Omega CN1166 manual Preset Single Register Write 1 Word 06 B, Loopback Diagnostic Test

Page 58

D. Preset Single Register (Write 1 Word)

06 B

The message sent to the controller consists of 8 bytes: the address and function number as usual, the address of the parameter to be written, and the two-byte value to which the parameter will be set, and finally the CRC16.

Addr.

Func.

Addr. of Word

 

Value

CRC16

 

 

 

 

 

 

 

 

 

 

6

HI

LO

HI

 

LO

HI

LO

 

 

 

 

 

 

 

 

 

The normal response is to echo the message in its entirety.

E. Loopback Diagnostic Test

08

The controller is sent an 8 byte message consisting of the usual preamble, a two-byte diagnostic code, and two bytes of data, followed by the CRC16.

Addr.

Func.

Diag. Code

 

Value

CRC16

 

 

 

 

 

 

 

 

 

 

8

HI

LO

HI

 

LO

HI

LO

 

 

 

 

 

 

 

 

 

Full MODBUS support in this area is not appropriate - consequently, the only Diagnostic Code supported is code 00. In response to the message, the controller must echo the message received exactly.

F. Preset Multiple Registers (Write n Words) 16 B

This message consists of eleven bytes. Only one parameter may be written at a time, even though this function number is supported. The preamble is followed by the address of the parameter to be written, and then a two-byte word count (always set to 1) and a single-byte byte count (always set to 2). Finally, the value to be written is followed by the CRC16.

Addr.

Func.

Addr. of Word

No. of Words

Count

 

 

 

 

 

 

 

 

16

HI

LO

0

1

2

 

 

 

 

 

 

 

 

Value

CRC16

 

 

 

 

HI

LO

HI

LO

The controller normally responds with a eight-byte reply, as follows:

Addr.

Func.

Addr. of Word

No. of Words

CRC16

 

 

 

 

 

 

 

 

 

16

HI

LO

0

1

HI

LO

 

 

 

 

 

 

 

 

4-4

Volume II

O077-4

Image 58
Contents Page Page RAMP/SOAK Profile Volume Installation & Configuration Instructions Volume Operating InstructionsContents Unpacking Procedure PANEL-MOUNTING the ControllerConnections and Wiring Rear Terminal Connections Thermocouple Input Mains Line Input2 24V Nominal AC/DC Supply RTD InputsRelay Outputs Linear InputsRemote Run/Hold Input SSR Drive OutputsDC Outputs 11 RS485 Serial Communications LinkInternal Links and Switches Removing the Profile Controller from ITS HousingRemoving the Output 2/Output 3 Option PCBs Replacing the Instrument in ITS Housing REMOVING/REPLACING the Output 2/OUTPUT 3 Option PCBsSelection of Input Type and Output 1 Type Input TypePrimary Output Output 1 Type CPU PCB Relay/SSR Drive/Solid State OutputOutput 2 TYPE/OUTPUT 3 Type Entry Into Configuration Mode Hardware Definition CodeConfigurat ion Mode Wit h Hardw are Definit ion Code displayedOption Selection Hardware Definition Code Input/Output Type SelectionConfiguration Mode Parameters Wit h Hardw are Definit ion Code displayedParameter AL1 OFF, AL2 OFF Parameter Page Exit from Configuration Mode Base Mode Modbus Communications Controller SET-UP ModeProgram Definition Mode CREATING/EDITING a Program Alphabetic IndexBase Mode Display Sequence no Program RunningReleasing a Program from Hold Starting a ProgramPutting a Program in Hold Aborting a ProgramDisplay Sequence Program Running Read Only whilst Program is running/heldRaPID Control Feature PRE-TUNE FeatureEngaging Both PRE-TUNE and RaPID Features Indication of PRE-TUNE and RaPID StatusRaPID Status when Viewing the Hardware Definition Code Hardware Definition Code has the following significanceManual Control Press till front panel shows Press or to change display toController SET-UP Mode Lower display = Parameter Function Adjustment Range Default Value Parameter DetailsON/OFF Parameter Function Adjustment Range Default Value Power Alarm Operation Deviation Exit from Controller SET-UP Mode When this display showsProgram Definition Mode CREATING/EDITING a Program EntryCreating a Program Basic GuidelinesDefining Segments Rate Mode To make a Soak segmentDefining Segments Time Mode Program Options Guaranteed Soak Band T p o i n tSegment Event Status Press key To display Default Values and Adjustment Ranges Exit from Program Define ModeModbus Functions Supported IntroductionMessage Formats Read Coil Status Read n Bits 01/02 CRC16Read Holding Registers Read n Words 03/04 Force Single Coil Write 1 BitLoopback Diagnostic Test Preset Single Register Write 1 Word 06 BPreset Multiple Registers Write n Words 16 B Error and Exception Responses CRC16 CalculationReversed BIT Order Used Parameter Numbers Bit Parameters Controller Status ByteWord Parameters Controller ParametersInstrument ID Parameters Volume O077-4 Profiler Commands Profiler Status ByteUniversal Input GeneralInput Range Remote RUN/HOLD Input Option SSR Drive/TTL OutputRelay Solid StateTypes Available Relay, SSR drive, solid state and DC Solid State SSR Drive/TTL Alarm Control Loop ControlReference Conditions PerformancePerformance Under Reference Conditions S077-A Volume See Performance EnvironmentalPhysical Appendix B Summary of Displays Program Define Mode Parameters Configuration Mode Parameters AppendixC RaPID Control Feature AT OFF Alphabetical Index S077-IDX Volume Making a Soak Segment S077-IDX Volume Unpacking Procedure Word Parameters II/4-8