II/4-8