Omega CN1166 manual Linear Inputs, Remote Run/Hold Input, Relay Outputs, SSR Drive Outputs

Page 10

1.3.5Linear Inputs

For linear mA input ranges, connection is made to Terminals 4 and 6 in the polarity shown in Figure 1-4. For linear mV and V ranges, connection is made to Terminals 4 and 5 in the polarity shown in Figure 1-4. For details of the linear input ranges available, refer to Appendix A.

1.3.6Remote Run/Hold Input

With this option fitted, Terminals 11 and 12 are used for external Run/Hold control of the currently-selected program; this has an effect identical to that of the front panel RUN key. These terminals may be connected to (a) the voltage-free contacts of a switch or relay, or (b) a TTL-compatible voltage. This is an edge-sensitive input for which the following convention has been adopted:

For TTL input, OFF = logic 1 and ON = logic 0

For a voltage-free input, OFF = open and ON = closed

Program control is as follows:

 

OFF-ON transition:

The currently-selected program will run (or

 

will resume running if it is currently held).

ON-OFF transition:

The currently-running program will be

 

held.

NOTE: When this input is used, the front panel RUN key can be used only to abort a program. Powering-up the Profile Controller whilst this input is ON will not cause a program to run. The RS485 Serial Communications option and the Remote Run/Hold option are mutually exclusive.

1.3.7Relay Outputs

The contacts are rated at 2A resistive at 120/240V AC.

1.3.8SSR Drive Outputs

These outputs produce a time-proportioned non-isolated DC signal (0 - 4.2V nominal into 1k￿ minimum).

1.3.9Solid State Outputs

These outputs provide up to 1A AC drive with a longer lifetime than an electromechanical relay. For further details, refer to Appendix A.

S077-1

Volume I

1-5

Image 10
Contents Page Page RAMP/SOAK Profile Volume Installation & Configuration Instructions Volume Operating InstructionsContents Unpacking Procedure PANEL-MOUNTING the ControllerConnections and Wiring Rear Terminal Connections Thermocouple Input Mains Line Input2 24V Nominal AC/DC Supply RTD InputsRelay Outputs Linear InputsRemote Run/Hold Input SSR Drive OutputsDC Outputs 11 RS485 Serial Communications LinkInternal Links and Switches Removing the Profile Controller from ITS HousingRemoving the Output 2/Output 3 Option PCBs Replacing the Instrument in ITS Housing REMOVING/REPLACING the Output 2/OUTPUT 3 Option PCBsSelection of Input Type and Output 1 Type Input TypePrimary Output Output 1 Type CPU PCB Relay/SSR Drive/Solid State OutputOutput 2 TYPE/OUTPUT 3 Type Entry Into Configuration Mode Hardware Definition CodeConfigurat ion Mode Wit h Hardw are Definit ion Code displayedOption Selection Hardware Definition Code Input/Output Type SelectionConfiguration Mode Parameters Wit h Hardw are Definit ion Code displayedParameter AL1 OFF, AL2 OFF Parameter Page Exit from Configuration Mode Base Mode Modbus Communications Controller SET-UP ModeProgram Definition Mode CREATING/EDITING a Program Alphabetic IndexBase Mode Display Sequence no Program RunningReleasing a Program from Hold Starting a ProgramPutting a Program in Hold Aborting a ProgramDisplay Sequence Program Running Read Only whilst Program is running/heldRaPID Control Feature PRE-TUNE FeatureEngaging Both PRE-TUNE and RaPID Features Indication of PRE-TUNE and RaPID StatusRaPID Status when Viewing the Hardware Definition Code Hardware Definition Code has the following significanceManual Control Press till front panel shows Press or to change display toController SET-UP Mode Lower display = Parameter Function Adjustment Range Default Value Parameter DetailsON/OFF Parameter Function Adjustment Range Default Value Power Alarm Operation Deviation Exit from Controller SET-UP Mode When this display showsProgram Definition Mode CREATING/EDITING a Program EntryCreating a Program Basic GuidelinesDefining Segments Rate Mode To make a Soak segmentDefining Segments Time Mode Program Options Guaranteed Soak Band T p o i n tSegment Event Status Press key To display Default Values and Adjustment Ranges Exit from Program Define ModeModbus Functions Supported IntroductionMessage Formats Read Coil Status Read n Bits 01/02 CRC16Read Holding Registers Read n Words 03/04 Force Single Coil Write 1 BitLoopback Diagnostic Test Preset Single Register Write 1 Word 06 BPreset Multiple Registers Write n Words 16 B Error and Exception Responses CRC16 CalculationReversed BIT Order Used Parameter Numbers Bit Parameters Controller Status ByteWord Parameters Controller ParametersInstrument ID Parameters Volume O077-4 Profiler Commands Profiler Status ByteUniversal Input GeneralInput Range Remote RUN/HOLD Input Option SSR Drive/TTL OutputRelay Solid StateTypes Available Relay, SSR drive, solid state and DC Solid State SSR Drive/TTL Alarm Control Loop ControlReference Conditions PerformancePerformance Under Reference Conditions S077-A Volume See Performance EnvironmentalPhysical Appendix B Summary of Displays Program Define Mode Parameters Configuration Mode Parameters AppendixC RaPID Control Feature AT OFF Alphabetical Index S077-IDX Volume Making a Soak Segment S077-IDX Volume Unpacking Procedure Word Parameters II/4-8