3.2CREATING A PROGRAM

A program is created in two steps:

1.Define the segments of your program; the parameters used depend on what Program Mode has been configured - Rate Mode (see Subsection 3.2.2) or Time Mode (see Subsection 3.2.3). The segment definitions determine whether the selected segment is a Ramp Segment, a Soak Segment or an End Segment.

2.Set the required Program Options (see Subsection 3.2.4). These determine:

(i) The number of cycles performed by the program,

(Ii) The timebase to be used (hours/minutes or minutes/seconds) (Iii) The width of the Guaranteed Soak Band (if enabled),

(Iv) The state of the event indicator for each segment in the program,

(v)The lock code to be used for subsequent entries into Program Define Mode.

3.2.1Basic Guidelines

1.The Ramp/Soak Profile Controller may contain up to four programs.

2.Each program may comprise up to 16 segments.

3.Each segment may be:

(a)a Ramp Segment (setpoint changing at a defined rate or between the initial value and a pre-determined final value over a defined time),

(b)a Soak Segment (setpoint constant for a defined time,) or

(c)an End Segment (marking the end of the program).

4.A program may contain only one End Segment (the last segment in the program).

5.If the program comprises 16 segments, Segment 16 is automatically an End Segment.

O077-3

Volume II

3-2

Image 47
Contents Page Page RAMP/SOAK Profile Volume Operating Instructions Volume Installation & Configuration InstructionsContents PANEL-MOUNTING the Controller Unpacking ProcedureConnections and Wiring Rear Terminal Connections RTD Inputs Mains Line Input2 24V Nominal AC/DC Supply Thermocouple InputSSR Drive Outputs Linear InputsRemote Run/Hold Input Relay Outputs11 RS485 Serial Communications Link DC OutputsRemoving the Profile Controller from ITS Housing Internal Links and SwitchesRemoving the Output 2/Output 3 Option PCBs REMOVING/REPLACING the Output 2/OUTPUT 3 Option PCBs Replacing the Instrument in ITS HousingInput Type Selection of Input Type and Output 1 TypeCPU PCB Relay/SSR Drive/Solid State Output Primary Output Output 1 TypeOutput 2 TYPE/OUTPUT 3 Type Hardware Definition Code Entry Into Configuration ModeWit h Hardw are Definit ion Code displayed Configurat ion ModeHardware Definition Code Input/Output Type Selection Option SelectionWit h Hardw are Definit ion Code displayed Configuration Mode ParametersParameter AL1 OFF, AL2 OFF Parameter Page Exit from Configuration Mode Base Mode Alphabetic Index Controller SET-UP ModeProgram Definition Mode CREATING/EDITING a Program Modbus CommunicationsDisplay Sequence no Program Running Base ModeAborting a Program Starting a ProgramPutting a Program in Hold Releasing a Program from HoldRead Only whilst Program is running/held Display Sequence Program RunningPRE-TUNE Feature RaPID Control FeatureIndication of PRE-TUNE and RaPID Status Engaging Both PRE-TUNE and RaPID FeaturesRaPID Status when Hardware Definition Code has the following significance Viewing the Hardware Definition CodePress till front panel shows Press or to change display to Manual ControlController SET-UP Mode Lower display = Parameter Details Parameter Function Adjustment Range Default ValueON/OFF Parameter Function Adjustment Range Default Value Power Alarm Operation Deviation When this display shows Exit from Controller SET-UP ModeEntry Program Definition Mode CREATING/EDITING a ProgramBasic Guidelines Creating a ProgramTo make a Soak segment Defining Segments Rate ModeDefining Segments Time Mode Program Options T p o i n t Guaranteed Soak BandSegment Event Status Press key To display Exit from Program Define Mode Default Values and Adjustment RangesMessage Formats IntroductionModbus Functions Supported CRC16 Read Coil Status Read n Bits 01/02Force Single Coil Write 1 Bit Read Holding Registers Read n Words 03/04Preset Multiple Registers Write n Words 16 B Preset Single Register Write 1 Word 06 BLoopback Diagnostic Test CRC16 Calculation Error and Exception ResponsesReversed BIT Order Used Bit Parameters Controller Status Byte Parameter NumbersController Parameters Word ParametersInstrument ID Parameters Volume O077-4 Profiler Status Byte Profiler CommandsGeneral Universal InputInput Range Remote RUN/HOLD Input Option Solid State OutputRelay SSR Drive/TTLTypes Available Relay, SSR drive, solid state and DC Solid State SSR Drive/TTL Loop Control Alarm ControlPerformance Under Reference Conditions PerformanceReference Conditions S077-A Volume Physical EnvironmentalSee Performance Appendix B Summary of Displays Program Define Mode Parameters Configuration Mode Parameters AppendixC RaPID Control Feature AT OFF Alphabetical Index S077-IDX Volume Making a Soak Segment S077-IDX Volume Unpacking Procedure Word Parameters II/4-8