(mV) input, alarms operate as if the
Input Range | Displayed Code  | Input Range  | Displayed Code  | 
  | 
  | 
  | 
  | 
0 - 20mA  | 3413  | 0 - 5V  | 4445  | 
4 - 20mA *  | 3414  | 1 - 5V  | 4434  | 
0 - 50mV  | 4443  | 0 - 10V *  | 4446  | 
10 - 50mV  | 4499  | 2 - 10V  | 4450  | 
  | 
  | 
  | 
  | 
* Default
process variable has gone 
DC Linear: Ranges Selectable from Front Panel:
(Changes may also be required to the CPU PCB link jumpers - see Volume I Subsection 2.5.1.)
Scale Range Maximum:  | Decimal point as required.  | |
Scale Range Minimum:  | Decimal point as for Scale  | |
  | Range Maximum.  | |
Minimum Span:  | 1 display LSD.  | 
  | 
Sensor Break Protection:  | Applicable to 4 - 20mA, 1 - 5V and 2 - 10V  | |
  | ranges only. Break detected within two  | |
seconds. Control outputs set to OFF (0% power); Alarms operate as if the process variable has gone 
REMOTE RUN/HOLD INPUT (OPTION)
Type:  | |
  | |
  | |
  | program will run or (if currently held)  | 
  | resume running.  | 
  | |
  | program will be held.  | 
Connection to contacts of external switch  | |
  | or relay; contacts open = OFF (minimum  | 
  | contact resistance = 5000), contacts  | 
  | closed = ON (maximum contact resistance  | 
  | = 50).  | 
TTL levels:  | OFF:   | 
  | ON: 2.0V to 24V  | 
Volume II  |